The SuperEvac

  PLUS II pump is a 2-stage 

ro tary vane design (at right) that increases 

efficiency and speeds pump down to 15 

microns. 
The pump lowers the internal pressure of 

a refrigeration system until moisture boils 

into a vapor. As the moisture is vaporized, 

it is evacuated by the pump to help dehy-

drate the system. Most technicians try to 

achieve between 250 and 1000 microns. 
A manometer or electronic vacuum gauge 

are the only ways to monitor evacua-

tion progress. Manometer readings are 

approximate in inches of mercury. Only an 

electronic vacuum gauge (see page 8) is 

accurate enough to show when you reach 

the desired mi cron range. 
As the chart shows, only an electronic 

gauge reads fine differences to provide 

assurance that the vacuum is low enough 

to boil the greatest possible amount of 

moisture.

The Purpose of the SuperEvac

 PLUS II Design

How one small drop dampens 

your profits. 

A small drop of moisture can hurt your 

profits and reputation. 
During new system set-up, protective caps 

are removed admitting moisture and air 

into system components.

First stage exhausts into the intake of the second stage 
similar to two single stage pumps connected together. 

If air – a non-condensable – remains in the 

system, it collects on the high side reduc-

ing system efficiency. This causes a rise 

in head pressure. The discharge valve gets 

hotter than normal and organic solids form 

causing compressor failure. 
Moisture in the system can form ice which 

closes off openings in expansion valves 

and cap tubes, and prevent adequate 

cooling. 
Ultimately moisture and air can produce 

acids  and  sludge  which  could  cause           

in -warranty  failures. 
During service and parts replacement, 

the same contaminants get in again, and 

you could be called back for repairs by a 

dissatisfied customer. 
Moisture and air can even enter through 

system leaks. And as the moisture in 

the air increases, so does the amount of 

contamination. The higher the humidity, 

the bigger your problem. 
A vacuum pump “pulls” air and moisture 

out of the system before the system is 

damaged. The higher and more complete 

the vacuum, the more moisture is 
removed. That’s why your SuperEvac

  

PLUS II pump is specifically engineered for 

high vacuums of 15 microns and better.

4

Boiling Temp 

of Water

Inches 

Mercury

Microns

212°F (100°C)

0

760,000

151°F (66°C)

22.05

200,000

101°F (38°C)

27.95

50,000

78°F (26°C)

28.95

25,000

35°F (2°C)

29.72

5,000

1°F (17°C)

29.88

1,000

-50°F (-46°C)

29.92

50

Summary of Contents for 93714

Page 1: ...I Vacuum Pump Operation and Maintenance Manual Models 9371x 9374x 9376x 9378x 9379x PN 143060_RevB 5 Commonwealth Ave Woburn MA 01801 Phone 781 665 1400 Toll Free 1 800 517 8431 Visit us at www TestEq...

Page 2: ...arrange inspection of the pump and packaging The CARRIER ALONE is responsible for handling and settling your claim Ritchie Engineering will cooperate in assessing damage if the pump is returned to the...

Page 3: ...motor can run on voltage as low as 85 volts with no issue and draws fewer amps than AC motors Large Impact Resistant Toughened Nylon Feet Reduces vibration and increases durability and longevity Help...

Page 4: ...d stage similar to two single stage pumps connected together If air a non condensable remains in the system it collects on the high side reduc ing system efficiency This causes a rise in head pressure...

Page 5: ...uum just prior to shut off 7 Disconnect pump and put cap on intake to keep out contaminants 8 If an extension cord is needed refer to the below chart for proper sizing 6 Use the 4 in 1 Vacuum Charge V...

Page 6: ...3 Replace cover and screw down by hand Do not use drill as cover could crack CAUTION Always remove cord before changing voltage Incorrect voltage setting can result in destruction of controller elect...

Page 7: ...mosphere and switch on pump run up to speed before connecting to system Four Most Common Comments on Pump Return Paperwork Your SuperEvac PLUS II pump features a heavy duty high torque motor for cold...

Page 8: ...dropped Micron gauge malfunction Poor motor performance Dirty oil Air leaks System leaks Fitting sealant compound Call factory Verify with second gauge Repair or replace Flush 1 to 3 times Repair or...

Page 9: ...coupling Replace motor Tighten bolts Adjust replace coupling Pump Cartridge Dirt low improper oil Air leaks 1 Caps connections 2 Gaskets O rings 3 Fittings 4 System leak Flush and replace oil Tighten...

Page 10: ...92741 92741 3 Oil fill cap and seal 93390 93390 93390 93390 4 Oil fill fitting 93391 93391 93391 93391 5 Pair of sight glass screws 92933 92933 92933 92933 6 Sight glass bezel 92934 92934 92934 92934...

Page 11: ...93366 93366 22 Complete parts for blank off 93367 93367 93367 93367 Motor 23 SuperEvac Universal Motor 93713 93713 93713 93713 24 Locking IEC to NEMA 5 15 92755 92755 92755 92755 25 Locking IEC to UK...

Page 12: ...tion products within warranty period Returns must be prepaid Warranty does not cover use of lithium bromide ammonia or leak stop type products How to Obtain Service Most returned pumps are merely in n...

Reviews: