LCD Error Messages and Potential Solution

 

Error 

Possible Causes 

Possible Solutions 

Hi Pressure Limit 

• 

Service valves on hoses closed 

• 

Open valves 

 

• 

Schrader core on A/C system not depressing 

• 

Replace Schrader core 

Tank Empty 

• 

No refrigerant in storage tank 

• 

Refill storage tank using Mode 6, Tank Refill 

 

• 

Tank not properly on scale 

• 

Reposition scale 

 

• 

Scale cord not properly connected 

• 

Check scale cord connection 

 

• 

Scale is out of calibration 

• 

Re-calibrate scale using Utility Mode 

Supply Tank Empty 

• 

Tank of new refrigerant is empty 

• 

Close supply tank valve and disconnect hoses. If 
tank is not empty, see “Refrigerant not being trans-
ferred during Tank Refill.”  

Tank Full 

• 

Tank is 80% full 

• 

Charge some refrigerant or transfer to another tank. 

 

• 

Scale is out of calibration 

• 

Re-calibrate scale using Utility Mode 

 

• 

Tank not properly on scale 

• 

Reposition tank 

Time Limit (during 
charging cycles) 

• 

Tank on unit is closed 

• 

Default time limit is too short 

• 

Open tank valve 

• 

Use default time of 10 minutes unless A/C system 

 

• 

Compressor not running 

• 

Call Technical Services 

 

• 

Tank or scale misaligned 

• 

Reposition tank and scale 

Time Limit (during 
recovery cycle) 

• 

A/C system has a leak 

• 

Locate and repair leak 

 

• 

Valves on service hoses shut 

• 

Open valves 

 

• 

Service hose is constricted 

• 

Straighten hose 

 

• 

Unit storage tank valve is closed 

• 

Open tank valves 

 

• 

Compressor not operating 

• 

Call Technical Services 

No Scale 

• 

Scale cord not connected 

• 

Properly connect cord 

 

• 

Scale cord damaged 

• 

Call Technical Services 

 

• 

Microprocessor malfunction 

• 

Call Technical Services 

No Tank 

• 

Tank is not on scale 

• 

Place tank on scale 

 

• 

Scale out of calibration 

• 

Calibrate scale using Utility Mode 

Possible Overcharge 

• 

Tank was disturbed during charging cycle 

• 

Re-start Full Cycle 

 

• 

Internal failure of unit 

• 

Call Technical Services 

Accum Time Limit 

• 

Internal failure of unit 

• 

Call Technical Services 

Accum Hi Pressure 

• 

Internal failure of unit 

• 

Call Technical Services 

Purge “Y” 

• 

Non-condensable gases are present in     
storage tank 

• 

Turn unit off and on to start purge cycle 

Purge “N” 

• 

Non-condensable gases are NOT present in 
storage tank 

• 

Normal condition 

Purge “E” 

• 

Time limit was reached before purge cycle 
was complete. 

• 

Turn unit off/on to start purge cycle.  If “E” remains 
after three on-off cycles, contact Technical Support. 

Summary of Contents for 39800

Page 1: ...Automatic Refrigerant Recovery Recycling Recharge System Model 39800 Operation Manual For Automotive Applications YELLOW JACKET...

Page 2: ...ath Deliberate inhalation of refrigerants is extremely dangerous Death can occur without warning Vapors reduce oxygen available for breathing and are heavier than air Decomposi tion products are hazar...

Page 3: ...nting when disconnecting from the automobile Only Use the Model 800 Series with the Correct Refrigerants See the specifications for a list of compatible refrigerants Operate the Unit within the Design...

Page 4: ...uge 3 Low Gauge 4 Auto High Side Hose Red 5 Auto Low Side Hose Blue 6 Tank Liquid Hose Red 7 Tank Vapor Hose Blue 8 Oil Drain Bottle 9 Oil Inject Bottle 10 Tool Tray 11 Main Power Switch 12 Oil Inject...

Page 5: ...bile A C system This mode is most often used prior to opening an A C system to atmosphere to replace a system component 2 MODE 2 Vacuum is used to vacuum air from a system previously opened to the atm...

Page 6: ...now be used to aid investigation of an A C system problem Ensure the automobile A C system is turned off prior to selecting a mode on the 800 SERIES 2 Connect the high and low side auto service hoses...

Page 7: ...until the desired time is shown Release the button and press ENTER to accept the vacuum time shown on the LCD By pass vacuum time by setting time to zero 8 When the LCD reads SET VACUUM HOLD TIME set...

Page 8: ...ned to remove and recycle all refrigerant in an A C system by transferring the refrigerant to the storage tank remove moisture in the system by pulling a vacuum and charging the system with a precise...

Page 9: ...Tank Refill In order to use the charging mode you must have at least six 6 pounds of refrigerant in the storage tank Follow this procedure to add refrigerant to the storage tank When adding R 134a to...

Page 10: ...GEMENT SYSTEM Press INCREASE or DECREASE to cycle through the registers The registers are Register 1 Total number of jobs to date Register 2 Cumulative run time in minutes Register 3 Refrigerant recov...

Page 11: ...Vacuum Pump Oil Pressing the ENTER key will turn the reminder off un til the next time you start the unit Pressing the RE SET key will reset the reminder until the next sched uled maintenance Check o...

Page 12: ...not responding call Technical Support Call Technical Support Call Technical Support Call Technical Support Fan not running in any cycle Loose power wire to fan Microprocessor malfunction Fan malfunct...

Page 13: ...ng Call Technical Services Tank or scale misaligned Reposition tank and scale Time Limit during recovery cycle A C system has a leak Locate and repair leak Valves on service hoses shut Open valves Ser...

Page 14: ...tory for repair If found defective we will upon compliance with the return instructions either credit replace or repair at our option the defective product provided it is returned within one year of t...

Reviews: