Common Problems and Potential Solution

 

Problem 

Possible Causes 

Possible Solutions 

37880 cannot pull auto-
mobile A/C system into 
a vacuum 



Service valves on hoses not properly installed



Service ball valve seals are worn.



Hoses on unit are loose or leak.



Automobile A/C system has a leak.



Check valve seals and threads and replace if needed.



Replace valve seals and Schrader core depressor.



Tighten or replace hoses on unit.



Find and repair leak in A/C system.

High side gauge      
readings above normal 



Restriction in A/C system or Schrader core.



Service hose ball valve closed.



Incorrect charge amount entered in unit.



Check hose connection and fix restriction. Replace
Schrader core. 



Open the valve.



Recover, check scale calibration, and recharge
system. 

Refrigerant not being 
transferred during Tank 
Refill.  



Valve on supply tank closed.



Ball valve on blue service hose closed or
hose is constricted. 



Wrong hose installed on new refrigerant tank.



Storage tank is full.



Open Valve.



Open valve or straighten hose.



Install blue service hose on refrigerant tank.



Close valve on new supply. Disconnect service hose.

Touch Pad will not    
accept commands 



Key on touch pad is stuck.



Bad Touch Pad.



Wire disconnected between touch pad and
microprocessor. 



Microprocessor malfunction.



Feel for non-responsive key. If not responding, call
Technical Support. 



Call Technical Support.



Call Technical Support.



Call Technical Support.

Fan not running in any 
cycle 



Loose power wire to fan.



Microprocessor malfunction.



Fan malfunction.



Locate loose fitting and reconnect.



Call Technical Support.



Call Technical Support.

Machine will not turn on 



Power cord is not plugged into a 120 Volt
outlet. 



Circuit breaker tripped on shop power panel.



Bad Main Power switch.



Loose wire.



Bad Transformer on microprocessor board.



Plug into outlet.



Reset circuit breaker. If circuit breaker immediately
trips, do not reset.  Consult a qualified electrician. 



Call Technical Support.



Repair loose wire.



Call Technical Support.

Unit will not recover  
refrigerant from A/C  
system 



Valves on service hoses shut.



Service hose is constricted.



Unit storage tank valve is closed.



Open valves.



Straighten hose.



Open tank valves.



Compressor not operating.



Call Technical Support.

Unit will not charge    
refrigerant into vehicle 



Valves on service hoses shut



Service hose is constricted



Unit storage tank valve is closed



Open valves



Straighten hose



Open tank valves



Compressor not operating



Call Technical Support.

Refrigerant leaking   
during charging 



Service valves on hoses not properly installed
on  A/C system. 



Check valve seals and threads and replace if needed.



Service ball valve seals are worn.



Replace valve seals and Schrader core depressor



Hoses on unit are loose or leak.



Tighten or replace hoses on unit



Automobile A/C system has a leak



Find leak in A/C system and repair.

Troubleshooting Information

 

The 37880 has a number of sophisticated features which 
make it by far the most user friendly A/C service system in 
the world. The unit was designed for easy operation, service 
and troubleshooting. Although the 37880 was manufactured 
with high quality components, a component failure could 
cause it to operate incorrectly.     

The following section is designed to provide you with addi-
tional information to help diagnose a system. If a problem 
occurs, please read this section thoroughly prior to calling 
technical support. This will reduce the time needed to restore 
your system to normal operation. Our technical support num-
ber is (800)769-8370. 

Summary of Contents for 37880 Series

Page 1: ...y Recycling Recharge System Operation Manual 37880 37881 37882 37887 37888 37889 37880 Series YELLOW JACKET 99 Washington Street Melrose MA 02176 Phone 781 665 1400 Toll Free 1 800 517 8431 Visit us a...

Page 2: ...th Deliberate inhalation of refrigerants is extremely danger ous Death can occur without warning Vapors reduce oxygen available for breathing and are heavier than air Decomposition products are hazard...

Page 3: ...r form is a po tentially hazardous material Please consult the manufac turer s Material Safety Data Sheet for additional informa tion and adhere to the following safety guidelines Avoid breathing high...

Page 4: ...3 Low Gauge 4 Auto High Side Hose Red 5 Auto Low Side Hose Blue 6 Tank Vapor Hose Red 7 Tank Liquid Hose Blue 8 Oil Drain Bottle 9 Oil Inject Bottle excluded on 37887 and 37888 10 Tool Tray 11 Main P...

Page 5: ...ystem compo nent 2 Option 2 Vacuum is used to vacuum air moisture from a system previously opened to the atmos phere This Option will then proceed to recharge the A C system This Option also allows th...

Page 6: ...r to selecting a mode on the machine 3 Connect the high and low side auto service hoses to the respective high and low side service ports on the automobile A C system Open the service hose valves 4 Pr...

Page 7: ...IES AND MY CAUSE DAMAGE TO OTHER AUTOMOBILES THAT YOU SERVICE IN THE FUTURE RECOVER cont VACUUM The vacuum function of the 37880 SERIES is designed to remove air moisture from the automobile A C syste...

Page 8: ...0 1 Verify the auto air conditioning system is off 2 Select CHARGE option from the main menu 3 When the LCD reads SET CHARGE AMOUNT set the amount of refrigerant to be charged into the A C system by u...

Page 9: ...e If vacuum hold time was set to zero the unit will transition into charge mode 11 Record the final vacuum level shown on the low pressure gauge If the two recorded levels are dif ferent the A C syste...

Page 10: ...hybrid A C system can cause serious issues with the electrical system Having too much of the wrong type of oil in a hybrid A C system can conduct the electricity to the outside of the A C compressor S...

Page 11: ...l low the instructions on the screen and the unit will clear itself automatically Repeat the identification process to insure the proper identification of the refrigerant purity level If the unit fail...

Page 12: ...e free The filters must be changed periodically to ensure the system is working properly A maintenance reminder prompts you when to change your filters All refrigerant must be removed from the old fil...

Page 13: ...d maintenance Check oil level when pump is running When pump is running oil level should be 1 2 to 5 8 up in the sight glass This level is necessary for proper op eration This maintenance is best perf...

Page 14: ...a 120 Volt outlet Circuit breaker tripped on shop power panel Bad Main Power switch Loose wire Bad Transformer on microprocessor board Plug into outlet Reset circuit breaker If circuit breaker immedi...

Page 15: ...ALIBRATION ERROR 6 TANK EMPTY REFRIGERANT BELOW 5 OF TANK CAPACITY REFILL TANK CHECK SCALE CALIBRATION ERROR 7 NOT ENOUGH REFRIGERANT UNIT IS LOW ON REFRIGERANT 10 LB MIN REFILL TANK ERROR 8 TANK REFI...

Page 16: ...e we will upon compliance with the return instructions either credit replace or repair at our option the defective product provided it is returned within one year of the date of factory shipment 90 da...

Reviews: