yellow jacket 37880 Series Operation Manual Download Page 12

12 

Purging Non-Condensable Gases

 

The 37880 is designed to automatically purge non-
condesable gases such as air present in the storage 
tank. When the pressure in the tank exceeds a treshold 
value, the unit will automatically purge the excess 
pressure. The unit will only purge when it is first turned 
on. The current purge status is displayed in the bottom 
right corner of the LCD when in Select Mode. 

The purge status should be either 

“Y”, “N”, 

or 

“E.” 

“Y” 

indicates air is present in the tank. The unit will 

purge the next time it is turned off and on.  An 

“N” 

in 

the window indicates a purge is not needed.   

An 

“E” 

will display on the LCD if the previous purge 

was insufficient to lower the non-condensable gas 

value below the limit. The purge time is set to 15 
seconds to minimize refrigerant loss. If the LCD 
continues to display an 

“E” 

after several purge cycles, 

there may be an error in the system. Check the 
pressure in the tank to determine if the system is 
purging unnecessarily.   

contact Ritchie Engineering Customer Service at (800)
769-8370. 

The best time to check the purge function is after       
the unit has sat overnight and the tank temperature     
is stable.   

Maintenance Reminders

 

FILTER - 

 MAINTENACE WARNING! CHANGE FIL-

TER DRIER

 

The 37880 has a unique filter system which ensures 
the refrigerant transferred to the storage cylinder is 
clean and moisture-free. The filters must be changed 
periodically to ensure the system is working properly.   
A maintenance reminder prompts you when to change 
your filters. All refrigerant must be removed from the  
old filters before they are removed. Follow the filter 
change procedures carefully to minimize refrigerant 
loss and ensure only clean, moisture-free refrigerant    
is transferred into the storage cylinder. 

The new J2788 standard requires that the unit lock out 
if the filter drier is not replaced at the proper interval. 
The unit will prompt you when it is near the end of its 
life. When the filter drier reaches 100 lbs of refrigerant 
processed it will warn the user that it is nearing the end 
of its life. When the filter drier reaches 150 lbs of refrig-
erant processed it will lock the user out and require a 
filter change before the unit can be used again. The 
filter driers are marked with a unique code that will be 
required to unlock the unit. 

Check Filter Life –

  



Select the REF MANAGEMENT option in the main 
menu. 



Press the RIGHT ARROW key to view the remain-
ing filter life. 

Filter Change Procedure before Scheduled Filter 
Change. 

Follow these steps to change the filter drier 

before the scheduled filter change: 



Hold down DOWN ARROW key and turn main 
power switch on. 



When display reads “INPUT SERIAL NUMBER”  
enter serial number using the keypad. 

Filter Change Procedure if Filter Lock Out is 
reached. 



When the display reads “ MAINTENACE WARN-
ING! CHANGE FILTER DRIER” 



Press Enter key to enter filter change mode.  



Enter serial number using the keypad 

Summary of Contents for 37880 Series

Page 1: ...y Recycling Recharge System Operation Manual 37880 37881 37882 37887 37888 37889 37880 Series YELLOW JACKET 99 Washington Street Melrose MA 02176 Phone 781 665 1400 Toll Free 1 800 517 8431 Visit us a...

Page 2: ...th Deliberate inhalation of refrigerants is extremely danger ous Death can occur without warning Vapors reduce oxygen available for breathing and are heavier than air Decomposition products are hazard...

Page 3: ...r form is a po tentially hazardous material Please consult the manufac turer s Material Safety Data Sheet for additional informa tion and adhere to the following safety guidelines Avoid breathing high...

Page 4: ...3 Low Gauge 4 Auto High Side Hose Red 5 Auto Low Side Hose Blue 6 Tank Vapor Hose Red 7 Tank Liquid Hose Blue 8 Oil Drain Bottle 9 Oil Inject Bottle excluded on 37887 and 37888 10 Tool Tray 11 Main P...

Page 5: ...ystem compo nent 2 Option 2 Vacuum is used to vacuum air moisture from a system previously opened to the atmos phere This Option will then proceed to recharge the A C system This Option also allows th...

Page 6: ...r to selecting a mode on the machine 3 Connect the high and low side auto service hoses to the respective high and low side service ports on the automobile A C system Open the service hose valves 4 Pr...

Page 7: ...IES AND MY CAUSE DAMAGE TO OTHER AUTOMOBILES THAT YOU SERVICE IN THE FUTURE RECOVER cont VACUUM The vacuum function of the 37880 SERIES is designed to remove air moisture from the automobile A C syste...

Page 8: ...0 1 Verify the auto air conditioning system is off 2 Select CHARGE option from the main menu 3 When the LCD reads SET CHARGE AMOUNT set the amount of refrigerant to be charged into the A C system by u...

Page 9: ...e If vacuum hold time was set to zero the unit will transition into charge mode 11 Record the final vacuum level shown on the low pressure gauge If the two recorded levels are dif ferent the A C syste...

Page 10: ...hybrid A C system can cause serious issues with the electrical system Having too much of the wrong type of oil in a hybrid A C system can conduct the electricity to the outside of the A C compressor S...

Page 11: ...l low the instructions on the screen and the unit will clear itself automatically Repeat the identification process to insure the proper identification of the refrigerant purity level If the unit fail...

Page 12: ...e free The filters must be changed periodically to ensure the system is working properly A maintenance reminder prompts you when to change your filters All refrigerant must be removed from the old fil...

Page 13: ...d maintenance Check oil level when pump is running When pump is running oil level should be 1 2 to 5 8 up in the sight glass This level is necessary for proper op eration This maintenance is best perf...

Page 14: ...a 120 Volt outlet Circuit breaker tripped on shop power panel Bad Main Power switch Loose wire Bad Transformer on microprocessor board Plug into outlet Reset circuit breaker If circuit breaker immedi...

Page 15: ...ALIBRATION ERROR 6 TANK EMPTY REFRIGERANT BELOW 5 OF TANK CAPACITY REFILL TANK CHECK SCALE CALIBRATION ERROR 7 NOT ENOUGH REFRIGERANT UNIT IS LOW ON REFRIGERANT 10 LB MIN REFILL TANK ERROR 8 TANK REFI...

Page 16: ...e we will upon compliance with the return instructions either credit replace or repair at our option the defective product provided it is returned within one year of the date of factory shipment 90 da...