4.7.

 

Error message

 

When  the  measured  value  PV  is  lower  than  SVL,  it  is  shown  as            (communication 

output  is  -16666),  indicating  that  the  thermocouple  is  inversely  connected,  thermal  resistance 
short-circuit  or  three-wire  connection  is  wrong,  and  the  ambient  temperature  (cold  end 
temperature)  is  too  low.  Please  check  whether  the  sensor  wiring  is  correct  or  the  sensor  is 
damaged. When the ambient temperature is too low, the lower limit SVL can be lowered to test.   

When  the  measured  value  PV  is  higher  than  SVH,  it  is  shown  as          (communication 

output is 18888), which indicates that the thermocouple is open circuit or the thermal resistance 
is  open  circuit,  and  the  actual  measurement  temperature  is  higher  than  the  upper  limit  of  the 
range (the sensor and the heating unit do not form the same loop, resulting in long-term heating). 
Please check whether the sensor is damaged and the control loop is connected correctly 

5.

 

Communication connection and set-up 

5.1.

 

Multiple controller communication connection 

When  the  sensor  indexing  code  Sn  is  not  set  to  a  valid  value,  it  is  displayed  as  Erro 
(communication output is 15555). 

                                                                                                                                                                                                                                                         

5.2.

 

 

Communication parameter setting

In normal state, long press        for more than 3 seconds 

to enter the communication parameter setting

 

No  Parameter Name  Symbol  Data Range 

Introductions 

Initial 

value 

Communication 

address 

Addr 

0

254 

Common  addresses  are  0  ~  9  and  can  be  extended  to 
254

 

Including

 

0 is broadcast address

 

251 is the initial value address of all parameters restored 
at factory

 

When  Addr=251,  press        and  all  parameters  of  the 
controller are restored to the factory initial value. About 5 
seconds later, the system will restart and enter the normal 
working state automatically. 

Communication 

rate 

bps

 

bAUd 

The 

value of 

0

10 

0

600

  1

1200

  2

2400

  3

4800

 

4

9600

5

14400

6

19200

7

28800

8

38400

 

9

57600

  10

115200

 

9600 

The number of 

Measurement 

and automatic 

inspection 

function 

CHLS 

01

88 

0X

The  single  digit  is  used  to  limit  the  control  loop 

number

The  set  range  of  X  is  1

8

match  with 

hardware

 

X0

10  digits  for  manual/automatic  inspection  function 

setting

 

X=0

Manually switch the loop to be displayed

 

X=1

8

Show  stop  time  for  each  channel  during 

automatic inspection, unit is second. 

28 

 

6.

 

Maintenance and preservation 

6.1.

 

Maintenance:  within 18  months following  the  purchase  of  the  instrument,  the  factory  shall  be 
responsible for the overall warranty for the failure of manufacturing quality. If the instrument is 
damaged due to improper use, the factory will charge users repair cost, and the instrument has 
lifetime warranty. 

6.2.

 

Storage: the instrument should be kept in dry, ventilated and free of corrosive gas with complete 
package.

 

 

上海亚泰仪表有限公司

 

Shanghai yatai instrument co., LTD

 

Phone

021-66186368

021-66186369 

Fax

021-66186226    technology  consulting

021-36160962 

E-mail

[email protected]    http://www.yatai.sh.cn 

Address: no. 128, zhenyuan road, baoshan city 

industrial park, Shanghai 

Document number

YT 01 20170303 2.0 

 