5
SETTING OPERATION CONDITIONS
55
( Example 2 )
Select BASIC and change the decel time 1 (C1
−
02) from 10.0 to 20.0 seconds while frequency
reference is displayed.
Table 24 Changing Constant Data when BASIC is Selected
Description
Key Sequence
Digital Operator Display
Remarks
⋅
Displaying frequency reference.
⋅
Displays Operation.
⋅
Displays Programming.
⋅
Select Programming.
⋅
Change the function display.
(Displays Accel/Decel.)
⋅
Select the function (accel/decel time).
⋅
Change the name display.
(Displays Decel Time 1.)
⋅
Depress DATA/ENTER key.
The value to be set blinks.
⋅
Change the value to 20.0 seconds.
⋅
Write
−
in the constant.
⋅
Return to Operation.
⋅
Select Operation to display frequency
reference.
DATA
ENTER
MENU
DATA
ENTER
DATA
ENTER
DATA
ENTER
DATA
ENTER
MENU
RESET
Frequency Ref
U1
−
01 = 60.00 HZ
** Main Menu **
Operation
** Main Menu **
Programming
Function b1
Sequence
Function C1
Accel/Decel
Accel Time 1
C1
−
01 =
10.0 Sec
Decel Time 1
C1
−
02 =
10.0 Sec
Decel Time 1
0010.0 Sec
Decel Time 1
0020.0 Sec
Entry Accepted
** Main Menu **
Operation
Frequency Ref
U1
−
01 = 60.00 HZ
When selecting Programmig,
Function b1 is displayed.
Searches for C1.
Displays C1
−
02.
After displaying Entry Accepted
for 1.5 seconds, returns to decel
time display.