3
WIRING
29
When determining wire size, consider voltage drop. Select a wire size so that voltage drop will
be less than 2% of the normal rated voltage. Voltage drop is calculated by the following
equation:
Phase
−
to
−
phase voltage drop (V)
=
3
¢
wire resistance (
Ω
/km)
¢
wiring distance (m)
¢
current (A)
¢
10
−
3
(7) Recommended Cable Gland
When installing the inverter unit as enclosed wall
−
mounted type (IP20), use the cable gland
listed below or equivalent.
Cable gland: SKINTOP ST or SKINTOP STE manufactured by LAPP.
Blind cap BLK
::
: SKINDICHT manufactured by LAPP.
DP
−
:::
: DP HOLE PLUG manufactured by HEYCO.
Table 8
Recommended Cable Gland
VS 616G5
Cable Lead
−
in Hole
Cable Gland
VS
−
616G5
Model
CIMR
−
Diameter
(mm)
Q’ty
Model
Diameter of
Applicable
Cable (mm)
Model of
Blind Cap
G5C51P5
to
35
1
STE21/29
18 to 25
DP
−
1375
to
G5C53P7
28
2
ST21
13 to 18
DP
−
1093
G5C55P5
35
3
STE21/29
18 to 25
DP
−
1375
G5C55P5
G5C57P5
22
1
ST13.5
6 to 12
DP
−
875
G5C5011
44
2
ST29
18 to 25
DP
−
1750
G5C5011
G5C5015
35
1
STE21/29
18 to 25
DP
−
1375
G5C5015
22
1
ST13.5
6 to 12
DP
−
875
NOTE