4
OPERATION
43
Table 13 Typical Operation by Control Circuit Terminal Signal
Description
Key Sequence
Digital Operator Display
Power ON
⋅
Displays frequency reference
value.
REMOTE mode is preset at the
factory.
Output Frequency Display
⋅
Switch to output frequency
display.
Forward Jog Run
(6Hz)
⋅
Close between control circuit
terminals 1 and 11 with 7 and
11 closed to perform JOG run.
⋅
Open between terminals 1 and
11, 7 and 11 after verifying
normal operation.
Frequency Setting
⋅
Input frequency reference
voltage (current) by control
circuit terminal 13 or 14 and
verify the input value by the
digital operator.
Output Frequency Display
⋅
Select output frequency monitor
display.
Forward Run
⋅
Close between control circuit
terminals 1 and 11 to perform
forward run.
Stop
⋅
Open between control circuit
terminals 1 and 11 to stop
operation.
1
2
3
4
5
Frequency Ref
U1
−
01 = 0.00 HZ
REMOTE LED lights. (SEQ, REF)
Output Freq
U1
−
02 = 0.00 HZ
Output Freq
U1
−
02 = 6.00 HZ
RUN LED lights. FWD LED lights.
Frequency Ref
U1
−
01 = 60.00 HZ
For reference voltage 10V
Output Freq
U1
−
02 = 0.00 HZ
Output Freq
U1
−
02 = 60.00 HZ
RUN LED lights. FWD LED lights.
Output Freq
U1
−
02 = 0.00 HZ
STOP LED lights.
(RUN LED blinks during
deceleration.)
STOP
RUN
RUN