Parameter
Declaration
Data Type
Memory Area
Description
ID
INPUT
DWORD
I, Q, M, D, L
constant
n
Low word: logical address of the DP
slave/PROFINET IO component
(module or submodule)
n
High word: irrelevant
STATUS
OUTPUT
DWORD
I, Q, M, D, L
Contains error information for SFC 14
DPRD_DAT in the form DW#16#40xxxx00
LEN
OUTPUT
INT
I, Q, M, D, L
Amount of data read in bytes
INPUTS
IN_OUT
ANY
I, Q, M, D
Target area for the read data.
It must have the same length as the area
that you configured for the selected DP
slave/PROFINET IO component. Only the
data type BYTE is permitted.
Please refer to SFC 14 - DPRD_DAT - Read consistent data.
15.3.2
FB 21 - SETIO - PROFIBUS/PROFINET write all Outputs
With the FB 21 SETIO you consistently transfer the data from the source area indicated
by
OUTPUTS
to the addressed PROFIBUS DP slave/PROFINET IO device, and, if nec-
essary, to the process image (in the case where you have configured the affected
address area for the DP standard slave as a consistency area in a process image). In
doing so, FB 21 calls the SFC 15 DPWR_DAT. The source area must have the same
length that you configured with for the selected component. In the case of a DP standard
slave with a modular structure or with several DP IDs, you can only access the data for
one component/DP ID with an FB 20 call each time at the configured start address.
Parameter
Declaration
Data Type
Memory Area
Description
ID
INPUT
DWORD
I, Q, M, D, L,
constant
n
Low word: logical address of the DP
slave/PROFINET IO component
n
(module or submodule)
n
High word: irrelevant
LEN
INPUT
INT
I, Q, M, D, L
Irrelevant
STATUS
OUTPUT
DWORD
I, Q, M, D, L
Contains error information for SFC 15
DPRD_DAT in the form DW#16#40xxxx00
OUTPUTS
IN_OUT
ANY
I, Q, M, D
Source area for the read data to be read. It
must have the same length as the area that
you configured for the selected DP slave/
PROFINET IO component. Only the data
type BYTE is permitted.
Please refer to SFC 15 - DPWR_DAT - Write consistent data.
15.3.3
FB 22 - GETIO_PART - PROFIBUS/PROFINET read a part of the Inputs
With the FB 22 GETIO_PART you consistently read a part of the process image area
belonging to a PROFIBUS DP slave/PROFINET IO device. In doing so, FB 22 calls the
SFC 81 UBLKMOV.
Error Information
Description
Error Information
Description
VIPA SPEED7
Standard
IO > FB 22 - GETIO_PART - PROFIBUS/PROFINET read a part of the Inputs
HB00 | OPL_SP7 | Operation list | en | 18-30