ERROR
STATUS
Description
1
8B07h
Parameter error, the length of the parameter field is invalid.
1
8B08h
Parameter error, the ID of the subfield is invalid.
1
8B09h
System error, the connection does not exist.
1
8B0Ah
Data error, the content of the subfield is not correct.
1
8B0Bh
Structure error, a subfield exists twice.
1
8B0Ch
Data error, the parameter does not contain all the necessary parameters.
1
8B0Dh
Data error, the
CONF_DB
does not contain a parameter field for system data.
1
8B0Eh
Data error/structure error, the
CONF_DB
type is invalid.
1
8B0Fh
System error, the CP does not have enough resources to process
CONF_DB
com-
pletely.
1
8B10
Data error, configuration by the user program is not set.
1
8B11
Data error, the specified type of parameter field is invalid.
1
8B12
Data error, too many connections were specified.
1
8B13
CP internal error
1
8F22h
Area length error reading a parameter.
1
8F23h
Area length error writing a parameter.
1
8F24h
Area error reading a parameter.
1
8F25h
Area error writing a parameter.
1
8F28h
Alignment error reading a parameter.
1
8F29h
Alignment error writing a parameter.
1
8F30h
The parameter is in the write-protected first current data block.
1
8F31h
The parameter is in the write-protected second current data block.
1
8F32h
The parameter contains a DB number that is too high.
1
8F33h
DB number error
1
8F3Ah
The target area was not loaded (DB).
1
8F42h
Timeout reading a parameter from the I/O area.
1
8F43h
Timeout writing a parameter from the I/O area.
1
8F44h
Address of the parameter to be read is disabled in the accessed rack.
1
8F45h
Address of the parameter to be written is disabled in the accessed rack.
1
8F7Fh
Internal error
8.2.13.3
Configuration Data Block
The configuration data block (
CONF_DB
) contains all the connection data and configura-
tion data (IP address, subnet mask, default router, NTP time server and other parame-
ters) for an Ethernet CP. The configuration data block is transferred to the CP with func-
tion block FB 55.
VIPA SPEED7
Network Communication
Ethernet Communication > FB 55 - IP_CONF - Progr. Communication Connections
HB00 | OPL_SP7 | Operation list | en | 18-30