54
Table 4.5 “B” Parameters
Access Level
Name
Address
Description
Data
Range
Unit
Default
During
Run
V/f
V/f
w/PG
OLV
FV
OLV
2
0 Operator
1 Terminals
2 Modbus
Communication
3 Option
Card
b1-01
0180h Reference
Source
4 Pulse
Input
1
1
Q Q Q Q Q
0 Operator
1 Terminals
2 Modbus
Communication
b1-02
0181h Run
Source
3 Option
Card
1
1
Q Q Q Q Q
0
Ramp to Stop
1
Coast to Stop
2
DC Injection to Stop
b1-03
0182h Stopping
Method
3
Coast with Timer
1
0
Q Q Q Q Q
0 Reverse
Enabled
b1-04
0183h Reverse
Operation
1 Reverse
Disabled
1
0
A A A A A
0
Run at Frequency Ref
1 Stop
2
Run at Minimum
Frequency
b1-05
0184h Zero-Speed
Operation
3
Run at Zero RPM
1
0
A
0
1 Scan (2.5 ms)
b1-06
0185h
Digital Input Scan Time
1
2 Scans (5.0 ms)
1
1
A A A A A
0
Cycle External Run
b1-07
0186h
Local / Remote Run Selection
1
Accept External Run
1
0
A A A A A
0 Disabled
b1-08
0187h
Run Command at
Programming Mode
1 Enabled
1
0
A A A A A
0 Disabled
b1-10
01DEh
Zero Speed Operation
Selection
1 Enabled
1
1
A
b2-01
0189h
DC Injection Start Frequency
0.0 ~ 10.0 Hz
0.1 Hz
0.5 Hz
A
A
A
A
A
b2-02
018Ah
DC Injection Current
0 ~ 100 %
1 %
50 %
A
A
A
b2-03
018Bh
DC Injection Time at Start
0.0 ~ 10.0 Sec
0.01 Sec
0.0 Sec
A
A
A
A
A
b2-04
018Ch
DC Injection Time at Stop
0.0 ~ 10.0 Sec
0.01 Sec
0.5 Sec
A
A
A
A
A
b2-08
0190h
Magnetic Flux Compensation
Level at Start
0 ~ 1000 %
1 %
0 %
A
0
Speed Search Frequency
Method - Disable
1
Speed Search Frequency
Method - Enable
2
Speed Search Current
Method - Disable
b3-01
0191h
Automatic Speed Search at
Start
3
Speed Search Current
Method - Enable
1
2
A
A A A
b3-02
0192h
Speed Search Current
(Current Detection Method)
0 ~ 200 %
1 %
Cntrl Meth
A A A
b3-03
0193h
Speed Search Decel Time
(Current Detection Method)
0.1 ~ 10.0 Sec
0.1 Sec
2.0 Sec
A
A
b3-05
0195h
Search Delay
(Either Method)
0.0 ~ 20.0 Sec
0.1 Sec
kVA Dep.
A A A A A
b3-10
019Ah
Search Detect Compensation
(Speed Detection Method)
1.0
~
1.2
0.01
1.1
A A A
b3-13
019Dh
Observer Proportional Gain
N4-08 During Speed Search
0.1
~
2.0
0.1
1
A
0 Disabled
b3-14
019Eh
Bi-directional Search
Selection
(Speed Detection Method)
1 Enabled
1
1
A
A A A
b3-17
01F0h
Search Restart Current Level
(Speed Detection Method)
0 ~ 200 %
1 %
150 %
A
A
A
b3-18
01F1h
Search Restart Detection Time
(Speed Detection Method)
0.0 ~ 1.0 Sec
0.01 Sec
0.1 Sec
A
A
A
Summary of Contents for Varispeed G7
Page 1: ...Modbus Communication Manual G7 Drive Drive Model CIMR G7U Document Number TM G7 11...
Page 2: ...2 Page intentionally blank...
Page 6: ...6 Notes...
Page 10: ...10 G7 Drive Connections Figure 1 2 G7 Drive Connections...
Page 18: ...18 Notes...
Page 32: ...32 Notes...
Page 80: ...80 Notes...
Page 82: ...82 Notes drive drive Name Date...