Date: 08/01/05, Rev: 05-08 

Page 11 of 17 

TM.F7SW.096

 

 

4.5 Modbus Registers

 

Modbus 

Address 

Monitor 

Name 

Description 

Unit 

024H 

Output Frequency 

Output frequency monitor 

0.01Hz *4 

*4: Scaling based on P2-10 (Output Monitor Units) setting.  Parameter P2-10 programs and functions exactly like 
standard parameter O1-03.   
 

4.6 Faults 

Fault Display 

Description 

Cause 

Countermeasures 

FRH 

Feedback Range 

High 

PID feedback out of range 
(high). Motor will coast to a 
stop. 

P1-01 = 4 or 5 and the PID 
feedback has exceeded the 
P1-02 level for the time set 
in P1-03. 

Correct the cause of the 

high feedback signal. 

FRL 

Feedback Range 

Low 

PID feedback out of range 
(low). Motor will coast to a 
stop. 

P1-01 = 4 or 5 and the PID 
feedback has fallen below 
the P1-05 level for the time 
set in P1-06. 

Correct the cause of the 

low feedback signal. 

 

4.7 Alarms 

Alarm Display 

Description 

Cause 

Countermeasures 

FRH 

Feedback Range 

High 

PID feedback out of range 

(high) 

P1-01 = 2 or 3 and the PID 
feedback has exceeded the 
P1-02 level for the time set 
in P1-03. 

Correct the cause of the 

high feedback signal. 

FRL 

Feedback Range 

Low 

PID feedback out of range 

(low) 

P1-01 = 2 or 3 and the PID 
feedback has fallen below 
the P1-05 level for the time 
set in P1-06. 

Correct the cause of the 

low feedback signal. 

 

 
5.0 Function Description 

 

5.1 Enhanced PID 

The Enhanced PID feature includes many enhancements over the drive’s standard PID function. The PID 
algorithm is programmed using the existing B5 group of parameters as well as the P group of parameters. 
See Section 2.0 for details. Enhanced features include: 
 

• 

The ramp in the PID setpoint behaves differently depending upon the PID mode and the reference 
source.  In most cases, the PID setpoint ramp affects only the PID setpoint.  When the PID + Trim feature 
is enabled (B5-01 = 3 or 4) and there is no independent PID setpoint, the PID ramp affects both the PID 
setpoint and the frequency reference. 

 

• 

The PID output is now algebraically summed with the frequency reference.  Motor rotation will be forward 
if:  a forward run is commanded and there is a positive PID + trim, or if a reverse run is commanded and 
there is a negative PID + trim.  Motor rotation will be reverse if:  a reverse run is commanded and there is 
a positive PID + trim, or if a forward run is commanded and there is a negative PID + trim.

 

 

• 

The integral time is lower-limited to the to the PID minimum output limit (P2-01).  The integrator is also 
held during the sleep mode, and the sleep minimum off time.  These changes were done to prevent 
integrator windup and insure smooth starts with a minimum of pressure overshoot.

 

Summary of Contents for Varispeed f7

Page 1: ...Enhanced PID for Air Compressors F7 Drive Software Technical Manual Software Number VSF11020X Drive Models CIMR F7UXXXXXX 096 Document Number TM F7SW 096 Date 08 01 05 Rev 05 08...

Page 2: ...standard functions or even inhibit standard functions It can be used to modify display text or parameter names Custom software is usually loaded to the drive before delivery The control board and driv...

Page 3: ...gram of Enhanced PID 2 Input B5 01 1 or 2 1 2 Simplified Block Diagram of Enhanced PID 3 Input B5 01 3 or 4 PID setpoint is independent of frequency reference 1 3 Simplified Block Diagram of Enhanced...

Page 4: ...Integral Hold Digital Input integrator can only increase Integral term is lower limited to PID minimum output Integral term is held during sleep and the sleep minimum off time PID Output Limit Indepe...

Page 5: ...ow multi function digital outputs are enabled if programmed detection is always active 1 Output DuringRUN Feedback high low multi function digital outputs are enabled if programmed detection is active...

Page 6: ...Lvl Low This parameter sets the detection level for PID feedback low detection function 100 0 100 0 0 0 No A P1 06 605H Feedback On Delay Time Low Fb Low On Delay This parameter sets the on delay tim...

Page 7: ...f Prop The PID output trim is proportional to the frequency reference 0 1 0 No A P2 05 60EH Frequency Reference Proportional Trim Lower Limit FrefProp Low Lim This parameter sets the lower limit of th...

Page 8: ...arameter determines what custom units are displayed for U1 01 D1 XX and U1 90 thru U1 96 0 No units displayed 1 PSI 2 kPa 3 o F Note Only applicable when O1 03 40 custom units 0 3 1 No A P2 10 612H Ou...

Page 9: ...d Flux Vector only 100 Maximum Output Frequency E1 04 0 01 Hz 3 F U1 90 720H PID Feedback PID Feedback Displays the PID feedback as a percentage of the maximum output frequency 100 Maximum Output Freq...

Page 10: ...the displayed units on the keypad are determined by parameter P2 09 3 Unit and scaling based on P2 10 Output Monitor Units setting Parameter P2 10 operates exactly the same way as O1 03 When P2 10 40...

Page 11: ...for the time set in P1 06 Correct the cause of the low feedback signal 5 0 Function Description 5 1 Enhanced PID The Enhanced PID feature includes many enhancements over the drive s standard PID funct...

Page 12: ...ysteresis share the same parameters as the PID feedback high detection alarm and fault P1 02 P1 03 P1 04 and P1 08 See Section 6 5 for a detailed block diagram 5 4 Customized Display of Keypad Monitor...

Page 13: ...Date 08 01 05 Rev 05 08 Page 13 of 17 TM F7SW 096 6 1 Enhanced PID with 2 Inputs B5 01 1 or 2...

Page 14: ...Date 08 01 05 Rev 05 08 Page 14 of 17 TM F7SW 096 6 2 Enhanced PID with 2 Inputs B5 01 3 or 4...

Page 15: ...Date 08 01 05 Rev 05 08 Page 15 of 17 TM F7SW 096 6 3 Enhanced PID with 3 Inputs B5 01 3 or 4...

Page 16: ...Date 08 01 05 Rev 05 08 Page 16 of 17 TM F7SW 096 6 4 Enhanced PID Feedback Detection...

Page 17: ...Date 08 01 05 Rev 05 08 Page 17 of 17 TM F7SW 096 6 5 PID Sleep Function and Blowdown Valve Digital Output...

Reviews: