TM.F7SW.096

 

4.2 Monitors (U1-XX) 

Control Mode *1

 

Monitor Number 

Modbus Address 

Monitor Name 

 

Digital 

Operator 

Display

 

Description 

Scaling for Multi-

function Analog 

Outputs 

Terminals 

FM and AM 

(H4-01, H4-04) 

Unit 

V/f 

V/f w/ PG 

Open Loop 

Vector 

F

lux Vector 

U1-01 040H 

Frequency 

Reference 

 

Frequency 

Ref 

Displays the 
frequency 
reference. 

100%: 

Maximum Output 

Frequency 

(E1-04) 

0.01 

Hz 

*2 

Q Q Q Q 

U1-02 041H 

Output 

Frequency 

 

Output Freq 

Displays the output 
frequency. 
 

100%: 

Maximum Output 

Frequency 

(E1-04) 

0.01 

Hz 

*3 

Q Q Q Q 

U1-05 044H 

Motor Speed 

 

Motor Speed 

Displays the 
encoder feedback 
speed or estimated 
motor speed. 

100%: 

Maximum Output 

Frequency 

(E1-04) 

0.01 

Hz 

*3 

- Q Q Q 

U1-20 053H 

Soft Starter 

Output 

 

SFS Output 

Displays the 
frequency 
reference after the 
Accel, Decel, and 
S-curve ramps. 

100%: 

Maximum Output 

Frequency 

(E1-04) 

0.01 

Hz 

*3 

Q Q Q Q 

U1-46 06DH 

Feed-Forward 

Speed 

 

FF Estimate 

SPD 

Displays the 
estimated feed-
forward speed 
(Flux Vector only). 

100%: 

Maximum Output 

Frequency 

(E1-04) 

0.01 

Hz 

*3 

- - - F 

U1-90 720H 

PID Feedback 

 

PID Feedback

 

Displays the PID 
feedback as a 
percentage of the 
maximum output 
frequency. 

100%: 

Maximum Output 

Frequency 

(E1-04) 

0.1% 

*2 

Q Q Q Q 

U1-91 721H 

PID Input 

 

PID Input

 

Displays the PID 
input value as a 
percentage of the 
maximum output 
frequency. 

100%: 

Maximum Output 

Frequency 

(E1-04) 

0.1% 

*2 

Q Q Q Q 

U1-92 722H 

PID Output 

 

PID Output

 

Displays the PID 
output value as a 
percentage of the 
maximum output 
frequency. 

100%: 

Maximum Output 

Frequency 

(E1-04) 

0.1% 

*2 

Q Q Q Q 

U1-93 723H 

PID 

Proportional 

Output 

 

PID P Output

 

Displays the PID 
proportional value 
as a percentage of 
the maximum 
frequency. 

100%: 

Maximum Output 

Frequency 

(E1-04) 

0.1% 

*2 

Q Q Q Q 

*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”. 
*2: Unit and scaling based on O1-03 (Display Scaling) setting. When O1-03 

 40 (custom units), the displayed 

units on the keypad are determined by parameter P2-09. 

*3: Unit and scaling based on P2-10 (Output Monitor Units) setting.  Parameter P2-10 operates exactly the same 

way as O1-03.  When P2-10 

 40 (custom units), the displayed units on the keypad are determined by 

parameter P2-09. 

Summary of Contents for Varispeed f7

Page 1: ...Enhanced PID for Air Compressors F7 Drive Software Technical Manual Software Number VSF11020X Drive Models CIMR F7UXXXXXX 096 Document Number TM F7SW 096 Date 08 01 05 Rev 05 08...

Page 2: ...standard functions or even inhibit standard functions It can be used to modify display text or parameter names Custom software is usually loaded to the drive before delivery The control board and driv...

Page 3: ...gram of Enhanced PID 2 Input B5 01 1 or 2 1 2 Simplified Block Diagram of Enhanced PID 3 Input B5 01 3 or 4 PID setpoint is independent of frequency reference 1 3 Simplified Block Diagram of Enhanced...

Page 4: ...Integral Hold Digital Input integrator can only increase Integral term is lower limited to PID minimum output Integral term is held during sleep and the sleep minimum off time PID Output Limit Indepe...

Page 5: ...ow multi function digital outputs are enabled if programmed detection is always active 1 Output DuringRUN Feedback high low multi function digital outputs are enabled if programmed detection is active...

Page 6: ...Lvl Low This parameter sets the detection level for PID feedback low detection function 100 0 100 0 0 0 No A P1 06 605H Feedback On Delay Time Low Fb Low On Delay This parameter sets the on delay tim...

Page 7: ...f Prop The PID output trim is proportional to the frequency reference 0 1 0 No A P2 05 60EH Frequency Reference Proportional Trim Lower Limit FrefProp Low Lim This parameter sets the lower limit of th...

Page 8: ...arameter determines what custom units are displayed for U1 01 D1 XX and U1 90 thru U1 96 0 No units displayed 1 PSI 2 kPa 3 o F Note Only applicable when O1 03 40 custom units 0 3 1 No A P2 10 612H Ou...

Page 9: ...d Flux Vector only 100 Maximum Output Frequency E1 04 0 01 Hz 3 F U1 90 720H PID Feedback PID Feedback Displays the PID feedback as a percentage of the maximum output frequency 100 Maximum Output Freq...

Page 10: ...the displayed units on the keypad are determined by parameter P2 09 3 Unit and scaling based on P2 10 Output Monitor Units setting Parameter P2 10 operates exactly the same way as O1 03 When P2 10 40...

Page 11: ...for the time set in P1 06 Correct the cause of the low feedback signal 5 0 Function Description 5 1 Enhanced PID The Enhanced PID feature includes many enhancements over the drive s standard PID funct...

Page 12: ...ysteresis share the same parameters as the PID feedback high detection alarm and fault P1 02 P1 03 P1 04 and P1 08 See Section 6 5 for a detailed block diagram 5 4 Customized Display of Keypad Monitor...

Page 13: ...Date 08 01 05 Rev 05 08 Page 13 of 17 TM F7SW 096 6 1 Enhanced PID with 2 Inputs B5 01 1 or 2...

Page 14: ...Date 08 01 05 Rev 05 08 Page 14 of 17 TM F7SW 096 6 2 Enhanced PID with 2 Inputs B5 01 3 or 4...

Page 15: ...Date 08 01 05 Rev 05 08 Page 15 of 17 TM F7SW 096 6 3 Enhanced PID with 3 Inputs B5 01 3 or 4...

Page 16: ...Date 08 01 05 Rev 05 08 Page 16 of 17 TM F7SW 096 6 4 Enhanced PID Feedback Detection...

Page 17: ...Date 08 01 05 Rev 05 08 Page 17 of 17 TM F7SW 096 6 5 PID Sleep Function and Blowdown Valve Digital Output...

Reviews: