5.2 Modified PID “Sleep” Function 

In standard software, parameter B5-16 controls both the sleep delay, and the wake-up delay.  In this 
software, parameter B5-16 controls the sleep delay, and P2-06 controls the wake-up delay.  The 
maximum settable range of B5-16 is increased from 25.5 seconds to 600.0 seconds. 
 
An additional timer has been added (P2-07) to the sleep function to insure that when the drive does go 
into the sleep mode, it remains in sleep mode even if the PID is calling for the drive to run.  This is to 
insure that the pressure in the “sump” of the air compressor can dissipate before it restarts.  This 
prevents foaming of the oil. 

 

5.3 Blowdown Valve Digital Output 

This digital output can be used to control the blowdown or loading valve for the air compressor.  When 
this output is energized, the blowdown valve is active, and the compressor is allowed to make air.  If this 
output is de-energized, the air compressor won’t produce any air, even if it is turning.  This output should 
normally be energized when the drive is running, but only after a delay after startup (determined by 
parameter number P2-08).  This allows the motor, drive, and compressor to start under less load.  The 
output will also de-energize if the PID feedback (air pressure) goes too high.  The level, time delays, and 
hysteresis share the same parameters as the PID feedback high detection alarm and fault. (P1-02, P1-
03, P1-04, and P1-08). See Section 6.5 for a detailed block diagram. 

 

5.4 Customized Display of Keypad Monitors 

When first powered up (or returning to the drive mode), the digital operator display will 
show pressure setpoint (U1-01), pressure feedback (U1-90), and output frequency 
(U1-02).  All PID setpoints (U1-01, D1-XX) and PID monitors (U1-9X) have user 
selectable scaling (O1-03) and keypad display units (P2-09). User selectable units will 
only be displayed when O1-03 

 40 (custom units).  Unit selections are PSI, kPa, and 

o

F.    

 
Other parameters that are normally scaled using O1-03, which include U1-02, U1-05, 
U1-20, and U1-46, are scaled by parameter P2-10. Parameter P2-10 will work in 
exactly the same manner as O1-03 does.  When the setting is 0, the units and scaling 
will be in 0.01Hz.  When the setting is 1, the units and scaling will be in 0.01%.  When 
the setting is 2 ~ 38, the scaling will be in RPM, with the setting of P2-10 acting as the 
number of motor poles for the calculation.  When the P2-10 

 40 (custom scaling), the 

keypad display units are determined by parameter P2-09. Unit selections are PSI, 
kPa, and 

o

F.   

 
 

6.0 Block Diagrams 

The following pages give detailed flowcharts of the following software functions: 

6.1 PID with 2 Inputs (B5-01 = 1 or 2) 
6.2 PID with 2 Inputs (B5-01 = 3 or 4) 
6.3 PID with 3 Inputs (B5-01 = 3 or 4) 
6.4 PID Feedback Detection 
6.5 PID Sleep function and Blowdown Valve Digital Output 

 

U1-01

U1-90

U1-02

U1-03

U1-94

U1-96

.
.
.

U1-93

U1-92

U1-91

U1-95

Summary of Contents for Varispeed f7

Page 1: ...Enhanced PID for Air Compressors F7 Drive Software Technical Manual Software Number VSF11020X Drive Models CIMR F7UXXXXXX 096 Document Number TM F7SW 096 Date 08 01 05 Rev 05 08...

Page 2: ...standard functions or even inhibit standard functions It can be used to modify display text or parameter names Custom software is usually loaded to the drive before delivery The control board and driv...

Page 3: ...gram of Enhanced PID 2 Input B5 01 1 or 2 1 2 Simplified Block Diagram of Enhanced PID 3 Input B5 01 3 or 4 PID setpoint is independent of frequency reference 1 3 Simplified Block Diagram of Enhanced...

Page 4: ...Integral Hold Digital Input integrator can only increase Integral term is lower limited to PID minimum output Integral term is held during sleep and the sleep minimum off time PID Output Limit Indepe...

Page 5: ...ow multi function digital outputs are enabled if programmed detection is always active 1 Output DuringRUN Feedback high low multi function digital outputs are enabled if programmed detection is active...

Page 6: ...Lvl Low This parameter sets the detection level for PID feedback low detection function 100 0 100 0 0 0 No A P1 06 605H Feedback On Delay Time Low Fb Low On Delay This parameter sets the on delay tim...

Page 7: ...f Prop The PID output trim is proportional to the frequency reference 0 1 0 No A P2 05 60EH Frequency Reference Proportional Trim Lower Limit FrefProp Low Lim This parameter sets the lower limit of th...

Page 8: ...arameter determines what custom units are displayed for U1 01 D1 XX and U1 90 thru U1 96 0 No units displayed 1 PSI 2 kPa 3 o F Note Only applicable when O1 03 40 custom units 0 3 1 No A P2 10 612H Ou...

Page 9: ...d Flux Vector only 100 Maximum Output Frequency E1 04 0 01 Hz 3 F U1 90 720H PID Feedback PID Feedback Displays the PID feedback as a percentage of the maximum output frequency 100 Maximum Output Freq...

Page 10: ...the displayed units on the keypad are determined by parameter P2 09 3 Unit and scaling based on P2 10 Output Monitor Units setting Parameter P2 10 operates exactly the same way as O1 03 When P2 10 40...

Page 11: ...for the time set in P1 06 Correct the cause of the low feedback signal 5 0 Function Description 5 1 Enhanced PID The Enhanced PID feature includes many enhancements over the drive s standard PID funct...

Page 12: ...ysteresis share the same parameters as the PID feedback high detection alarm and fault P1 02 P1 03 P1 04 and P1 08 See Section 6 5 for a detailed block diagram 5 4 Customized Display of Keypad Monitor...

Page 13: ...Date 08 01 05 Rev 05 08 Page 13 of 17 TM F7SW 096 6 1 Enhanced PID with 2 Inputs B5 01 1 or 2...

Page 14: ...Date 08 01 05 Rev 05 08 Page 14 of 17 TM F7SW 096 6 2 Enhanced PID with 2 Inputs B5 01 3 or 4...

Page 15: ...Date 08 01 05 Rev 05 08 Page 15 of 17 TM F7SW 096 6 3 Enhanced PID with 3 Inputs B5 01 3 or 4...

Page 16: ...Date 08 01 05 Rev 05 08 Page 16 of 17 TM F7SW 096 6 4 Enhanced PID Feedback Detection...

Page 17: ...Date 08 01 05 Rev 05 08 Page 17 of 17 TM F7SW 096 6 5 PID Sleep Function and Blowdown Valve Digital Output...

Reviews: