Acceleration time parameters always set the time to accelerate from 0 Hz to the maximum output frequency (E1-04).
Deceleration time parameters always set the time to decelerate from maximum output frequency to 0 Hz. C1-01 and C1-02
are the default active accel/decel settings.
No.
Parameter Name
Setting Range
Default
C1-01
Acceleration Time 1
0.0 to 6000.0 s
<1>
10.0 s
C1-02
Deceleration Time 1
C1-03
Acceleration Time 2
C1-04
Deceleration Time 2
C1-05
Acceleration Time 3 (Motor 2 Accel Time 1)
C1-06
Deceleration Time 3 (Motor 2 Decel Time 1)
C1-07
Acceleration Time 4 (Motor 2 Accel Time 2)
C1-08
Deceleration Time 4 (Motor 2 Decel Time 2)
<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the time
is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.
Switching Acceleration Times by Digital Input
Accel/decel times 1 are active by default if no input is set. Activate accel/decel times 2, 3, and 4 by digital inputs
(H1-
oo
= 7 and 1A) as explained in
Table i.34
.
Table i.34 Accel/Decel Time Selection by Digital Input
Accel/Decel Time Sel. 1
H1-
oo
= 7
Accel/Decel Time Sel. 2
H1-
oo
= 1A
Active Times
Acceleration
Deceleration
0
0
C1-01
C1-02
1
0
C1-03
C1-04
0
1
C1-05
C1-06
1
1
C1-07
C1-08
Figure i.62
shows an operation example for changing accel/decel. times. The example below requires that the stopping method
be set for “Ramp to stop” (b1-03 = 0).
Output
frequency
Accel Time 1
(C1-01)
Decel Time 1
(C1-02)
Accel Time 2
(C1-03)
Decel Time 2
(C1-04)
Decel Time 1
(C1-02)
Time
FWD (REV)
Run command
ON
OFF
ON
ON
Accel/Decel Time Selection 1
(Terminals S1 to S8, H1-
oo
= “7”)
Accel Time 3
(C1-05)
Decel Time 3
(C1-06)
Accel Time 4
(C1-07)
Decel Time 4
(C1-08)
Decel Time 1
(C1-02)
ON
OFF
ON
OFF
ON
Accel/Decel Time Selection 2
(Terminals S1 to S8, H1-
oo
= “1A”)
ON
Figure i.62 Timing Diagram of Accel/Decel Time Change
Switching Acceleration and Deceleration Times by Motor Selection
When switching between motor 1 and 2 using a digital input (H1-
oo
= 16), parameters C1-01 to C1-04 become accel/decel
times 1 and 2 for motor 1, while C1-05 to C1-08 become accel/decel times 1 and 2 for motor 2. Accel/decel times 1 and 2 can
be switched for each motor using a digital inputs set to H1-
oo
= 7 like shown in
Table i.35
.
Note:
1.
The motor 2 selection function cannot be used with PM motors.
2.
Attempting to use the digital input setting “Accel/Decel time 2 selection” (H1-
oo
= 1A) together with motor 1/2 switching triggers an
oPE03 error, indicating contradictory multifunction input settings.
i.5 Start-Up Programming and Operation
YASKAWA ELECTRIC TOEP C710636 04D U1000 Industrial MATRIX Drive Quick Start Guide