C.9 MEMOBUS/Modbus Data Table
462
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
003DH
bit 0
CRC Error
bit 1
Data Length Error
bit 2
Reserved
bit 3
Parity Error
bit 4
Overrun Error
bit 5
Framing Error
bit 6
Timeout
bit 7 to bit F
Reserved
003EH
Output Frequency
003FH
0.01% units
0040H to 004AH
Used for various monitors U1-
for parameter details.
004BH
Drive Status (U1-12)
bit 0
During Run
bit 1
During Zero Speed
bit 2
During Reverse Run
bit 3
During Fault Reset Signal Input
bit 4
During Speed Agree
bit 5
Drive Ready
bit 6
Alarm
bit 7
Fault
bit 8
During Operation Error (oPE
)
bit 9
During Momentary Power Loss
bit A
Motor 2 selected
bit B
Reserved
bit E
ComRef status, NetRef status
bit F
ComCtrl status, NetCtrl status
004CH to 007EH
Used for various monitors U1-
, U4-
, U5-
and U6-
for parameter details.
007FH
Alarm Register Contents on page 469
for alarm codes.
0080H to 0097H
Used for monitors U2-
, U3-
. Refer to
for parameter details and Refer to
Fault Trace Contents on page 468
for register
value descriptions.
0098H
High Word of Accumulated Operation Time Monitor, 10H units (U4-01)
0099H
Low Word of Accumulated Operation Time Monitor, 1H units (U4-01)
009AH
High Word of Cooling Fan Operation Time Monitor (U4-03)
009BH
Low Word of Cooling Fan Operation Time Monitor (U4-03)
009CH to 00AAH
Reserved
00ABH
Drive Rated Current
00ACH
Motor Speed (U1-05)
r/min units
00ADH
0.01% units
00AEH, 00AFH
Reserved
00B0H
Option Code Connected to CN5-A
Register contains ASCII code of the option card.
DI-A3 = 0001H
DO-A3 = 0002H
AI-A3 = 0003H
AO-A3 = 0004H
PG-B3 = 0011H
PG-X3 = 0012H
Communication Option: Register contains ASCII code of 1st and 3rd digit of the option card type number.
Example: Register value is 5343H for “SC” if a SI-C3 option card is installed.
00B1H
Reserved
00B2H
Option Code Connected to CN5-B
00B3H
Option Code Connected to CN5-C
00B4H
Reserved
00B5H
Frequency Reference After Soft-
starter (U1-16)
r/min units
00B6H
0.01% units
00B7H
Frequency Reference
00B8H
0.01% units
00B9H to 00BEH
Reserved
00BFH
Lists the last to digits of operation error code oPE
.
Register No.
Contents