5.7 H: Terminal Functions
YASKAWA ELECTRIC
SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
181
P
a
ra
me
te
r D
e
ta
ils
5
5.7
H: Terminal Functions
H parameters are used to assign functions to the external terminals.
u
H1: Multi-Function Digital Inputs
n
H1-01 to H1-08: Functions for Terminals S1 to S8
These parameters assign functions to the multi-function digital inputs. The various functions and their settings are listed
below in
.
Table 5.20 Multi-Function Digital Input Terminal Settings
No.
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.
Parameter Name
Setting
Range
Default
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
1 to 7E
40 (F)
: Forward Run Command (2-wire sequence)
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
1 to 7E
41 (F)
: Reverse Run Command (2-wire sequence)
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
0 to 7E
24: External Fault
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
0 to 7E
14: Fault Reset
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
0 to 7E
3 (0)
: Multi-Step Speed Reference 1
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
0 to 7E
4 (3)
: Multi-Step Speed Reference 2
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
0 to 7E
6 (4)
: Jog Reference Selection
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
0 to 7E
8: Baseblock Command (N.O.)
Setting
Function
Page
Setting
Function
Page
0
3-wire sequence
31
PID integral hold
1
Local/remote selection
34
PID soft starter cancel
2
External reference 1/2 selection
35
PID input level selection
3
Multi-Step Speed Reference 1
40
Forward run command (2-wire sequence)
4
Multi-Step Speed Reference 2
41
Reverse run command (2-wire sequence)
5
Multi-Step Speed Reference 3
42
Run command (2-wire sequence 2)
6
Jog reference selection
43
FWD/REV command (2-wire sequence 2)
7
Accel/decel time selection 1
44
Offset frequency 1
8
Baseblock command (N.O.)
45
Offset frequency 2
9
Baseblock Command (N.C.)
46
Offset frequency 3
A
Accel/decel ramp hold
50
Disturb Function Cancel
B
Drive overheat alarm (OH2)
51
Synchronous Accel/Decel
C
Analog terminal input selection
53
Energy Saving On/Off
D
PG encoder disable
59
DC Injection Braking 1
E
ASR integral reset
60
DC Injection Braking 2
F
Through mode
61
External Speed Search command 1
10
Up command
62
External Speed Search command 2
11
Down command
63
Field Weakening
12
Forward jog
65
KEB (N.C.)
13
Reverse jog
66
KEB (N.O.)
14
Fault reset
67
Communications test mode
15
Fast Stop (N.O.)
6A
Drive enabled
16
Motor 2 selection
71
Speed/Torque Control switch
17
Fast Stop (N.C.)
72
Zero Servo
18
Timer function input
77
ASR gain switch
19
PID disable
78
External torque reference polarity inversion
1A
Accel/decel time selection 2
7C
Short Circuit Braking (N.O.)
1B
Program lockout
7D
Short Circuit Braking (N.C.)
20 to 2F
External fault
7E
Forward/reverse detection (V/f control with simple PG)
30
PID integral reset