5.3 C: Tuning
YASKAWA ELECTRIC
SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
151
P
a
ra
me
te
r D
e
ta
ils
5
n
C5-25: Motor 2 ASR Limit
Functions for motor 2 in the same way that C5-05 functions for motor 1. Sets the ASR output limit for motor 2 as a
percentage of the maximum output frequency (E4-04). For more details, see
.
n
C5-26: Motor 2 ASR Primary Delay Time Constant
Functions for motor 2 in the same way that C5-06 functions for motor 1.
Sets the filter time constant for the time from the speed loop to the torque command output. For more details, see
ASR Primary Delay Time Constant on page 149
Note:
This parameter rarely requires adjustment.
n
C5-27: Motor 2 ASR Gain Switching Frequency
Functions for motor 2 in the same way that C5-07 functions for motor 1.
Sets the frequency for motor 2 to change ASR proportional gain 1 and 2 (C5-21, C5-23) as well as the integral time 1 and
2 (C5-22, C5-24). For more details, see
C5-01, C5-03 / C5-02, C5-04: ASR Proportional Gain 1, 2 / ASR Integral Time
.
Note:
A multi-function input set for the ASR gain switch (H1-
= 77) takes priority over the ASR gain switching frequency.
n
C5-28: Motor 2 ASR Integral Limit
Functions for motor 2 in the same way that C5-08 functions for motor 1.
Sets the upper limit for ASR as a percentage of the rated load.
n
C5-32: Integral Operation during Accel/Decel for Motor 2
Functions for motor 2 in the same way that C5-12 functions for motor 1.
Enables integral operation during acceleration and deceleration. For more details, see
C5-12: Integral Operation during
Accel/Decel (V/f w/PG) on page 150
.
Setting 0: Disabled
Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled
Integral operation is always enabled.
n
C5-37, C5-38: Motor 2 Inertia, Motor 2 Load Inertia Ratio
These parameters function for motor 2 in the same way that C5-17 and C5-18 function for motor 1.
No.
Parameter Name
Setting Range
Default
C5-21
<1> The setting range is 1.00 to 300.00 in CLV.
Motor 2 ASR Proportional Gain 1
0.00 to 300.00
Determined by E3-01
C5-22
Motor 2 ASR Integral Time 1
0.000 to 10.000 s
Determined by E3-01
C5-23
Motor 2 ASR Proportional Gain 2
0.00 to 300.00
Determined by E3-01
C5-24
Motor 2 ASR Integral Time 2
0.000 to 10.000 s
Determined by E3-01
No.
Parameter Name
Setting Range
Default
C5-25
Motor 2 ASR Limit
0.0 to 20.0%
5.0%
No.
Parameter Name
Setting Range
Default
C5-26
Motor 2 ASR Primary Delay Time Constant
0.000 to 0.500 s
0.004 s
No.
Parameter Name
Setting Range
Default
C5-27
Motor 2 ASR Gain Switching Frequency
0.0 to 400.0 Hz
0.0 Hz
No.
Parameter Name
Setting Range
Default
C5-28
Motor 2 ASR Integral Limit
0 to 400%
400%
No.
Parameter Name
Setting Range
Default
C5-32
Integral Operation during Accel/Decel for Motor 2
0, 1
0