B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
407
Pa
ra
met
e
r Li
st
B
u
o: Operator Related Parameters
The o parameters are used to set up the digital operator displays.
n
o1: Digital Operator Display Selection
n
o2: Digital Operator Keypad Functions
No. (Addr.)
<8> Default setting value is determined by the digital operator display selection (o1-03).
<34> Default setting is determined by the control mode (A1-02).
Name
Description
Setting
Page
o1-01
(500H)
Drive Mode Unit Monitor
Selection
Selects the content of the last monitor that is shown when scrolling through Drive Mode
display. Enter the last three digits of the monitor parameter number to be displayed: U
-
.
Default: 106 (Monitor
U1-06)
Min: 104
Max: 905
o1-02
(501H)
User Monitor Selection after
Power Up
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
Default: 1
Min: 1
Max: 5
o1-03
(502H)
Digital Operator Display Selection
Sets the units the drive should use to display the frequency reference and motor speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04, or E5-04)
3: User-selected units (set by o1-10 and o1-11)
Min: 0
Max: 3
o1-04
(503H)
V/f Pattern Display Unit
0: Hz
1: r/min
Min: 0
Max: 1
o1-10
(520H)
User-Set Display Units Maximum
Value
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
Min: 1
Max: 60000
o1-11
(521H)
User-Set Display Units Decimal
Display
Min: 0
Max: 3
No. (Addr.)
Name
Description
Setting
Page
o2-01
(505H)
LO/RE Key Function Selection
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
Default: 1
Min: 0
Max: 1
o2-02
(506H)
STOP Key Function Selection
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
Default: 1
Min: 0
Max: 1
o2-03
(507H)
User Parameter Default Value
0: No change.
1: Set defaults. Saves parameter settings as default values for a User Initialization.
2: Clear all. Clears the default settings that have been saved for a User Initialization.
Default: 0
Min: 0
Max: 2
o2-04
(508H)
Drive Model Selection
Enter the drive model. Setting required only if installing a new control board.
Default: Determined by
drive capacity
Min: –
Max: –
o2-05
(509H)
Frequency Reference Setting
Method Selection
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted using the up and down
arrow keys only.
Default: 0
Min: 0
Max: 1
o2-06
(50AH)
Operation Selection when Digital
Operator is Disconnected
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
Default: 0
Min: 0
Max: 1
o2-07
(527H)
Motor Direction at Power Up when
Using Operator
0: Forward
1: Reverse
This parameter requires that drive operation be assigned to the digital operator.
Default: 0
Min: 0
Max: 1
o2-09
(50DH)
Reserved
–
–
–
All Modes
All Modes
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes