APPLICATIONS
2.2.8 Reference Pulse Inhibit Function (INHIBIT)
— 2-36 —
2.2.8 Reference Pulse Inhibit Function (INHIBIT)
The reference pulse inhibit function inhibits a Servopack for position control from counting
input reference pulses.
While this function is being used, the motor remains in Servo locked (clamped) status. The
/P-CON signal is used to enable or prohibit this function.
When this function is used, therefore, the /P-CON signal cannot be used to switch between
proportion (P) control and proportional/integral (PI) control for speed loop. (PI control is al-
ways used.)
Cn-01 bit F
Error
counter
Reference
pulse
0
1
OFF
ON
+
−
Feedback pulse
Servopack
/P-CON
/P-CON
Schematic Block Diagram for INHIBIT Function
Note
Use Cn-01 bit F to enable/disable the INHIBIT function.
Using Reference Pulse Inhibit Function (INHIBIT)
To use the INHIBIT function, set the memory switch Cn-01 bit F to 1:
Cn-01 Bit F
Reference Pulse Inhibit
Function (INHIBIT)
(1: Enable, 0: Disable)
Factory
Setting: 0
For Position Control
The INHIBIT function will be enabled.
Setting
Meaning
0
Does not use the INHIBIT function.
Reference pulses are always counted.
Uses the INHIBIT function.
/P-CON signal is used to enable or prohibit the INHIBIT function.
/P-CON
Meaning
1
OFF
Counts reference pulses.
1
ON
Prohibits the Servopack from counting reference
pulses.
The motor remains in Servo locked (clamped) status.
2
Positions
Positions