2.2Setting Parameters According to Host Controller
— 2-29 —
Using Contact Input Speed Control
To use the contact input speed control function, perform the following settings.
1) Set the following memory switch to 1.
Cn-02 Bit 2
Contact Input Speed Control
Selection
(1: Enable, 0: Disable)
Factory
Setting: 0
For Speed/Torque Control
The contact input speed control function will be enabled.
If the contact input speed control function is used,
the contents of the input signals shown below will
change.
Setting
Meaning
Input Signal
0
Does not use the contact
IN1 (CN1-1)
Set in Cn-2A
0
Does not use the contact
input speed control function.
IN2 (CN1-2)
Set in Cn-2B
put speed co t o u ct o
Uses the contact input speed
0: OFF, 1: ON
Uses the contact input speed
control function.
IN1
IN2
Speed Setting
control function.
IN1 and IN2 will become
0
0
Stop (or analog speed reference)
1
IN1 and IN2 will become
contact input speed control
0
1
Cn-1F, SPEED1
1
contact input speed control
signals automatically
1
1
Cn-20, SPEED2
g
y
regardless of CN-2B and
C 2C
tti
1
0
Cn-21, SPEED3
g
Cn-2C settings.
2) Set three motor speeds in the following parameters.
Cn-1F
SPEED1
1st Speed (Contact
Input Speed Control)
Unit:
min
−
1
Setting
Range: 0 to
Maximum
Speed
Factory
Setting:
100
For Speed/Torque
Control
Cn-20
SPEED2
2nd Speed (Contact
Input Speed Control)
Unit:
min
−
1
Setting
Range: 0 to
Maximum
Speed
Factory
Setting:
200
For Speed/Torque
Control
Cn-21
SPEED3
3rd Speed (Contact
Input Speed Control)
Unit:
min
−
1
Setting
Range: 0 to
Maximum
Speed
Factory
Setting:
300
For Speed/Torque
Control
Use these parameters to set motor speeds when
the contact input speed control function is used
(set bit 2 of memory switch Cn-02).
Speed selection input signals IN1 and IN2 enable
the motor to run at the preset speeds.
2
Servomotor
Contact
input
Servopack
SPEED 1
SPEED 2
SPEED 3
M
Run the
motor at
internally
set
speed
Contact input speed control
(Memory switch Cn-02 bit 2 = 1)
Servomotor
Contact
input
Servopack
SPEED 1
SPEED 2
SPEED 3
M
Run the
motor at
internally
set
speed
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com