3.5 Wiring the Power Supply to the SERVOPACK
3.5.1 Terminal Symbols and Terminal Names
3-26
3.5
Wiring the Power Supply to the SERVOPACK
Refer to the following manual or catalog for information on cables and peripheral devices.
AC Servo Drives
Σ
-7 Series (Catalog No.: KAEP S800001 23)
Σ
-7-Series Peripheral Device Selection Manual (Manual No.: SIEP S800001 32)
3.5.1
Terminal Symbols and Terminal Names
Use the main circuit connector or terminal block on the SERVOPACK to wire the main circuit
power supply and control circuit power supply to the SERVOPACK.
The SERVOPACKs have the following three types of main circuit power supply input specifica-
tions.
•
Three-Phase, 200-VAC Power Supply Input
•
Single-Phase, 200-VAC Power Supply Input
CAUTION
Wire all connections correctly according to the following table and specified reference infor-
mation. There is a risk of SERVOPACK failure or fire if incorrect wiring is performed.
Terminal
Symbols
Terminal Name
Specifications and Reference
L1, L2, and
L3
Main circuit power supply
input terminals for AC
power supply input
Three-phase, 200 VAC to 240 VAC, -15% to +10%, 50 Hz/60
Hz
L1C and L2C
Control power supply termi-
nals
Single-phase, 200 VAC to 240 VAC, -15% to +10%, 50 Hz/60
Hz
B1/ , B2,
and B3
Regenerative Resistor termi-
nals
3.5.5 Wiring Regenerative Resistors
If the internal regenerative resistor is insufficient, remove the
lead or short bar between B2 and B3 and connect an Exter-
nal Regenerative Resistor between B1/ and B2. The Exter-
nal Regenerative Resistor is not included. Obtain it separately.
1 and 2
DC Reactor terminals for
power supply harmonic
suppression
3.5.6 Wiring Reactors for Harmonic Suppression
These terminals are used to connect a DC Reactor for power
supply harmonic suppression or power factor improvement.
–
None. (Do not connect anything to this terminal.)
Terminal
Symbols
Terminal Name
Specifications and Reference
L1 and L2
Main circuit power supply
input terminals for AC
power supply input
Single-phase, 200 VAC to 240 VAC, -15% to +10%, 50 Hz/60
Hz
L1C and L2C
Control power supply termi-
nals
Single-phase, 200 VAC to 240 VAC, -15% to +10%, 50 Hz/60
Hz
B1/ , B2,
and B3
Regenerative Resistor termi-
nals
3.5.5 Wiring Regenerative Resistors
If the internal regenerative resistor is insufficient, remove the
lead or short bar between B2 and B3 and connect an Exter-
nal Regenerative Resistor between B1/ and B2. The Exter-
nal Regenerative Resistor is not included. Obtain it separately.
1 and 2
DC Reactor terminals for
power supply harmonic
suppression
3.5.6 Wiring Reactors for Harmonic Suppression
These terminals are used to connect a DC Reactor for power
supply harmonic suppression or power factor improvement.
L3 and
–
None. (Do not connect anything to these terminals.)