5 Conditions for Compliance with EC Directives
E-49
5.2 Conditions for Compliance with the Low
Voltage Directive
The products have been tested according to IEC/EN 61800-5-1 and EN 50178,
and they comply the Low Voltage Directive. To comply with the Low Voltage
Directive, the equipment or machine in which you use the products must meet
the following conditions.
Installation Environment and Insulation
Conditions
III
Compliance standards: IEC 60364-4-44 and IEC
60664-1
2
Compliance standards: IEC 60364-4-44 and IEC
60664-1
-5
C to
60
C*
Refer to the following section for application at
55°C or higher.
2,000 m
max.*
Refer to the following section for application at
1,000 m or higher.
Refer to
Compliance standard: IEC 60529
I
Compliance standard: IEC 61140
AC power
supply
CE Marking is not applicable if a DC power sup-
ply input is used.
* If you combine a
-7-Series SERVOPACK with a
-V-Series Option Module,
the following
-V-Series SERVOPACKs specifications must be used: a sur-
rounding air temperature of 0°C to 55°C and an altitude of 1,000 m max. Also,
the applicable range cannot be increased by derating.
External Power Supply for Control Circuits
For the DC power supply for the control signal I/O circuits (CN1 and CN8), use
a power supply device with double insulation or reinforced insulation.
Installation of a Short-Circuit Protection Element
Always use Fuses that comply with UL standards on the main circuit power
supply line.
Use either non-time delay fuses or semiconductor fuses.
Refer to
3.3 Molded-Case Circuit Breakers and Fuses
on page 28 for informa-
tion on selecting fuse voltage and current ratings.
Overvoltage
Category
Pollution Degree
Surrounding Air
Temperature
Altitude
Degree of
Protection
Protective Class
Input Power
Supply