3 Wiring
E-28
3.3 Molded-Case Circuit Breakers and Fuses
Using an AC Power Supply
Use a molded-case circuit breaker and fuse to protect the power supply line.
They protect the power line by shutting OFF the circuit when overcurrent is
detected. Select these devices based on the information in the following tables.
Note: The following tables provide the net values of the current capacity and
inrush current. Select a fuse and a molded-case circuit breaker that meet the
following conditions.
• Main circuit and control circuit: No breaking at three times the current
value given in the table for 5 s.
• Inrush current: No breaking at the current value given in the table for
20 ms.
-7S SERVOPACKs
Main
Circuit
Power
Supply
Maxi-
mum Ap-
plicable
Motor Ca-
pacity
[kW]
SERVO-
PACK
Model:
SGD7S-
Power
Supply
Capacity
per
SERVO-
PACK
[kVA]*
Current Capacity
Inrush Current
Rated
Voltage
Main
Circuit
[Arms]
*
Control
Power
Supply
[Arms]
Main
Circuit
[A0-p]
Control
Power
Supply
[A0-p]
Fuse
[V]
MCCB
[V]
Three-
phase,
200
VAC
0.05
R70A
0.2
0.4
0.2
34
34
250
240
0.1
R90A
0.3
0.8
0.2
1R6A
0.5
1.3
0.4
2R8A
1.0
2.5
0.5
3R8A
1.3
3.0
0.75
5R5A
1.6
4.1
1.0
7R6A
2.3
5.7
1.5
120A
3.2
7.3
2.0
180A
4.0
10
0.25
3.0
200A
5.9
15
5.0
330A
7.5
25
0.3
68
6.0
470A
10.7
29
7.5
550A
14.6
37
11
590A
21.7
54
0.4
114
15
780A
29.6
73
Continued on next page.