3.2 Operations
3-47
9
head1
3
Utility Function Mode
(1) Preparation
The following conditions must be met to initialize the vibration detection level.
• The write prohibited setting (Fn010) must not be set to write-protect parameters.
• The test without a motor function must be disabled (Pn00C.0 = 0).
(2) Operating Procedure
Use the following procedure.
• The vibration may not be detected because of improper
servo gains. Also, not all kinds of vibrations can be
detected. Use the detection result as a guideline.
• Set a proper moment of inertia ratio (Pn103). Improper
setting may result in the vibration alarm, warning misde-
tection, or non-detection.
• The references that are used to operate your system must
be input to execute this function.
• Execute this function under the operating condition for
which the vibration detection level should be set.
• Execute this function while the motor speed reaches at
least 10% of its maximum.
Step
Display after Operation
Keys
Operation
1
Press the
Key to view the main
menu for the utility function mode.
Use the
or
Key to move
through the list and select Fn01B.
2
Press the
Key. The display changes
to the Fn01B execution display.
3
Press the
Key.
“Init” is displayed flashing, and the vibra-
tion level is detected and initialized.
Note: Continues initialization until the
Key is pressed again.
R U N
−
F U N C T I O N
−
F n 0 1 4 : O p t I n i t
F n 0 1 B : V i b l
−
v l I n i t
F n 0 1 E : S v M o t O p I D
F n 0 1 F : F B O p M o t I D
L e v e l I n i t
R U N
V i b r a t i o n D e t e c t
S t a r t : [ D A T A ]
R e t u r n : [ S E T ]
L e v e l I n i t
R U N
V i b r a t i o n D e t e c t
I n i t