![YASKAWA JEPMC-MP2300 User Manual Download Page 35](http://html.mh-extra.com/html/yaskawa/jepmc-mp2300/jepmc-mp2300_user-manual_907070035.webp)
2.2 MP2300 Basic Module Functions
2-7
2
Module Specifications
( 2 ) Indicators
The following table shows the indicators that show the operating status of the Basic Module and error information.
For details on indicator meanings, refer to
6.3.3 ( 2 ) LED Indicator Meanings
on page 6-7.
( 3 ) Switch Settings
The DIP switch sets the operating conditions for the Basic Module when the power is turned ON.
Indicator
Color
Status
RDY
Green
Lit during normal operation.
RUN
Green
Lit during execution of user program.
ALM
Red
Lit/blinking when warning occurs.
ERR
Red
Lit/blinking when malfunction occurs.
TX
Green
Lit during transmission of
MECHATROLINK I/II data.
BAT
Red
Lit during battery alarm.
RDY
ALM
TX
RUN
ERR
BAT
SW1
OFF
ޓޓޓ
ON
STOP
SUP
INIT
CNFG
MON
TEST
123456
No.
Name
Setting
Operating Mode
Default
Setting
Details
6
STOP
ON
User program stopped
OFF
Stops the user program execution. Enabled only
when the power is turned ON.
OFF
User program running
5
SUP
ON
System use
OFF
Always leave set to OFF.
OFF
Normal operation
4
INIT
ON
Memory clear
OFF
Set to ON to clear the memory. If this switch is set
to OFF, the program stored in flash memory will
be executed.
OFF
Normal operation
3
CNFG
ON
Configuration mode
OFF
Set to ON to execute self-configuration for
connected devices.
OFF
Normal operation
2
MON
ON
System use
OFF
Always leave set to OFF.
OFF
Normal operation
1
TEST
ON
System use
OFF
Always leave set to OFF.
OFF