For wires with a cross section of 0.08mm
2
up to 1.5mm
2
.
Pos.
Function
Type
Description
1
+AI 0
I
+ Channel 0
2
DC 24V
O
DC 24V for sensor Channel 0
3
0V
O
Ground for sensor
(with 3 wire measurement)
4
---
---
not connected
5
+AI 0
I
+ Channel 0
6
DC 24V
O
DC 24V for sensor Channel 1
7
0V
O
Ground for sensor
(with 3 wire measurement)
8
---
---
not connected
I: Input, O: Output
At CPU, PROFIBUS and PROFINET the input respectively output area is embedded to
the corresponding address area.
IX - Index for access via CANopen with s = Subindex, depends on number and type of
analog modules
SX - Subindex for access via EtherCAT with Index 6000h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Addr.
Name
Bytes
Function
IX
SX
+0
AI 0
2
Analog value channel 0
6401h/s
01h
+2
AI 1
2
Analog value channel 1
6401h/s+1
02h
No byte of the output area is used by the module.
Pin assignment
In-/Output area
Input area
Output area
VIPA System SLIO
Analog Input
031-1BB60 - AI 2x12Bit 0(4)...20mA - Sensor
HB300 | SM-AIO | | en | 17-05
77