-80 ... 80mV
Meas. range
(funct. no.)
Voltage
(U)
Decimal
(D)
Hex
Range
Formulas
-80 ... 80mV
Siemens S7 format
(11h)
94.07mV
32511
7EFFh
overrange
80mV
27648
6C00h
nominal range
0V
0
0000h
-80mV
-27648
9400h
-94.07mV
-32512
8100h
underrange
-80 ... 80mV
Siemens S7 format
(21h)
100mV
20480
5000h
overrange
80mV
16384
4000h
nominal range
0V
0
0000h
-80mV
-16384
C000h
-100mV
-20480
B000h
underrange
Meas. range
(funct. no.)
Voltage
(U)
Decimal
(D)
Hex
Range
Formulas
0 ... 10V
Siemens S7 format
(10h)
11.76V
32511
7EFFh
overrange
10V
27648
6C00h
nominal range
5V
13824
3600h
0V
0
0000h
-1.76V
-4864
ED00h
underrange
0 ... 10V
Siemens S5 format
(20h)
12.5V
20480
5000h
overrange
10V
16384
4000h
nominal range
5V
8192
2000h
0V
0
0000h
-2V
-3277
F333h
underrange
Voltage
0 ... 10V
VIPA System SLIO
Analog Input
Measuring ranges and function numbers
HB300 | SM-AIO | | en | 17-05
38