Meas. range
(funct. no.)
Current
(I)
Decimal
(D)
Hex
Range
Formulas
0 ... 20mA
Siemens
S7 format
(31h)
23.52mA
32511
7EFFh
overrange
20mA
27648
6C00h
nominal range
10mA
13824
3600h
0mA
0
0000h
-3.52mA
-4864
ED00h
underrange
0 ... 20mA
Siemens
S5 format
(41h)
25.00mA
20480
5000h
overrange
20mA
16384
4000h
nominal range
10mA
8192
2000h
0mA
0
0000h
-4,00mA
-3277
F333h
underrange
4 ... 20mA
Siemens
S7 format
(30h)
22.81mA
32511
7EFFh
overrange
20mA
27648
6C00h
nominal range
12mA
13824
3600h
4mA
0
0000h
1.19mA
-4864
ED00h
underrange
4 ... 20mA
Siemens
S5 format
(40h)
24.00mA
20480
5000h
overrange
20mA
16384
4000h
nominal range
12mA
8192
2000h
4mA
0
0000h
0.8mA
-3277
F333h
underrange
0 ... 20mA / 4KM format
Meas. range
(funct. no.)
Current
(I)
Decimal
(D)
Hex
Range
Formulas
0 ... 20mA
4KM format
(3Fh)
20.457mA
4095
0FFFh
overrange
20mA
4000
0FA0h
nominal range
10mA
2000
07D0h
0mA
0
0000h
---
underrange
Current
0(4) ... 20mA
VIPA System SLIO
Analog Input
Measuring ranges and function numbers
HB300 | SM-AIO | | en | 17-05
40