3.5.1 Technical data
Order no.
031-1BB30
Type
SM 031
Module ID
0401 15C3
Current consumption/power loss
Current consumption from backplane bus
80 mA
Power loss
0.7 W
Technical data analog inputs
Number of inputs
2
Cable length, shielded
200 m
Rated load voltage
DC 24 V
Current consumption from load voltage L+ (without load)
15 mA
Voltage inputs
ü
Min. input resistance (voltage range)
100 kΩ
Input voltage ranges
0 V ... +10 V
Operational limit of voltage ranges
+/-0.3%
Operational limit of voltage ranges with SFU
-
Basic error limit voltage ranges
+/-0.2%
Basic error limit voltage ranges with SFU
-
Destruction limit voltage
max. 30V
Current inputs
-
Max. input resistance (current range)
-
Input current ranges
-
Operational limit of current ranges
-
Operational limit of current ranges with SFU
-
Basic error limit current ranges
-
Radical error limit current ranges with SFU
-
Destruction limit current inputs (voltage)
-
Destruction limit current inputs (electrical current)
-
Resistance inputs
-
Resistance ranges
-
Operational limit of resistor ranges
-
Operational limit of resistor ranges with SFU
-
Basic error limit
-
Basic error limit with SFU
-
Destruction limit resistance inputs
-
Resistance thermometer inputs
-
VIPA System SLIO
Analog Input
031-1BB30 - AI 2x12Bit 0...10V > Technical data
HB300 | SM-AIO | | en | 17-05
61