YASKAWA HB300 Manual Download Page 1

SM-AIO | | Manual

HB300 | SM-AIO | | en | 17-05

VIPA System SLIO

Analog signal modules - SM 03x

www.vipa.com/en/service-support/manual

Summary of Contents for HB300

Page 1: ...SM AIO Manual HB300 SM AIO en 17 05 VIPA System SLIO Analog signal modules SM 03x www vipa com en service support manual ...

Page 2: ...SLIO_SM AIO 13 GB 2017 VIPA GmbH Ohmstr 4 91074 Herzogenaurach Telephone 09132 744 0 Fax 09132 744 1864 Email info vipa com Internet www vipa com ...

Page 3: ...37 3 4 031 1BB10 AI 2x12Bit 0 4 20mA ISO 47 3 4 1 Technical data 49 3 4 2 Parameter data 52 3 4 3 Diagnostics and interrupt 54 3 5 031 1BB30 AI 2x12Bit 0 10V 59 3 5 1 Technical data 61 3 5 2 Parameter data 63 3 5 3 Diagnostic data 64 3 6 031 1BB40 AI 2x12Bit 0 4 20mA 67 3 6 1 Technical data 69 3 6 2 Parameter data 72 3 6 3 Diagnostic data 73 3 7 031 1BB60 AI 2x12Bit 0 4 20mA Sensor 76 3 7 1 Techni...

Page 4: ...x16 24 Bit Strain gauge DMS 171 3 16 1 Connection variants 173 3 16 2 In Output area 175 3 16 3 Technical data 178 3 16 4 Functionality 180 3 16 5 Parameter data 181 3 16 6 Deployment of the filter functions 185 3 16 7 Calibration 186 3 16 8 Steady state detection 186 3 16 9 Diagnostics 187 3 17 031 1CB30 AI 2x16Bit 0 10V 190 3 17 1 Technical data 192 3 17 2 Parameter data 195 3 17 3 Diagnostics a...

Page 5: ...arameter data 295 3 26 3 Diagnostic data 299 3 27 031 1PA00 AI1x 3Ph 230 400V 1A 302 3 27 1 Technical data 305 3 27 2 Safety precautions 307 3 27 3 Basics 309 3 27 4 Connection 312 3 27 5 Parameter data 314 3 27 6 Measurands 316 3 27 7 Process data communication 318 3 27 8 Error messages and diagnostics 329 3 27 9 Use handling block 332 4 Analog Output 336 4 1 General 336 4 2 Analog value 336 4 3 ...

Page 6: ...ata 396 4 11 032 1CB40 AO 2x16Bit 0 4 20mA 399 4 11 1 Technical data 401 4 11 2 Parameter data 403 4 11 3 Diagnostic data 404 4 12 032 1CB70 AO 2x16Bit 10V 408 4 12 1 Technical data 410 4 12 2 Parameter data 412 4 12 3 Diagnostic data 413 4 13 032 1CD30 AO 4x16Bit 0 10V 417 4 13 1 Technical data 419 4 13 2 Parameter data 421 4 13 3 Diagnostic data 422 4 14 032 1CD40 AO 4x16Bit 0 4 20mA 425 4 14 1 ...

Page 7: ...pective purchase contract Hereby VIPA GmbH declares that the products and systems are in compliance with the essential requirements and other relevant provisions Conformity is indicated by the CE marking affixed to the product For more information regarding CE marking and Declaration of Conformity DoC please contact your local VIPA customer service organization VIPA SLIO System 100V System 200V Sy...

Page 8: ...of chapters Every chapter provides a self contained description of a specific topic The following guides are available in the manual n An overall table of contents at the beginning of the manual n References with page numbers The manual is available in n printed form on paper n in electronic form as PDF file Adobe Acrobat Reader Important passages in the text are highlighted by following icons and...

Page 9: ... department n commissioning n operation CAUTION The following conditions must be met before using or commis sioning the components described in this manual Hardware modifications to the process control system should only be carried out when the system has been disconnected from power Installation and hardware modifications only by properly trained per sonnel The national rules and regulations of t...

Page 10: ...les that have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in the electrical load Only the consequent implementation of protection devices and meticulous attention to the applicable rules and regulations for handling the respective equipment can prevent failures of electrostatic sensitive modules Modules must be shipped in the original pa...

Page 11: ...mplexity is low because the supply of the DC 24V power section is integrated to the backplane bus and defective modules may be replaced with standing wiring By deployment of the power modules in contrasting colors within the system further isolated areas may be defined for the DC 24V power section supply respectively the electronic power supply may be extended with 2A VIPA System SLIO Basics and m...

Page 12: ...ectronic and the electronic of the connected periphery modules are supplied The DC 24 power section supply for the linked periphery modules is established via a further connection of the power module By installing of up to 64 periphery modules at the backplane bus these are electrically connected this means these are assigned to the backplane bus the elec tronic modules are power supplied and each...

Page 13: ...e line extension no special con figuration is required Each periphery module consists of a terminal and an electronic module 1 Terminal module 2 Electronic module The terminal module serves to carry the electronic module contains the backplane bus with power supply for the electronic the DC 24V power section supply and the staircase shaped terminal for wiring Additionally the terminal module has a...

Page 14: ...the shield bus carrier With each head module to protect the backplane bus connectors there is a mounted bus cover in the scope of delivery You have to remove the bus cover of the head module before mounting a System SLIO module For the protection of the backplane bus con nector you always have to mount the bus cover at the last module of your system again The bus cover has the order no 000 0AA00 T...

Page 15: ...2 3 Dimensions Dimensions CPU 01xC Dimensions CPU 01x VIPA System SLIO Basics and mounting Dimensions HB300 SM AIO en 17 05 15 ...

Page 16: ...Dimensions bus coupler and line extension slave Dimensions line extension master VIPA System SLIO Basics and mounting Dimensions HB300 SM AIO en 17 05 16 ...

Page 17: ...Dimensions in mm Dimension periphery module Dimensions electronic module VIPA System SLIO Basics and mounting Dimensions HB300 SM AIO en 17 05 17 ...

Page 18: ...h locking lever is opened The modules are each installed on a mounting rail The electronic and power section supply are connected via the backplane bus Up to 64 modules may be mounted Please consider here that the sum current of the electronic power supply does not exceed the maximum value of 3A By means of the power module 007 1AB10 the current of the electronic power supply may be expanded accor...

Page 19: ...possible combinations for coding with the use of both coding sockets 1 Plug according to your coding 2 coding jacks in the coding sockets of your elec tronic module until they lock 2 Now plug the according coding plugs into the coding jacks 3 To fix the coding put both the electronic and terminal module together until they lock CAUTION Please consider that when replacing an already coded electroni...

Page 20: ...cover at the right side of the Head module by pulling it forward Keep the cover for later mounting 4 For mounting turn the locking lever of the module upward until it engages 5 For mounting place the module to the module installed before and push the module to the mounting rail guided by the strips at the upper and lower side of the module 6 Turn the locking lever of the periphery module downward ...

Page 21: ...nnected to the corresponding terminal module With wiring the terminal modules terminals with spring clamp technology are used for wiring The spring clamp technology allows quick and easy connection of your signal and supply lines In contrast to screw terminal connections this type of connection is vibration proof Umax 240V AC 30V DC Imax 10A Cross section 0 08 1 5mm2 AWG 28 16 Stripping length 10m...

Page 22: ...the mounting of shield bus carriers are necessary The shield bus carrier available as accessory serves to carry the shield bus to connect cable shields 1 Each System SLIO module has a carrier hole for the shield bus carrier Push the shield bus carrier until they engage into the module With a flat mounting rail for adaptation to a flat mounting rail you may remove the spacer of the shield bus car r...

Page 23: ... 08 1 5mm2 AWG 28 16 Stripping length 10mm 1 Pin number at the connector 2 Opening for screwdriver 3 Connection hole for wire 1 Insert a suited screwdriver at an angel into the square opening as shown Press and hold the screwdriver in the opposite direction to open the contact spring 2 Insert the stripped end of wire into the round opening You can use wires with a cross section of 0 08mm2 up to 1 ...

Page 24: ...on supply 8 Sys 0V I GND for electronic section supply I Input CAUTION Since the power section supply is not internally protected it is to be exter nally protected with a fuse which corresponds to the maximum current This means max 10A is to be protected by a 10A fuse fast respectively by a line circuit breaker 10A characteristics Z The electronic power section supply is internally protected again...

Page 25: ...be activated Here the power module with the order number 007 1AB10 is to be placed between the peripheral modules n If the 10A for the power section supply is no longer sufficient you may use the power module from VIPA with the order number 007 1AB00 So you have also the possibility to define isolated groups n The power module with the order number 007 1AB10 is to be used if the 3A for the electro...

Page 26: ... are necessary The shield bus carrier available as accessory serves to carry the shield bus to connect cable shields 1 Each System SLIO module has a carrier hole for the shield bus carrier Push the shield bus carrier until they engage into the module With a flat mounting rail for adaptation to a flat mounting rail you may remove the spacer of the shield bus car rier 2 Put your shield bus into the ...

Page 27: ...3 Attach the cables with the accordingly stripped cable screen and fix it by the shield clamp with the shield bus VIPA System SLIO Basics and mounting Wiring power modules HB300 SM AIO en 17 05 27 ...

Page 28: ...tion 1 Power off your system 2 Remove if exists the wiring of the module 3 For demounting and exchange of a head module or a group of modules due to mounting reasons you always have to remove the electronic module right beside After mounting it may be plugged again Press the unlocking lever at the lower side of the just mounted right module and pull it forward 4 Turn the locking lever of the modul...

Page 29: ...nto operation 1 Power off your system 2 Remove if exists the wiring of the module group 3 For demounting and exchange of a head module or a group of modules due to mounting reasons you always have to remove the electronic module right beside After mounting it may be plugged again Press the unlocking lever at the lower side of the just mounted right module near the module group and pull it forward ...

Page 30: ...een the both modules and push it guided by the stripes at both sides to the mounting rail 8 Turn all the locking lever downward again 9 Plug again the electronic module which you have removed before 10 Wire your module group ð Now you can bring your system back into operation VIPA System SLIO Basics and mounting Demounting periphery modules HB300 SM AIO en 17 05 30 ...

Page 31: ...ring power modules on page 23 Behaviour After PowerON the MF LED of one module respectively more modules flashes The RUN LED remains off Reason At this position a module is placed which does not correspond to the configured module Remedy Match configuration and hardware structure Behaviour After PowerON all of the RUN LEDs up to the defective module are flashing With all following modules the MF L...

Page 32: ...ce to the interference cause interferences to your control occur by means of different coupling mechanisms There are n galvanic coupling n capacitive coupling n inductive coupling n radiant coupling In the most times it is enough to take care of some elementary rules to guarantee the EMC Please regard the following basic rules when installing your PLC n Take care of a correct area wide grounding o...

Page 33: ...earth conductor is impedance low because otherwise the interference currents may appear as interference cause When isolating cables you have to regard the following n If possible use only cables with isolation tangle n The hiding power of the isolation should be higher than 80 n Normally you should always lay the isolation of cables on both sides Only by means of the both sided connection of the i...

Page 34: ... Insulation voltage to reference earth Inputs outputs AC DC 50V test voltage AC 500V Protective measures against short circuit Environmental conditions to EN 61131 2 Climatic Storage transport EN 60068 2 14 25 70 C Operation Horizontal installation hanging EN 61131 2 0 60 C Horizontal installation lying EN 61131 2 0 55 C Vertical installation EN 61131 2 0 50 C Air humidity EN 60068 2 30 RH1 withou...

Page 35: ...rity 2 EN 61000 4 3 HF field immunity casing 80MHz 1000MHz 10V m 80 AM 1kHz 1 4GHz 2 0GHz 3V m 80 AM 1kHz 2GHz 2 7GHz 1V m 80 AM 1kHz EN 61000 4 6 HF conducted 150kHz 80MHz 10V 80 AM 1kHz EN 61000 4 4 Burst degree of severity 3 EN 61000 4 5 Surge degree of severity 3 Due to the high energetic single pulses with Surge an appropriate external protective circuit with lightning protection elements lik...

Page 36: ...ording channel The parameterization via CPU PROFIBUS and PROFINET happens by means of record sets DS The corresponding record set number may be found at the respective module description Here also the indices IX respectively subindices SX for CANopen respec tively EtherCAT are listed The modules have diagnostics capability The following errors can release a diagnostic n Error in parameterization n...

Page 37: ...oon as a measured value exceeds the overdrive region respectively falls below the underdrive region the following value is issued n Measuring value end of overdrive region 32767 7FFFh n Measuring value end of underdrive region 32768 8000h At a parameterization error the value 32767 7FFFh is issued 3 3 Measuring ranges and function numbers In the following there are the measuring ranges with functi...

Page 38: ...ange 0V 0 0000h 80mV 16384 C000h 100mV 20480 B000h underrange Meas range funct no Voltage U Decimal D Hex Range Formulas 0 10V Siemens S7 format 10h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h 1 76V 4864 ED00h underrange 0 10V Siemens S5 format 20h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V 8192 2000h 0V 0 0000h 2V 3277 F333h underrange Vo...

Page 39: ...13824 3600h 0V 0 0000h 5V 13824 CA00h 10V 27648 9400h 11 76V 32512 8100h underrange 10V Siemens S5 format 22h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V 8192 2000h 0V 0 0000h 5V 8192 E000h 10V 16384 C000h 12 5V 20480 B000h underrange 10V VIPA System SLIO Analog Input Measuring ranges and function numbers HB300 SM AIO en 17 05 39 ...

Page 40: ...t 30h 22 81mA 32511 7EFFh overrange 20mA 27648 6C00h nominal range 12mA 13824 3600h 4mA 0 0000h 1 19mA 4864 ED00h underrange 4 20mA Siemens S5 format 40h 24 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 12mA 8192 2000h 4mA 0 0000h 0 8mA 3277 F333h underrange 0 20mA 4KM format Meas range funct no Current I Decimal D Hex Range Formulas 0 20mA 4KM format 3Fh 20 457mA 4095 0FFFh overrange ...

Page 41: ...430 underrange 3 wire PT1000 59h 1000 C 10000 overrange 200 850 C 2000 8500 nominal range 243 C 2430 underrange 3 wire NI100 5Ah 295 C 2950 overrange 60 250 C 600 2500 nominal range 105 C 1050 underrange 3 wire NI1000 5Bh 295 C 2950 overrange 60 250 C 600 2500 nominal range 105 C 1050 underrange 4 wire PT100 60h 1000 C 10000 overrange 200 850 C 2000 8500 nominal range 243 C 2430 underrange 4 wire ...

Page 42: ... underrange 3 wire 0 600W 79h overrange 0 600W 0 32767 nominal range underrange 3 wire 0 3000W 7Ah overrange 0 3000W 0 32767 nominal range underrange 4 wire 0 60W 80h overrange 0 60W 0 32767 nominal range underrange 4 wire 0 600W 81h overrange 0 600W 0 32767 nominal range underrange 4 wire 0 3000W 82h overrange 0 3000W 0 32767 nominal range underrange 2 wire 0 60W 90h overrange 0 60W 0 6000 nomina...

Page 43: ...0W A1h overrange 0 600W 0 6000 nominal range underrange 4 wire 0 3000W A2h overrange 0 3000W 0 30000 nominal range underrange 2 wire 0 60W D0h 70 55W 32511 overrange 0 60W 0 27648 nominal range underrange 2 wire 0 600W D1h 705 5W 32511 overrange 0 600W 0 27648 nominal range underrange 2 wire 0 3000W D2h 3528W 32511 overrange 0 3000W 0 27648 nominal range underrange 3 wire 0 60W D8h 70 55W 32511 ov...

Page 44: ...ng value in C 0 1 C digit Measuring value in F 0 1 F digit Measuring value in K 0 1K digit Range Type J Fe Cu Ni IEC 210 1200 C 346 2192 F 63 2 1473 2K B0h ext comp 0 C C0h int comp 0 C 14500 26420 17232 overrange 2100 12000 3460 21920 632 14732 nominal range underrange Type K Ni Cr Ni 270 1372 C 454 2501 6 F 0 1645 2K B1h ext comp 0 C C1h int comp 0 C 16220 29516 18952 overrange 2700 13720 4540 2...

Page 45: ...17690 580 32162 2232 20422 nominal range 1700 2740 1032 underrange Type T Cu Cu Ni 270 400 C 454 752 F 3 2 673 2K B5h ext comp 0 C C5h int comp 0 C 5400 10040 8132 overrange 2700 4000 4540 7520 32 6732 nominal range underrange Type B PtRh PtRh 0 1820 C 32 2786 5 F 273 2 2093 2K B6h ext comp 0 C C6h int comp 0 C 20700 32766 23432 overrange 0 18200 320 27865 2732 20932 nominal range 1200 1840 1532 u...

Page 46: ...K B8h ext comp 0 C C8h int comp 0 C 12000 21920 14732 overrange 2700 10000 4540 18320 0 12732 nominal range underrange Type L Fe Cu Ni 200 900 C 328 1652 F 73 2 1173 2K B9h ext comp 0 C C9h int comp 0 C 11500 21020 14232 overrange 2000 9000 3280 16520 732 11732 nominal range underrange VIPA System SLIO Analog Input Measuring ranges and function numbers HB300 SM AIO en 17 05 46 ...

Page 47: ...ackplane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in...

Page 48: ... is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h No byte of...

Page 49: ... voltage ranges with SFU Destruction limit voltage Current inputs ü Max input resistance current range 60 Ω Input current ranges 4 mA 20 mA 0 mA 20 mA Operational limit of current ranges 0 5 Operational limit of current ranges with SFU Basic error limit current ranges 0 3 Radical error limit current ranges with SFU Destruction limit current inputs voltage max 24V Destruction limit current inputs e...

Page 50: ...on External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 12 Measurement principle successive approximation Basic conversion time 1 15 ms all channels Noise suppression for frequency 80dB UCM 20V Technical data sensor supply Output voltage typ 2 Output voltage typ 24 V 1 5 V Output curr...

Page 51: ...l difference between inputs and Mana Ucm DC 75 V AC 50 V Max potential difference between inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 4 Output bytes 0 Parameter bytes 20 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm...

Page 52: ... 08h CH1FN 1 Function number channel 1 31h 81h 310Ah 09h CH1FO 1 Function option channel 1 00h 81h 310Bh 0Ah CH1UL 2 Upper limit value channel 1 7FFFh 81h 310Ch 310Dh 0Bh CH1LL 2 Lower limit value channel 1 8000h 81h 310Eh 310Fh 0Ch This record set may only be transferred at STOP state Byte Bit 7 0 0 n Diagnostic interrupt 00h disabled 40h enabled n Here you can enable respectively disable the dia...

Page 53: ...nge 0 20mA Siemens S5 format 41h 25 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 10mA 8192 2000h 0mA 0 0000h 4 00mA 3277 F333h underrange 4 20mA Siemens S7 format 30h 22 81mA 32511 7EFFh overrange 20mA 27648 6C00h nominal range 12mA 13824 3600h 4mA 0 0000h 1 19mA 4864 ED00h underrange 4 20mA Siemens S5 format 40h 24 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 12mA 8192 2...

Page 54: ...reset otherwise you receive a parameterization error By preset ting 7FFFh for the upper respectively 8000h for the lower limit value the corresponding limit is deactivated As soon as the measuring value is beyond the limits and the limit value monitoring is activated a process interrupt is initialized 3 4 3 Diagnostics and interrupt Event Process interrupt Diagnostics inter rupt parameterizable Er...

Page 55: ...0 n Bit 1 Lower limit underflow channel 1 n Bit 7 2 reserved Byte Bit 7 0 0 1 16bit µs value at the moment of the interrupt µs ticker In the SLIO module there is a 32 bit timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again PRIT_US represents the lower 2 byte of the µs ticker value 0 216 1 Via the parameterization you may activate a diagnostic i...

Page 56: ...tic bits per channel 08h 07h NUMCH 1 Number of channels of a module 02h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR CH7ERR 6 reserved 00h 0Ch 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at channel e...

Page 57: ...nel group 0 n Bit 1 set at error in channel group 1 n Bit 7 2 reserved Byte Bit 7 0 0 Channel specific error Channel x n Bit 0 set at project engineering parameterization error n Bit 1 row value above the permissible range n Bit 2 row value below the acceptable range n Bit 3 reserved n Bit 4 error sensor supply voltage n Bit 5 set at process interrupt lost n Bit 6 set at measuring range underflow ...

Page 58: ... ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again DIAG_US µs ticker VIPA System SLIO Analog Input 031 1BB10 AI 2x12Bit 0 4 20mA ISO Diagnostics and interrupt HB300 SM AIO en 17 05 58 ...

Page 59: ...4V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble shooti...

Page 60: ...ng address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h No byte of the output area is used by the...

Page 61: ...ges 0 2 Basic error limit voltage ranges with SFU Destruction limit voltage max 30V Current inputs Max input resistance current range Input current ranges Operational limit of current ranges Operational limit of current ranges with SFU Basic error limit current ranges Radical error limit current ranges with SFU Destruction limit current inputs voltage Destruction limit current inputs electrical cu...

Page 62: ...le temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 12 Measurement principle successive approximation Basic conversion time 2 ms all channels Noise suppression for frequency 50dB at 50Hz UCM 2V Status information alarms diagnostics Status display yes Inter...

Page 63: ...tes 4 Output bytes 0 Parameter bytes 6 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes KC certification yes 3 5 2 Parameter data DS Record set for access via CPU PROFIBUS...

Page 64: ...h 0V 0 0000h 2V 3277 F333h underrange 3 5 3 Diagnostic data This module does not support diagnostic interrupt functions the diagnostics data serve for information about this module On error the corresponding channel LED of the module is activated and the error is registered in the diagnostics data The following errors are listed in the diagnostics data n Error in project engineering parameterizati...

Page 65: ...00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set at external auxiliary supply missing n Bit 6 5 reserved n Bit 7 set at error in parameterization Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 rese...

Page 66: ... n Bit 0 set at configuring parameter assignment error n Bit 5 1 reserved n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again CHT...

Page 67: ...dication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8...

Page 68: ...d PROFINET the input respectively output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 An...

Page 69: ...sic error limit voltage ranges Basic error limit voltage ranges with SFU Destruction limit voltage Current inputs ü Max input resistance current range 110 Ω Input current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 3 0 5 Operational limit of current ranges with SFU Basic error limit current ranges 0 2 0 3 Radical error limit current ranges with SFU Destruction limit current ...

Page 70: ...moelement ranges with SFU Destruction limit thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 12 Measurement principle successive approximation Basic conversion time 2 ms all channels Noise suppression for frequency 50dB at ...

Page 71: ...n inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 4 Output bytes 0 Parameter bytes 6 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage...

Page 72: ...a value assigned to the measuring range analog value and vice versa Meas range funct no Current I Decimal D Hex Range Formulas 0 20mA Siemens S7 format 31h 23 52mA 32511 7EFFh overrange 20mA 27648 6C00h nominal range 10mA 13824 3600h 0mA 0 0000h 3 52mA 4864 ED00h underrange 0 20mA Siemens S5 format 41h 25 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 10mA 8192 2000h 0mA 0 0000h 4 00mA ...

Page 73: ...pen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h More can be found in the according manual of your bus coupler Name Bytes Function Default DS IX SX ERR_A 1 Diagnostic 00h 01h 2F01h 02h MODTYP 1 Module information 15h 03h ERR_C 1 reserved 00h 04h ERR_D 1 Diagnostic 00h 05h CHTYP 1 Channel type 71h 06h ...

Page 74: ...l communication error n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input output 76h Counter n Bit 7 reserved Byte Bit 7 0 0 Number of diagnostic bits per channel here 08h Byte Bit 7 0 0 Number of channels of a module here 02h Byte Bit 7 0 0 n Bit 0 set at error in channel group 0 n Bit 1 set at error in ...

Page 75: ...Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again CH0ERR CH1ERR Channel specific CH2ERR CH7ERR reserved DIAG_US µs ticker VIPA System SLIO Analog Input 031 1BB40 AI 2x12Bit 0 4 20mA Diagnostic data HB300 SM AIO en...

Page 76: ...Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble shooting LEDs on page 31 Error channel x n Signal leaves measuring range n Error in parameterization on ...

Page 77: ...ely output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1...

Page 78: ...oltage ranges with SFU Destruction limit voltage Current inputs ü Max input resistance current range 110 Ω Input current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 5 Operational limit of current ranges with SFU Basic error limit current ranges 0 3 Radical error limit current ranges with SFU Destruction limit current inputs voltage max 24V Destruction limit current inputs el...

Page 79: ...ble temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 12 Measurement principle successive approximation Basic conversion time 2 ms all channels Noise suppression for frequency 50dB at 50Hz UCM 2V Technical data sensor supply Output voltage typ 2 Output volt...

Page 80: ... between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 4 Output bytes 0 Parameter bytes 6 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Enviro...

Page 81: ...lue assigned to the measuring range analog value and vice versa Meas range funct no Current I Decimal D Hex Range Formulas 0 20mA Siemens S7 format 31h 23 52mA 32511 7EFFh overrange 20mA 27648 6C00h nominal range 10mA 13824 3600h 0mA 0 0000h 3 52mA 4864 ED00h underrange 0 20mA Siemens S5 format 41h 25 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 10mA 8192 2000h 0mA 0 0000h 4 00mA 3277...

Page 82: ...The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h More can be found in the according manual of your bus coupler Name Bytes Function Default DS IX SX ERR_A 1 Diagnostic 00h 01h 2F01h 02h MODTYP 1 Module information 15h 03h ERR_C 1 reserved 00h 04h ERR_D 1 Diagnostic 00h 05h CHTYP 1 Channel type 71h 06h NUMB...

Page 83: ...mmunication error n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input output 76h Counter n Bit 7 reserved Byte Bit 7 0 0 Number of diagnostic bits per channel here 08h Byte Bit 7 0 0 Number of channels of a module here 02h Byte Bit 7 0 0 n Bit 0 set at error in channel group 0 n Bit 1 set at error in chan...

Page 84: ...7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again CH0ERR CH1ERR Channel specific CH2ERR CH7ERR reserved DIAG_US µs ticker VIPA System SLIO Analog Input 031 1BB60 AI 2x12Bit 0 4 20mA Sensor Diagnostic data HB300 SM AIO...

Page 85: ... 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble shoo...

Page 86: ...ing address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h No byte of the output area is used by th...

Page 87: ...ror limit voltage ranges 0 2 Basic error limit voltage ranges with SFU Destruction limit voltage max 30V Current inputs Max input resistance current range Input current ranges Operational limit of current ranges Operational limit of current ranges with SFU Basic error limit current ranges Radical error limit current ranges with SFU Destruction limit current inputs voltage Destruction limit current...

Page 88: ... thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 12 Measurement principle successive approximation Basic conversion time 2 ms all channels Noise suppression for frequency 50dB at 50Hz UCM 2V Status information alarms diagn...

Page 89: ...tasizes Input bytes 4 Output bytes 0 Parameter bytes 6 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes KC certification yes 3 8 2 Parameter data DS Record set for access ...

Page 90: ... to a value assigned to the measuring range analog value and vice versa Meas range funct no Voltage U Decimal D Hex Range Formulas 10V Siemens S7 format 12h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h 5V 13824 CA00h 10V 27648 9400h 11 76V 32512 8100h underrange 10V Siemens S5 format 22h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V 8192 2000h...

Page 91: ...eering parameterization n Measuring range overflow n Measuring range underflow DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by DS 00h IX Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h More ...

Page 92: ...0 module class 0101b analog module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer overflow n Bit 4 set at internal communication error n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input output 76h Counter n Bit 7 ...

Page 93: ...asuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMCH Channels CHERR Channel error CH0ERR CH1ERR Channel specific CH2ERR CH7ERR reserved DIAG_...

Page 94: ...lane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in con...

Page 95: ... following points when assembling n Do not arrange the module directly apart from a power module with a high feeding current n Do not install the module at the end of a line n The module should be in a static condition i e the temperature should be as constant as possible in the environment of your module closed switchgear cabinet free from air draught n The accuracy is reached after approx 30 min...

Page 96: ...echnical data analog inputs Number of inputs 2 Cable length shielded 200 m Rated load voltage DC 24 V Current consumption from load voltage L without load 30 mA Voltage inputs Min input resistance voltage range 10 MΩ Input voltage ranges 80 mV 80 mV Operational limit of voltage ranges 0 3 Operational limit of voltage ranges with SFU 0 1 Basic error limit voltage ranges 0 25 Basic error limit volta...

Page 97: ...it thermoresistor ranges with SFU Destruction limit resistance thermometer inputs Thermocouple inputs ü Thermocouple ranges type B type C type E type J type K type L type N type R type S type T Operational limit of thermocouple ranges Type E L T J K N 2 5K Type B C R S 8 0K Operational limit of thermocouple ranges with SFU Type E L T J K N 1 5K Type B C R S 4 0K Basic error limit thermoelement ran...

Page 98: ...y red LED Channel error display red LED per channel Isolation Between channels Between channels of groups to Between channels and backplane bus ü Between channels and power supply Max potential difference between circuits Max potential difference between inputs Ucm DC 75 V AC 50 V Max potential difference between Mana and Mintern Uiso Max potential difference between inputs and Mana Ucm Max potent...

Page 99: ...ication yes KC certification yes The indicated error limits are valid starting from the following temperatures n Thermoelement type T 200 C n Thermoelement type K 100 C n Thermoelement type B 700 C n Thermoelement type N 150 C n Thermoelement type E 150 C n Thermoelement type R 200 C n Thermoelement type S 100 C n Thermoelement type J 100 C VIPA System SLIO Analog Input 031 1BB90 AI 2x16Bit TC Tec...

Page 100: ...el 0 02h 80h 3107h 08h CH0UL 2 Upper limit value channel 0 7FFFh 80h 3108h 3109h 09h CH0LL 2 Lower limit value channel 0 8000h 80h 310Ah 310Bh 0Ah CH1FN 1 Function number channel 1 C1h 81h 310Ch 0Bh CH1FO 1 Function option channel 1 02h 81h 310Dh 0Ch CH1UL 2 Upper limit value channel 1 7FFFh 81h 310Eh 310Fh 0Dh CH1LL 2 Lower limit value channel 1 8000h 81h 3110h 3111h 0Eh This record set may only ...

Page 101: ...h the corresponding channel is deactivated 80 80mV Meas range funct no Voltage U Decimal D Hex Range Formulas 80 80mV Siemens S7 format 11h 94 07mV 32511 7EFFh overrange 80mV 27648 6C00h nominal range 0V 0 0000h 80mV 27648 9400h 94 07mV 32512 8100h underrange 80 80mV Siemens S7 format 21h 100mV 20480 5000h overrange 80mV 16384 4000h nominal range 0V 0 0000h 80mV 16384 C000h 100mV 20480 B000h under...

Page 102: ...rrange Type N Ni Cr Si 270 1300 C 454 2372 F 0 1573 2K B2h ext comp 0 C C2h int comp 0 C 15500 28220 18232 overrange 2700 13000 4540 23720 0 15732 nominal range underrange Type R PtRh Pt 50 1769 C 58 3216 2 F 223 2 2042 2K B3h ext comp 0 C C3h int comp 0 C 20190 32766 22922 overrange 500 17690 580 32162 2232 20422 nominal range 1700 2740 1032 underrange Type S PtRh Pt 50 1769 C 58 3216 2 F 223 2 2...

Page 103: ...t comp 0 C C7h int comp 0 C 25000 32766 23432 overrange 0 23150 320 27865 2732 20932 nominal range 1200 1840 1532 underrange Type E Ni Cr Cu Ni 270 1000 C 454 1832 F 0 1273 2K B8h ext comp 0 C C8h int comp 0 C 12000 21920 14732 overrange 2700 10000 4540 18320 0 12732 nominal range underrange Type L Fe Cu Ni 200 900 C 328 1652 F 73 2 1173 2K B9h ext comp 0 C C9h int comp 0 C 11500 21020 14232 overr...

Page 104: ...t Diagnostics interrupt parameterizable Error in project engineering param X Wire break X X Measuring range overflow X Measuring range underflow X Limit overflow X X Limit underflow X X Diagnostic buffer overflow X Communication error X Process interrupt lost X So you may react to asynchronous events there is the possibility to activate a process interrupt A process interrupt interrupts the linear...

Page 105: ... serves for diagnostics data for diagnostic interruptincoming As soon as the reason for releasing a diagnostic interrupt is no longer present the diag nostic interruptgoing automatically takes place All events of a channel between diagnostic interruptincoming and diagnostic interruptgoing are not stored and get lost Within this time window 1 diagnostic interruptincoming until last diagnostic inter...

Page 106: ...set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set at external auxiliary supply missing n Bit 6 5 reserved n Bit 7 set at error in parameterization Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal di...

Page 107: ...rameterization error n Bit 3 1 reserved n Bit 4 set at wire break n Bit 5 set at process interrupt lost n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the...

Page 108: ...4V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble shooti...

Page 109: ...ss via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h 4 AI 2 2 Analog value channel 2 6401h s 2 03h 6 AI 3 2 Analog value channe...

Page 110: ...ges 0 2 Basic error limit voltage ranges with SFU Destruction limit voltage max 30V Current inputs Max input resistance current range Input current ranges Operational limit of current ranges Operational limit of current ranges with SFU Basic error limit current ranges Radical error limit current ranges with SFU Destruction limit current inputs voltage Destruction limit current inputs electrical cu...

Page 111: ...le temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 12 Measurement principle successive approximation Basic conversion time 4 ms all channels Noise suppression for frequency 50dB at 50Hz UCM 2V Status information alarms diagnostics Status display yes Inter...

Page 112: ...es 8 Output bytes 0 Parameter bytes 8 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes KC certification yes 3 10 2 Parameter data DS Record set for access via CPU PROFIBUS...

Page 113: ...00h overrange 10V 16384 4000h nominal range 5V 8192 2000h 0V 0 0000h 2V 3277 F333h underrange 3 10 3 Diagnostic data So this module does not support diagnostic interrupt functions the diagnostics data serve for information about this module On error the corresponding channel LED of the module is activated and the error is registered in the diagnostics data The following errors are listed in the di...

Page 114: ... error channel 2 00h 0Ch CH3ERR 1 Channel specific error channel 3 00h 0Dh CH4ERR CH 7ERR 4 reserved 00h 0Eh 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set at external auxiliary supply missing n Bit 6 5 reserved n Bit 7 set at error in parameterization Byte Bit 7 0 0 n...

Page 115: ...it 0 set at error in channel group 0 n Bit 1 set at error in channel group 1 n Bit 2 set at error in channel group 2 n Bit 3 set at error in channel group 3 n Bit 7 4 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 5 1 reserved n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserve...

Page 116: ...ostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again DIAG_US µs ticker VIPA System SLIO Analog Input 031 1BD30 AI 4x12Bit 0 10V Diagnostic data HB300 SM AIO en 17 05 116 ...

Page 117: ...dication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8...

Page 118: ... CPU PROFIBUS and PROFINET the input respectively output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s...

Page 119: ... resistance voltage range Input voltage ranges Operational limit of voltage ranges Operational limit of voltage ranges with SFU Basic error limit voltage ranges Basic error limit voltage ranges with SFU Destruction limit voltage Current inputs ü Max input resistance current range 110 Ω Input current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 3 0 5 Operational limit of curre...

Page 120: ...ational limit of thermocouple ranges Operational limit of thermocouple ranges with SFU Basic error limit thermoelement ranges Basic error limit thermoelement ranges with SFU Destruction limit thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement ...

Page 121: ...potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 8 Output bytes 0 Parameter bytes 8 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 m...

Page 122: ...CH2FN 1 Function number channel 2 31h 82h 3102h 03h CH3FN 1 Function number channel 3 31h 83h 3103h 04h In the following there are the measuring ranges with corresponding function number listed which were supported by the analog module With FFh the corresponding channel is deactivated The formulas listed here allow you to transform an evaluated measuring value digital value to a value assigned to ...

Page 123: ...module does not support diagnostic interrupt functions the diagnostics data serve for information about this module On error the corresponding channel LED of the module is activated and the error is registered in the diagnostics data The following errors are listed in the diagnostics data n Error in project engineering parameterization n Measuring range overflow n Measuring range underflow DS Reco...

Page 124: ...ecific error channel 2 00h 0Ch CH3ERR 1 Channel specific error channel 3 00h 0Dh CH4ERR CH7ERR 4 reserved 00h 0Eh 11h DIAG_US 4 µs Ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 reserved n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set at external auxiliary supply missing n Bit 6 5 reserved n Bit 7 set at error in parameterization Byte Bit 7 0 0 n Bit 3 0...

Page 125: ...t 0 set at error in channel group 0 n Bit 1 set at error in channel group 1 n Bit 2 set at error in channel group 2 n Bit 3 set at error in channel group 3 n Bit 7 4 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 5 1 reserved n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved...

Page 126: ...tic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again DIAG_US µs ticker VIPA System SLIO Analog Input 031 1BD40 AI 4x12Bit 0 4 20mA Diagnostic data HB300 SM AIO en 17 05 126 ...

Page 127: ... 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble shoo...

Page 128: ...ess via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h 4 AI 2 2 Analog value channel 2 6401h s 2 03h 6 AI 3 2 Analog value chann...

Page 129: ...ror limit voltage ranges 0 2 Basic error limit voltage ranges with SFU Destruction limit voltage max 30V Current inputs Max input resistance current range Input current ranges Operational limit of current ranges Operational limit of current ranges with SFU Basic error limit current ranges Radical error limit current ranges with SFU Destruction limit current inputs voltage Destruction limit current...

Page 130: ... thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 12 Measurement principle successive approximation Basic conversion time 4 ms all channels Noise suppression for frequency 50dB at 50Hz UCM 2V Status information alarms diagn...

Page 131: ...asizes Input bytes 8 Output bytes 0 Parameter bytes 8 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes KC certification yes 3 12 2 Parameter data DS Record set for access ...

Page 132: ...ou to transform an evaluated measuring value digital value to a value assigned to the measuring range analog value and vice versa Meas range funct no Voltage U Decimal D Hex Range Formulas 10V Siemens S7 format 12h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h 5V 13824 CA00h 10V 27648 9400h 11 76V 32512 8100h underrange 10V Siemens S5 format 22h 12 5V 20480 5...

Page 133: ...ineering parameterization n Measuring range overflow n Measuring range underflow DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by DS 00h IX Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h Mor...

Page 134: ... error in parameterization Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer overflow n Bit 4 set at internal communication error n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog o...

Page 135: ...ror n Bit 5 1 reserved n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMCH Channels CHERR Channel error CH0ERR CH3ERR Chann...

Page 136: ... Backplane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error ...

Page 137: ... 1 AI 0 I Channel 0 2 AI 0 I Ground Channel 0 3 AI 2 I Channel 2 4 AI 2 I Ground Channel 2 5 AI 1 I Channel 1 6 AI 1 I Ground Channel 1 7 AI 3 I Channel 3 8 AI 3 I Ground Channel 3 I Input Pin assignment VIPA System SLIO Analog Input 031 1BD80 AI 4x16Bit R RTD HB300 SM AIO en 17 05 137 ...

Page 138: ...hat the corresponding channel is always deactivated in the parametrization The corresponding channel of channel 0 is channel 2 and of channel 1 is channel 3 Not used channels must always be de activated in the parametrization At CPU PROFIBUS and PROFINET the input respectively output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on numbe...

Page 139: ... Operational limit of current ranges with SFU Basic error limit current ranges Radical error limit current ranges with SFU Destruction limit current inputs voltage Destruction limit current inputs electrical current Resistance inputs ü Resistance ranges 0 60 Ohm 0 600 Ohm 0 3000 Ohm Operational limit of resistor ranges 0 4 Operational limit of resistor ranges with SFU 0 2 Basic error limit 0 2 Bas...

Page 140: ...ure error internal compensation Technical unit of temperature measurement C F K Resolution in bit 16 Measurement principle Sigma Delta Basic conversion time 4 2 324 1 ms 50 Hz 3 8 270 5 ms 60 Hz per channel Noise suppression for frequency 80dB at 50Hz UCM 6V Status information alarms diagnostics Status display yes Interrupts yes parameterizable Process alarm yes parameterizable Diagnostic interrup...

Page 141: ...ce between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 8 Output bytes 0 Parameter bytes 34 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes K...

Page 142: ...H0LL 2 Lower limit value channel 0 8000h 80h 310Ah 310Bh 0Ah CH1FN 1 Function number channel 1 50h 81h 310Ch 0Bh CH1FO 1 Function option channel 1 00h 81h 310Dh 0Ch CH1UL 2 Upper limit value channel 1 7FFFh 81h 310Eh 310Fh 0Dh CH1LL 2 Lower limit value channel 1 8000h 81h 3110h 3111h 0Eh CH2FN 1 Function number channel 2 50h2 82h 3112h 0Fh CH2FO 1 Function option channel 2 00h 82h 3113h 10h CH2UL ...

Page 143: ...Bit 0 1 Temperature system 00 C 01 F 10 K n Bit 7 2 reserved Byte Bit 7 0 0 n Bit 0 1 Interference frequency suppression 01 60Hz 10 50Hz n Bit 7 2 reserved In the following there are the measuring ranges with corresponding function number listed which were supported by the analog module With FFh the corresponding channel is deactivated Measuring range funct no Measuring value Signal range Range 2 ...

Page 144: ...underrange 3 wire NI100 5Ah 295 C 2950 overrange 60 250 C 600 2500 nominal range 105 C 1050 underrange 3 wire NI1000 5Bh 295 C 2950 overrange 60 250 C 600 2500 nominal range 105 C 1050 underrange 4 wire PT100 60h 1000 C 10000 overrange 200 850 C 2000 8500 nominal range 243 C 2430 underrange 4 wire PT1000 61h 1000 C 10000 overrange 200 850 C 2000 8500 nominal range 243 C 2430 underrange 4 wire NI10...

Page 145: ...ge 0 3000W 0 32767 nominal range underrange 4 wire 0 60W 80h overrange 0 60W 0 32767 nominal range underrange 4 wire 0 600W 81h overrange 0 600W 0 32767 nominal range underrange 4 wire 0 3000W 82h overrange 0 3000W 0 32767 nominal range underrange 2 wire 0 60W 90h overrange 0 60W 0 6000 nominal range underrange 2 wire 0 600W 91h overrange 0 600W 0 6000 nominal range underrange 2 wire 0 3000W 92h o...

Page 146: ...30000 nominal range underrange 2 wire 0 60W D0h 70 55W 32511 overrange 0 60W 0 27648 nominal range underrange 2 wire 0 600W D1h 705 5W 32511 overrange 0 600W 0 27648 nominal range underrange 2 wire 0 3000W D2h 3528W 32511 overrange 0 3000W 0 27648 nominal range underrange 3 wire 0 60W D8h 70 55W 32511 overrange 0 60W 0 27648 nominal range underrange 3 wire 0 600W D9h 705 5W 32511 overrange 0 600W ...

Page 147: ...7 2 04h 24 2 20 5 05h 14 2 12 2 06h 9 2 8 0 07h 6 6 5 9 08h 4 2 3 8 For Code 00h 01h and 02h the tolerances of the technical data with interference frequency suppression are valid For each channel an upper and a lower limit may be defined Here only values of the nominal range may be preset otherwise you receive a parameterization error By preset ting 7FFFh for the upper respectively 8000h for the ...

Page 148: ...CANopen the process interrupt data a transferred via an emergency telegram Operating with CPU PROFIBUS and PROFINET the process interrupt data were trans ferred via diagnostics telegram SX Subindex for access via EtherCAT with Index 5000h More can be found in the according manual of your bus coupler Name Bytes Function Default SX PRIT_OL 1 Limit overflow channel x 00h 02h PRIT_UL 1 Limit underflow...

Page 149: ...n DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by DS 00h IX Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h More can be found in the according manual of your bus coupler Name Bytes Function ...

Page 150: ...t 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer overflow n Bit 4 set at internal communication error n Bit 5 reserved n Bit 6 set at process interrupt lost n Bit 7 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input output 76h Counter n Bit 7 reserved Byte Bit 7 0 0 Numbe...

Page 151: ...at wire break n Bit 5 set at process interrupt lost n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMCH Channels CHERR Chan...

Page 152: ...5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble ...

Page 153: ...epends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h 4 AI 2 2 Analog value channel 2 6401h s 2 03h 6 AI 3 2 Analog value channel 3 6401h s 3 04h 8 AI 4 2 Analo...

Page 154: ...nput resistance voltage range Input voltage ranges Operational limit of voltage ranges Operational limit of voltage ranges with SFU Basic error limit voltage ranges Basic error limit voltage ranges with SFU Destruction limit voltage Current inputs ü Max input resistance current range 60 Ω Input current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 5 Operational limit of curren...

Page 155: ...ational limit of thermocouple ranges Operational limit of thermocouple ranges with SFU Basic error limit thermoelement ranges Basic error limit thermoelement ranges with SFU Destruction limit thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement ...

Page 156: ...ence between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 16 Output bytes 0 Parameter bytes 14 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g ...

Page 157: ... Interference frequency suppression channel 0 n Bit 2 3 Interference frequency suppression channel 1 n Bit 4 5 Interference frequency suppression channel 2 n Bit 6 7 Interference frequency suppression channel 3 n Bit 8 9 Interference frequency suppression channel 4 n Bit 10 11 Interference frequency suppression channel 5 n Bit 12 13 Interference frequency suppression channel 6 n Bit 14 15 Interfer...

Page 158: ...module does not support diagnostic interrupt functions the diagnostics data serve for information about this module On error the corresponding channel LED of the module is activated and the error is registered in the diagnostics data The following errors are listed in the diagnostics data n Error in project engineering parameterization n Measuring range overflow n Measuring range underflow DS Reco...

Page 159: ...el specific error channel 5 00h 0Fh CH6ERR 1 Channel specific error channel 6 00h 10h CH7ERR 1 Channel specific error channel 7 00h 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set at external auxiliary supply missing n Bit 6 5 reserved n Bit 7 set at error in parameteri...

Page 160: ... set at error in channel 6 n Bit 7 set at error in channel 7 Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 5 1 reserved n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With Powe...

Page 161: ...ication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 ...

Page 162: ...x depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h 4 AI 2 2 Analog value channel 2 6401h s 2 03h 6 AI 3 2 Analog value channel 3 6401h s 3 04h 8 AI 4 2 An...

Page 163: ... inputs ü Min input resistance voltage range 100 kΩ Input voltage ranges 0 V 10 V 10 V 10 V Operational limit of voltage ranges Operational limit of voltage ranges with SFU Basic error limit voltage ranges Basic error limit voltage ranges with SFU Destruction limit voltage max 30V Current inputs Max input resistance current range Input current ranges Operational limit of current ranges Operational...

Page 164: ...perational limit of thermocouple ranges Operational limit of thermocouple ranges with SFU Basic error limit thermoelement ranges Basic error limit thermoelement ranges with SFU Destruction limit thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measureme...

Page 165: ...erence between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 16 Output bytes 0 Parameter bytes 14 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 ...

Page 166: ...0 1 Interference frequency suppression channel 0 n Bit 2 3 Interference frequency suppression channel 1 n Bit 4 5 Interference frequency suppression channel 2 n Bit 6 7 Interference frequency suppression channel 3 n Bit 8 9 Interference frequency suppression channel 4 n Bit 10 11 Interference frequency suppression channel 5 n Bit 12 13 Interference frequency suppression channel 6 n Bit 14 15 Inter...

Page 167: ...mulas 0 10V Siemens S7 format 10h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h 1 76V 4864 ED00h underrange 0 10V Siemens S5 format 20h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V 8192 2000h 0V 0 0000h 2V 3277 F333h underrange 3 15 3 Diagnostic data So this module does not support diagnostic interrupt functions the diagnostics data serve for ...

Page 168: ...71h 06h NUMBIT 1 Number diagnostic bits per channel 08h 07h NUMCH 1 Number of channels of a module 08h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR 1 Channel specific error channel 2 00h 0Ch CH3ERR 1 Channel specific error channel 3 00h 0Dh CH4ERR 1 Channel specific error channel 4 00h 0Eh CH5ERR 1 Chan...

Page 169: ...r of diagnostic bits per channel here 08h Byte Bit 7 0 0 Number of channels of a module here 08h Byte Bit 7 0 0 n Bit 0 set at error in channel 0 n Bit 1 set at error in channel 1 n Bit 2 set at error in channel 2 n Bit 3 set at error in channel 3 n Bit 4 set at error in channel 4 n Bit 5 set at error in channel 5 n Bit 6 set at error in channel 6 n Bit 7 set at error in channel 7 MODTYP Module in...

Page 170: ...ring range overflow Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again CH0ERR CH7ERR Channel specific DIAG_US µs ticker VIPA System SLIO Analog Input 031 1BF74 AI 8x12Bit 10V Diagnostic data HB300 SM AIO en 17 05 170 ...

Page 171: ...rammable power supply for the load cell s full bridge s n Parallel operation of load cells possible n Diagnostic function n 16bit resolution 24bit internal 1 Locking lever terminal module 2 Labeling strip 3 Backplane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF Description green red Bus communica...

Page 172: ...X X On at activated Input Freeze X X X X X On at short circuit respectively over load of the excitation voltage X X X X X On at overrange of the excitation voltage X X X X X On at overrange of the differential voltage on off blinking 2Hz B not relevant X VIPA System SLIO Analog Input 031 1CA20 AI 1x16 24 Bit Strain gauge DMS HB300 SM AIO en 17 05 172 ...

Page 173: ...SEN 6 SEN I Sensor of the excitation voltage USEN 7 EXC O Signal of the excitation voltage UEXC 8 Shield Connection for cable shield O Output I Input Please always use the excitation voltage UEXC of the module The con nection of sensors with external power supply is not possible 3 16 1 Connection variants The following table shows the properties of the sensors which can be used with the 6 wire mea...

Page 174: ...el connected via a connection box to the strain gauge DMS module Please consider that the load cells are aligned together for this operating mode and approved by the manufacturer And the current feed capacity of the transducer electronic should not be overloaded The current feed capacity is derived from the number of parallel con nected load cells excitation voltage UEXC and the bridge resistance ...

Page 175: ...V not possible X X X 12V not possible not possible X X To connect your sensors please always use shielded cables Please always use the excitation voltage UEXC of the module The con nection of sensors with external power supply is not possible 3 16 2 In Output area At CPU PROFIBUS and PROFINET the input respectively output area is embedded to the corresponding address area IX Index for access via C...

Page 176: ... the module n Input Freeze In the activated state no measurement values are passed to the digital filter As long as the command bit is set this bit remains set n Steady State As soon as a measured value is longer than the time SSW within the tolerance window SST in the status word the Steady State bit is set As soon as this condition is not true the last measured value is first used the comparison...

Page 177: ... Bit 7 Set reference point à DMS_STAT bit 7 active n Input Freeze In the activated state no measurement values are passed to the digital filter By a brief activation of Input Freeze pulses e g caused by a filling procedure can be prevented which would override the filter unnecessarily The status of Input Freeze can be determined at any time via bit 0 of DMS_STAT n Adjustment Store adjustment Used ...

Page 178: ...tion limit current max 12V External bridge supply possible Internal bridge supply possible ü Configurable bridge supply 2 5V max 120mA 5V max 120mA 7 5V max 100mA 10V max 90mA 12V max 80mA Resolution in bit 24 Measurement principle successive approximation Basic conversion time 1ms cycle 10ms 330ms depending on the filter Input filter hardware Low pass 10kHz 3rd order Input filter software dynamic...

Page 179: ...een channels and power supply Max potential difference between circuits Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input by...

Page 180: ...creases proportionally n optical strain gauge DMS An optical strain gauge DMS consists of a fibre used as a sensor with a laser applied grid in the fibre During the measurement the behavior is used that with mechanical load the optical properties of the sensor are changed Light is passed with a certain wavelength into the sensor Depending on the deformation of the laser applied grid of the sensor ...

Page 181: ...ion voltage RO Rated output YA Absolute value YR Relative value NL Nominal load SF Scale factor Y Resulting weight value YA Absolute value GN Gain TA Tara 3 16 5 Parameter data DS Record set for access via CPU PROFIBUS and PROFINET IX Index for access via CANopen SX Subindex for access via EtherCAT with Index 3100h EtherCAT Slot More can be found in the according manual of your bus coupler Due to ...

Page 182: ...re you can specify the power supply for the excitation voltage UEXC which the module provides via the pins EXC und EXC Please always use the excitation voltage U of the moduleEXC The con nection of strain gauge DMS sensors with external power supply is not possible Byte Bit 7 0 0 1 n Interval for the calibration Calibration interval as 100ms value 00h de activates the calibration n By setting a ca...

Page 183: ...ns frequency interference n Dynamic IIR filter automatic selection Filter selection dependent on the current weight change n Static IIR filter De activation respectively fix setting of a filter level IIR1 IIR8 Byte Bit 7 0 0 1 Sampling rate for filter change over in ms n Here you can specify the time for re evaluation for the filter change over in ms Byte Bit 7 0 0 1 Limit value for filter change ...

Page 184: ...load of the force transducer unit free Information to nominal load can be found in the data sheet of you force transducer Byte Bit 7 0 0 1 Scale factor for the nominal load n Here you can specify the scale factor for the nominal load such as to convert kg to g Example Nominal load in kg and scale factor 1000 03E8h results display in g Byte Bit 7 0 0 1 Tolerance for Steady State n Here you can spec...

Page 185: ...n the FILT parameter dependent on the current weight change it is automatically switched between 8 different filters The aim here is to obtain a filter with the best possible damping which must lead to stable measuring values The Dynamic IIR filter acts as 1 order low pass filter and has the following properties If there is a rapid change of the input value it is switched over to the next lower fi...

Page 186: ...table value is shown bit 7 set reference point in the command byte DMS_CMD is to set 5 Set bit 1 store adjustment in the command byte DMS_CMD ð As soon as the adjustment data were stored successfully the module measures with these parameters The adjustment data remain even after a power loss condition and can be deleted delete adjustment via bit 2 The adjustment data can be rewritten only every 12...

Page 187: ...omatically takes place All events of a channel between diagnostic interruptincoming and diagnostic interruptgoing are not stored and get lost Within this time window 1 diagnostic interruptincoming until last diagnostic interruptgoing the MF LED of the module is on The following events can cause a diagnostic interrupt n External auxiliary supply is missing n Internal diagnostic puffer overflow n In...

Page 188: ... reserved n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set at external auxiliary supply missing n Bit 6 5 reserved n Bit 7 set at error in parameterization Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer o...

Page 189: ...n error n Bit 2 1 reserved n Bit 3 set at short circuit of excitation voltage UEXC n Bit 5 4 reserved n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow 1 7 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts...

Page 190: ...ane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in conf...

Page 191: ...ditional shield bus carrier is not necessary I Input At CPU PROFIBUS and PROFINET the input respectively output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes...

Page 192: ...ltage ranges with SFU Basic error limit voltage ranges 0 1 Basic error limit voltage ranges with SFU Destruction limit voltage max 30V Current inputs Max input resistance current range Input current ranges Operational limit of current ranges Operational limit of current ranges with SFU Basic error limit current ranges Radical error limit current ranges with SFU Destruction limit current inputs vol...

Page 193: ...thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 16 Measurement principle successive approximation Basic conversion time 240 µs all channels Noise suppression for frequency 80dB at 50Hz UCM 9V Status information alarms diag...

Page 194: ... inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 4 Output bytes 0 Parameter bytes 20 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage...

Page 195: ...nel 0 7FFFh 80h 3106h 3107h 07h CH0LL 2 Lower limit value channel 0 8000h 80h 3108h 3109h 08h CH1FN 1 Function number channel 1 10h 81h 310Ah 09h RES13 1 reserved 00h 81h 310Bh 0Ah CH1UL 2 Upper limit value channel 1 7FFFh 81h 310Ch 310Dh 0Bh CH1LL 2 Lower limit value channel 1 8000h 81h 310Eh 310Fh 0Ch This record set may only be transferred at STOP state Byte Bit 7 0 0 n Diagnostic interrupt 00h...

Page 196: ...ns S5 format 20h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V 8192 2000h 0V 0 0000h 2V 3277 F333h underrange For each channel an upper and a lower limit may be defined Here only values of the nominal range may be preset otherwise you receive a parameterization error By preset ting 7FFFh for the upper respectively 8000h for the lower limit value the corresponding limit is deactivate...

Page 197: ...rCAT with Index 5000h More can be found in the according manual of your bus coupler Name Bytes Function Default SX PRIT_OL 1 Limit overflow channel x 00h 02h PRIT_UL 1 Limit underflow channel x 00h 03h PRIT_US 2 µs ticker 00h 04h 05h Byte Bit 7 0 0 n Bit 0 Limit overflow channel 0 n Bit 1 Limit overflow channel 1 n Bit 7 2 reserved Byte Bit 7 0 0 n Bit 0 Limit underflow channel 0 n Bit 1 Limit und...

Page 198: ...set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by DS 00h IX Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h More can be found in the according manual of your bus coupler Name Bytes Function Default DS I...

Page 199: ...ffer overflow n Bit 4 set at internal communication error n Bit 5 reserved n Bit 6 set at process interrupt lost n Bit 7 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input output 76h Counter n Bit 7 reserved Byte Bit 7 0 0 Number of diagnostic bits per channel here 08h Byte Bit 7 0 0 Number of channels of a module...

Page 200: ... Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again CHERR Channel error CH0ERR CH1ERR Channel specific DIAG_US µs ticker VIPA System SLIO Analog Input 031...

Page 201: ...strip 3 Backplane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X...

Page 202: ...cable shield an additional shield bus carrier is not neces sary I Input If a 2wire measuring transducer is used you have to connect in line an external power supply At CPU PROFIBUS and PROFINET the input respectively output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via Ether...

Page 203: ...esistance voltage range Input voltage ranges Operational limit of voltage ranges Operational limit of voltage ranges with SFU Basic error limit voltage ranges Basic error limit voltage ranges with SFU Destruction limit voltage Current inputs ü Max input resistance current range 60 Ω Input current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 2 Operational limit of current rang...

Page 204: ...ocouple ranges Operational limit of thermocouple ranges with SFU Basic error limit thermoelement ranges Basic error limit thermoelement ranges with SFU Destruction limit thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 16 M...

Page 205: ...ntial difference between inputs and Mana Ucm DC 3 V Max potential difference between inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 4 Output bytes 0 Parameter bytes 20 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76...

Page 206: ...nel 0 7FFFh 80h 3106h 3107h 07h CH0LL 2 Lower limit value channel 0 8000h 80h 3108h 3109h 08h CH1FN 1 Function number channel 1 31h 81h 310Ah 09h RES13 1 reserved 00h 81h 310Bh 0Ah CH1UL 2 Upper limit value channel 1 7FFFh 81h 310Ch 310Dh 0Bh CH1LL 2 Lower limit value channel 1 8000h 81h 310Eh 310Fh 0Ch This record set may only be transferred at STOP state Byte Bit 7 0 0 n Diagnostic interrupt 00h...

Page 207: ... Hex Range Formulas 0 20mA Siemens S7 format 31h 23 52mA 32511 7EFFh overrange 20mA 27648 6C00h nominal range 10mA 13824 3600h 0mA 0 0000h 3 52mA 4864 ED00h underrange 0 20mA Siemens S5 format 41h 25 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 10mA 8192 2000h 0mA 0 0000h 4 00mA 3277 F333h underrange 4 20mA Siemens S7 format 30h 22 81mA 32511 7EFFh overrange 20mA 27648 6C00h nominal r...

Page 208: ... activate a process interrupt A process interrupt interrupts the linear program sequence and jumps depending on the master system to a corresponding Interrupt routine Here you can react to the process interrupt accordingly With CANopen the process interrupt data a transferred via an emergency telegram Operating with CPU PROFIBUS and PROFINET the process interrupt data were trans ferred via diagnos...

Page 209: ...st diagnostic interruptgoing the MF LED of the module is on The following errors are listed in the diagnostics data n Error in project engineering parameterization n Measuring range overflow n Measuring range underflow n Process interrupt lost n Power supply failed DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by ...

Page 210: ... Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer overflow n Bit 4 set at internal communication error n Bit 5 reserved n Bit 6 set at process interrupt lost n Bit 7 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h ...

Page 211: ...nterrupt lost n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMBIT Diagnostic bits NUMCH Channels CHERR Channel error CH0ER...

Page 212: ...plane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in co...

Page 213: ...dditional shield bus carrier is not neces sary I Input At CPU PROFIBUS and PROFINET the input respectively output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Byt...

Page 214: ...rational limit of voltage ranges with SFU Basic error limit voltage ranges 0 1 Basic error limit voltage ranges with SFU Destruction limit voltage max 30V Current inputs Max input resistance current range Input current ranges Operational limit of current ranges Operational limit of current ranges with SFU Basic error limit current ranges Radical error limit current ranges with SFU Destruction limi...

Page 215: ... Destruction limit thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 16 Measurement principle successive approximation Basic conversion time 240 µs all channels Noise suppression for frequency 80dB at 50Hz UCM 9V Status info...

Page 216: ...etween inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 4 Output bytes 0 Parameter bytes 20 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C S...

Page 217: ...hannel 0 7FFFh 80h 3106h 3107h 07h CH0LL 2 Lower limit value channel 0 8000h 80h 3108h 3109h 08h CH1FN 1 Function number channel 1 12h 81h 310Ah 09h RES13 1 reserved 00h 81h 310Bh 0Ah CH1UL 2 Upper limit value channel 1 7FFFh 81h 310Ch 310Dh 0Bh CH1LL 2 Lower limit value channel 1 8000h 81h 310Eh 310Fh 0Ch This record set may only be transferred at STOP state Byte Bit 7 0 0 n Diagnostic interrupt ...

Page 218: ...gital value to a value assigned to the measuring range analog value and vice versa Meas range funct no Voltage U Decimal D Hex Range Formulas 10V Siemens S7 format 12h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h 5V 13824 CA00h 10V 27648 9400h 11 76V 32512 8100h underrange 10V Siemens S5 format 22h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V...

Page 219: ... and interrupt Event Process interrupt Diagnostics interrupt parameterizable Error in project engineering parameterization X Measuring range overflow X Measuring range underflow X Limit overflow X X Limit underflow X X Diagnostic buffer overflow X Communication error X Process interrupt lost X So you may react to asynchronous events there is the possibility to activate a process interrupt A proces...

Page 220: ...6 1 Via the parameterization you may activate a diagnostic interrupt for the module With a diagnostics interrupt the module serves for diagnostics data for diagnostic interruptincoming As soon as the reason for releasing a diagnostic interrupt is no longer present the diag nostic interruptgoing automatically takes place All events of a channel between diagnostic interruptincoming and diagnostic in...

Page 221: ...agnostic bits per channel 08h 07h NUMCH 1 Number of channels of a module 02h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR CH7ERR 6 reserved 00h 0Ch 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at chan...

Page 222: ...nels of a module here 02h Byte Bit 7 0 0 n Bit 0 set at error in channel group 0 n Bit 1 set at error in channel group 1 n Bit 7 2 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 4 1 reserved n Bit 5 set at process interrupt lost n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reser...

Page 223: ...c µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again DIAG_US µs ticker VIPA System SLIO Analog Input 031 1CB70 AI 2x16Bit 10V Diagnostics and interrupt HB300 SM AIO en 17 05 223 ...

Page 224: ...terminal module 2 Labeling strip 3 Backplane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Erro...

Page 225: ...address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h 4 AI 2 2 Analog value channel 2 6401h s 2 03...

Page 226: ...ltage ranges with SFU Basic error limit voltage ranges 0 1 Basic error limit voltage ranges with SFU Destruction limit voltage max 30V Current inputs Max input resistance current range Input current ranges Operational limit of current ranges Operational limit of current ranges with SFU Basic error limit current ranges Radical error limit current ranges with SFU Destruction limit current inputs vol...

Page 227: ...thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 16 Measurement principle successive approximation Basic conversion time 480 µs all channels Noise suppression for frequency 80dB at 50Hz UCM 9V Status information alarms diag...

Page 228: ...puts and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 8 Output bytes 0 Parameter bytes 32 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage te...

Page 229: ...t value channel 0 8000h 80h 3108h 3109h 08h CH1FN 1 Function number channel 1 10h 81h 310Ah 09h RES13 1 reserved 00h 81h 310Bh 0Ah CH1UL 2 Upper limit value channel 1 7FFFh 81h 310Ch 310Dh 0Bh CH1LL 2 Lower limit value channel 1 8000h 81h 310Eh 310Fh 0Ch CH2FN 1 Function number channel 2 10h 82h 3110h 0Dh RES19 1 reserved 00h 82h 3111h 0Eh CH2UL 2 Upper limit value channel 2 7FFFh 82h 3112h 3113h ...

Page 230: ...re the measuring ranges with corresponding function number listed which were supported by the analog module With FFh the corresponding channel is deactivated The formulas listed here allow you to transform an evaluated measuring value digital value to a value assigned to the measuring range analog value and vice versa Meas range funct no Voltage U Decimal D Hex Range Formulas 0 10V Siemens S7 form...

Page 231: ... process interrupt interrupts the linear program sequence and jumps depending on the master system to a corresponding Interrupt routine Here you can react to the process interrupt accordingly With CANopen the process interrupt data a transferred via an emergency telegram Operating with CPU PROFIBUS and PROFINET the process interrupt data were trans ferred via diagnostics telegram SX Subindex for a...

Page 232: ...his time window 1 diagnostic interruptincoming until last diagnostic interruptgoing the MF LED of the module is on The following errors are listed in the diagnostics data n Error in project engineering parameterization n Measuring range overflow n Measuring range underflow n Process interrupt lost n Power supply failed DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS...

Page 233: ... supply missing n Bit 6 5 reserved n Bit 7 set at error in parameterization Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer overflow n Bit 4 set at internal communication error n Bit 5 reserved n Bit 6 set at process interrupt lost n Bit 7 reserved By...

Page 234: ...Bit 4 1 reserved n Bit 5 set at process interrupt lost n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMBIT Diagnostic bits...

Page 235: ...al module 2 Labeling strip 3 Backplane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at b...

Page 236: ...ss via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h 4 AI 2 2 Analog value channel 2 6401h s 2 03h 6 AI 3 2 Analog value channe...

Page 237: ...ges 0 1 Basic error limit voltage ranges with SFU Destruction limit voltage max 30V Current inputs Max input resistance current range Input current ranges Operational limit of current ranges Operational limit of current ranges with SFU Basic error limit current ranges Radical error limit current ranges with SFU Destruction limit current inputs voltage Destruction limit current inputs electrical cu...

Page 238: ...e temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 16 Measurement principle successive approximation Basic conversion time 480 µs all channels Noise suppression for frequency 80dB at 50Hz UCM 9V Status information alarms diagnostics Status display yes Inte...

Page 239: ...utput bytes 0 Parameter bytes 9 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification in preparation KC certification yes 3 21 2 Parameter data DS Record set for access via CPU PRO...

Page 240: ...responding channel is deactivated The formulas listed here allow you to transform an evaluated measuring value digital value to a value assigned to the measuring range analog value and vice versa Meas range funct no Voltage U Decimal D Hex Range Formulas 0 10V Siemens S7 format 10h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h 1 76V 4864 ED00h underrange 0 10...

Page 241: ...formation 15h 03h ERR_C 1 reserved 00h 04h ERR_D 1 Diagnostic 00h 05h CHTYP 1 Channel type 71h 06h NUMBIT 1 Number diagnostic bits per channel 08h 07h NUMCH 1 Number of channels of a module 04h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR 1 Channel specific error channel 2 00h 0Ch CH3ERR 1 Channel speci...

Page 242: ...n channel group 0 n Bit 1 set at error in channel group 1 n Bit 2 set at error in channel group 2 n Bit 3 set at error in channel group 3 n Bit 7 4 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 5 1 reserved n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved MODTYP Module inf...

Page 243: ...ostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again DIAG_US µs ticker VIPA System SLIO Analog Input 031 1CD35 AI 4x16Bit 0 10V Diagnostic data HB300 SM AIO en 17 05 243 ...

Page 244: ...1 Locking lever terminal module 2 Labeling strip 3 Backplane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports...

Page 245: ...output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h...

Page 246: ...U Basic error limit voltage ranges Basic error limit voltage ranges with SFU Destruction limit voltage Current inputs ü Max input resistance current range 60 Ω Input current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 2 Operational limit of current ranges with SFU Basic error limit current ranges 0 1 Radical error limit current ranges with SFU Destruction limit current input...

Page 247: ...FU Destruction limit thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 16 Measurement principle successive approximation Basic conversion time 240 µs all channels Noise suppression for frequency 80dB UCM 4V Status informatio...

Page 248: ... inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 8 Output bytes 0 Parameter bytes 32 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage...

Page 249: ...N 1 Function number channel 1 31h 81h 310Ah 09h RES13 1 reserved 00h 81h 310Bh 0Ah CH1UL 2 Upper limit value channel 1 7FFFh 81h 310Ch 310Dh 0Bh CH1LL 2 Lower limit value channel 1 8000h 81h 310Eh 310Fh 0Ch CH2FN 1 Function number channel 2 31h 82h 3110h 0Dh RES19 1 reserved 00h 82h 3111h 0Eh CH2UL 2 Upper limit value channel 2 7FFFh 82h 3112h 3113h 0Fh CH2LL 2 Lower limit value channel 2 8000h 82...

Page 250: ...Interference frequency suppression channel 3 00 deactivated 01 60Hz 10 50Hz e g 10101010 all channels frequency suppression 50Hz In the following there are the measuring ranges with corresponding function number listed which were supported by the analog module With FFh the corresponding channel is deactivated The formulas listed here allow you to transform an evaluated measuring value digital valu...

Page 251: ... 3277 F333h underrange For each channel an upper and a lower limit may be defined Here only values of the nominal range may be preset otherwise you receive a parameterization error By preset ting 7FFFh for the upper respectively 8000h for the lower limit value the corresponding limit is deactivated As soon as the measuring value is beyond the limits and the limit value monitoring is activated a pr...

Page 252: ...cess via EtherCAT with Index 5000h More can be found in the according manual of your bus coupler Name Bytes Function Default SX PRIT_OL 1 Limit overflow channel x 00h 02h PRIT_UL 1 Limit underflow channel x 00h 03h PRIT_US 2 µs ticker 00h 04h 05h Byte Bit 7 0 0 n Bit 0 Limit overflow channel 0 n Bit 1 Limit overflow channel 1 n Bit 2 Limit overflow channel 2 n Bit 3 Limit overflow channel 3 n Bit ...

Page 253: ...ocess interrupt lost n Power supply failed DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by DS 00h IX Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h More can be found in the according manual...

Page 254: ...fer overflow n Bit 4 set at internal communication error n Bit 5 reserved n Bit 6 set at process interrupt lost n Bit 7 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input output 76h Counter n Bit 7 reserved Byte Bit 7 0 0 Number of diagnostic bits per channel here 08h Byte Bit 7 0 0 Number of channels of a module ...

Page 255: ...nterrupt lost n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again CHERR Channel error CH0ERR CH3ERR Channel specific CH4ERR CH7ER...

Page 256: ...ing lever terminal module 2 Labeling strip 3 Backplane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an er...

Page 257: ... PROFIBUS and PROFINET the input respectively output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h...

Page 258: ...nput resistance voltage range Input voltage ranges Operational limit of voltage ranges Operational limit of voltage ranges with SFU Basic error limit voltage ranges Basic error limit voltage ranges with SFU Destruction limit voltage Current inputs ü Max input resistance current range 60 Ω Input current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 2 Operational limit of curren...

Page 259: ...perational limit of thermocouple ranges Operational limit of thermocouple ranges with SFU Basic error limit thermoelement ranges Basic error limit thermoelement ranges with SFU Destruction limit thermocouple inputs Programmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measureme...

Page 260: ...tial difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 8 Output bytes 0 Parameter bytes 9 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Wei...

Page 261: ...y suppression channel 0 n Bit 3 2 Interference frequency suppression channel 1 n Bit 5 4 Interference frequency suppression channel 2 n Bit 7 6 Interference frequency suppression channel 3 00 deactivated 01 60Hz 10 50Hz e g 10101010 all channels frequency suppression 50Hz In the following there are the measuring ranges with corresponding function number listed which were supported by the analog mo...

Page 262: ... not support diagnostic interrupt functions the diagnostics data serve for information about this module On error the corresponding channel LED of the module is activated and the error is registered in the diagnostics data The following errors are listed in the diagnostics data n Error in project engineering parameterization n Measuring range overflow n Measuring range underflow n Power supply fai...

Page 263: ... 7ERR 4 reserved 00h 0Eh 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set at external auxiliary supply missing n Bit 6 5 reserved n Bit 7 set at error in parameterization Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information present...

Page 264: ...7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 5 1 reserved n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232...

Page 265: ...plane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in co...

Page 266: ...ess via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 6000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AI 0 2 Analog value channel 0 6401h s 01h 2 AI 1 2 Analog value channel 1 6401h s 1 02h 4 AI 2 2 Analog value channel 2 6401h s 2 03h 6 AI 3 2 Analog value chann...

Page 267: ...ror limit voltage ranges 0 1 Basic error limit voltage ranges with SFU Destruction limit voltage max 30V Current inputs Max input resistance current range Input current ranges Operational limit of current ranges Operational limit of current ranges with SFU Basic error limit current ranges Radical error limit current ranges with SFU Destruction limit current inputs voltage Destruction limit current...

Page 268: ...mmable temperature compensation External temperature compensation Internal temperature compensation Temperature error internal compensation Technical unit of temperature measurement Resolution in bit 16 Measurement principle successive approximation Basic conversion time 480 µs all channels Noise suppression for frequency 80dB at 50Hz UCM 35V Status information alarms diagnostics Status display ye...

Page 269: ... Mintern Uiso DC 75 V AC 50 V Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 8 Output bytes 0 Parameter bytes 32 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage temperatur...

Page 270: ...H1FN 1 Function number channel 1 12h 81h 310Ah 09h RES13 1 reserved 00h 81h 310Bh 0Ah CH1UL 2 Upper limit value channel 1 7FFFh 81h 310Ch 310Dh 0Bh CH1LL 2 Lower limit value channel 1 8000h 81h 310Eh 310Fh 0Ch CH2FN 1 Function number channel 2 12h 82h 3110h 0Dh RES19 1 reserved 00h 82h 3111h 0Eh CH2UL 2 Upper limit value channel 2 7FFFh 82h 3112h 3113h 0Fh CH2LL 2 Lower limit value channel 2 8000h...

Page 271: ...ction number listed which were supported by the analog module With FFh the corresponding channel is deactivated The formulas listed here allow you to transform an evaluated measuring value digital value to a value assigned to the measuring range analog value and vice versa Meas range funct no Voltage U Decimal D Hex Range Formulas 10V Siemens S7 format 12h 11 76V 32511 7EFFh overrange 10V 27648 6C...

Page 272: ... and interrupt Event Process interrupt Diagnostics interrupt parameterizable Error in project engineering parameterization X Measuring range overflow X Measuring range underflow X Limit overflow X X Limit underflow X X Diagnostic buffer overflow X Communication error X Process interrupt lost X So you may react to asynchronous events there is the possibility to activate a process interrupt A proces...

Page 273: ...ain PRIT_US represents the lower 2 byte of the µs ticker value 0 216 1 Via the parameterization you may activate a diagnostic interrupt for the module With a diagnostics interrupt the module serves for diagnostics data for diagnostic interruptincoming As soon as the reason for releasing a diagnostic interrupt is no longer present the diag nostic interruptgoing automatically takes place All events ...

Page 274: ... channels of a module 04h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR 1 Channel specific error channel 2 00h 0Ch CH3ERR 1 Channel specific error channel 3 00h 0Dh CH4ERR CH 7ERR 4 reserved 00h 0Eh 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error...

Page 275: ... n Bit 0 set at error in channel group 0 n Bit 1 set at error in channel group 1 n Bit 2 set at error in channel group 2 n Bit 3 set at error in channel group 3 n Bit 7 4 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 4 1 reserved n Bit 5 set at process interrupt lost n Bit 6 set at measuring range underflow n Bit 7 set at measu...

Page 276: ...c µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again DIAG_US µs ticker VIPA System SLIO Analog Input 031 1CD70 AI 4x16Bit 10V Diagnostics and interrupt HB300 SM AIO en 17 05 276 ...

Page 277: ...s 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configurat...

Page 278: ... following points when assembling n Do not arrange the module directly apart from a power module with a high feeding current n Do not install the module at the end of a line n The module should be in a static condition i e the temperature should be as constant as possible in the environment of your module closed switchgear cabinet free from air draught n The accuracy is reached after approx 30 min...

Page 279: ...chnical data analog inputs Number of inputs 2 Cable length shielded 200 m Rated load voltage DC 24 V Current consumption from load voltage L without load 30 mA Voltage inputs Min input resistance voltage range 10 MΩ Input voltage ranges 80 mV 80 mV Operational limit of voltage ranges 0 3 Operational limit of voltage ranges with SFU 0 1 Basic error limit voltage ranges 0 25 Basic error limit voltag...

Page 280: ...it thermoresistor ranges with SFU Destruction limit resistance thermometer inputs Thermocouple inputs ü Thermocouple ranges type B type C type E type J type K type L type N type R type S type T Operational limit of thermocouple ranges Type E L T J K N 2 5K Type B C R S 8 0K Operational limit of thermocouple ranges with SFU Type E L T J K N 1 5K Type B C R S 4 0K Basic error limit thermoelement ran...

Page 281: ...nel error display red LED per channel Isolation Between channels Between channels of groups to Between channels and backplane bus ü Between channels and power supply Max potential difference between circuits Max potential difference between inputs Ucm DC 75 V AC 50 V Max potential difference between Mana and Mintern Uiso Max potential difference between inputs and Mana Ucm Max potential difference...

Page 282: ...Thermoelement type J 100 C 3 25 2 Parameter data DS Record set for access via CPU PROFIBUS and PROFINET IX Index for access via CANopen SX Subindex for access via EtherCAT with Index 3100h EtherCAT Slot More can be found in the according manual of your bus coupler Name Bytes Function Default DS IX SX DIAG_EN 1 Diagnostics 00h 00h 3100h 01h WIBRK_EN 1 Wire break recognition 00h 00h 3101h 02h TEMPCN...

Page 283: ...served Byte Bit 7 0 0 n Bit 0 1 Interference frequency suppression 01 60Hz 10 50Hz n Bit 7 2 reserved In the following there are the measuring ranges with corresponding function number listed which were supported by the analog module With FFh the corresponding channel is deactivated DIAG_EN Diagnostics WIBRK_EN Wire break recognition TEMPCNF Temperature system SUPR Interference fre quency suppress...

Page 284: ...g value in F 0 1 F digit Measuring value in K 0 1K digit Range Type J Fe Cu Ni IEC 210 1200 C 346 2192 F 63 2 1473 2K B0h ext comp 0 C C0h int comp 0 C 14500 26420 17232 overrange 2100 12000 3460 21920 632 14732 nominal range underrange Type K Ni Cr Ni 270 1372 C 454 2501 6 F 0 1645 2K B1h ext comp 0 C C1h int comp 0 C 16220 29516 18952 overrange 2700 13720 4540 25016 0 16452 nominal range underra...

Page 285: ...al range 1700 2740 1032 underrange Type T Cu Cu Ni 270 400 C 454 752 F 3 2 673 2K B5h ext comp 0 C C5h int comp 0 C 5400 10040 8132 overrange 2700 4000 4540 7520 32 6732 nominal range underrange Type B PtRh PtRh 0 1820 C 32 2786 5 F 273 2 2093 2K B6h ext comp 0 C C6h int comp 0 C 20700 32766 23432 overrange 0 18200 320 27865 2732 20932 nominal range 1200 1840 1532 underrange Type C WRe5 WRe26 0 23...

Page 286: ...stics data The following errors are listed in the diagnostics data n Error in project engineering parameterization n Measuring range overflow n Measuring range underflow DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by DS 00h IX Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 b...

Page 287: ...Bit 6 5 reserved n Bit 7 set at error in parameterization Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer overflow n Bit 4 set at internal communication error n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input ...

Page 288: ...re break n Bit 5 reserved n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMBIT Diagnostic bits NUMCH Channels CHERR Channel...

Page 289: ...ane bus 4 LED status indication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AI x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in conf...

Page 290: ... is channel 3 Not used channels must always be de activated in the parametrization n 4 wire measurement is only possible via the channels 0 and 1 The measurement current for channel 0 is applied at pin 1 and 2 The measure ment for channel 0 happens at pin 3 and 4 The analog value for channel 0 is rep resented in input word 0 The measurement current for channel 1 is applied at pin 5 and 6 The measu...

Page 291: ...d by the module 3 26 1 Technical data Order no 031 1LD80 Type SM 031 Module ID 0410 1544 Current consumption power loss Current consumption from backplane bus 55 mA Power loss 1 W Technical data analog inputs Number of inputs 4 Cable length shielded 200 m Rated load voltage DC 24 V Current consumption from load voltage L without load 30 mA Voltage inputs Min input resistance voltage range Input vo...

Page 292: ...istance thermometer ranges Pt100 Pt1000 Ni100 Ni1000 Operational limit of resistance thermometer ranges 0 4 Operational limit of resistance thermometer ranges with SFU 0 2 Basic error limit thermoresistor ranges 0 2 Basic error limit thermoresistor ranges with SFU 0 1 Destruction limit resistance thermometer inputs max 24V Thermocouple inputs Thermocouple ranges Operational limit of thermocouple r...

Page 293: ...LED Channel error display red LED per channel Isolation Between channels Between channels of groups to Between channels and backplane bus ü Between channels and power supply Max potential difference between circuits Max potential difference between inputs Ucm DC 6 V Max potential difference between Mana and Mintern Uiso Max potential difference between inputs and Mana Ucm Max potential difference ...

Page 294: ... 9 mm x 109 mm x 76 5 mm Weight 60 g Environmental conditions Operating temperature 0 C to 60 C Storage temperature 25 C to 70 C Certifications UL certification yes KC certification yes VIPA System SLIO Analog Input 031 1LD80 AI 4x16Bit R RTD Technical data HB300 SM AIO en 17 05 294 ...

Page 295: ...ion number channel 2 50h2 82h 3106h 07h CH3FN 1 Function number channel 3 50h2 83h 3107h 08h 1 This record set may only be transferred at STOP state 2 with 2 channel operation FFh Byte Bit 7 0 0 n Diagnostic interrupt 00h disabled 40h enabled n Here you can enable respectively disable the diagnostic interrupt Byte Bit 7 0 0 n Bit 0 Wire break recognition channel 0 1 on n Bit 1 Wire break recogniti...

Page 296: ...0 2500 nominal range 105 C 1050 underrange 2 wire NI1000 53h 295 C 2950 overrange 60 250 C 600 2500 nominal range 105 C 1050 underrange 3 wire PT100 58h 1000 C 10000 overrange 200 850 C 2000 8500 nominal range 243 C 2430 underrange 3 wire PT1000 59h 1000 C 10000 overrange 200 850 C 2000 8500 nominal range 243 C 2430 underrange 3 wire NI100 5Ah 295 C 2950 overrange 60 250 C 600 2500 nominal range 1...

Page 297: ...0W 71h overrange 0 600W 0 32767 nominal range underrange 2 wire 0 3000W 72h overrange 0 3000W 0 32767 nominal range underrange 3 wire 0 60W 78h overrange 0 60W 0 32767 nominal range underrange 3 wire 0 600W 79h overrange 0 600W 0 32767 nominal range underrange 3 wire 0 3000W 7Ah overrange 0 3000W 0 32767 nominal range underrange 4 wire 0 60W 80h overrange 0 60W 0 32767 nominal range underrange 4 w...

Page 298: ...al range underrange 3 wire 0 3000W 9Ah overrange 0 3000W 0 30000 nominal range underrange 4 wire 0 60W A0h overrange 0 60W 0 6000 nominal range underrange 4 wire 0 600W A1h overrange 0 600W 0 6000 nominal range underrange 4 wire 0 3000W A2h overrange 0 3000W 0 30000 nominal range underrange 2 wire 0 60W D0h 70 55W 32511 overrange 0 60W 0 27648 nominal range underrange 2 wire 0 600W D1h 705 5W 3251...

Page 299: ...diagnostic interrupt functions the diagnostics data serve for information about this module On error the corresponding channel LED of the module is activated and the error is registered in the diagnostics data The following errors are listed in the diagnostics data n Error in project engineering parameterization n Measuring range overflow n Measuring range underflow DS Record set for access via CP...

Page 300: ...H 7ERR 4 reserved 00h 0Eh 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set at external auxiliary supply missing n Bit 6 5 reserved n Bit 7 set at error in parameterization Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information presen...

Page 301: ...rror channel x n Bit 0 set at error in project engineering parameterization n Bit 3 1 reserved n Bit 4 set at wire break n Bit 5 reserved n Bit 6 set at measuring range underflow n Bit 7 set at measuring range overflow Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts...

Page 302: ...phase and neutral wires 230 400V 1A n Retentive storage of the energy values n Diagnostic function n Resolution of the measured value 24bit n The following measurands can be found in 4 quadrant operation Voltage current Electrical power Electrical work Harmonics Phase shift cos j Frequency 1 Locking lever terminal module 2 Labeling strip 3 Backplane bus 4 LED status indication 5 DC 24V power secti...

Page 303: ...t value undershot omitted in 1 phase operation I red Current in the parametrized range Current limit value exceeded cos red Phase shift cos j in the parametrized range Phase shift cos j limit value undershot omitted in 1 phase operation TEMP red Temperature in the parametrized range Temperature limit value exceeded P green B P Power proportional blinks with increasing frequency proportional to the...

Page 304: ...nt IL2 7 IL3 I Current measurement IL3 8 IN I Current measurement IN I Input When using the 031 1PA00 the DC 24V power section supply of the fur ther backplane bus is interrupted By installing a power module after the 031 1PA00 the DC 24V power section supply at the backplane bus can be continued CAUTION Use only with terminal module 001 0AA40 Please consider that the electronic module AI1x 3Ph 23...

Page 305: ... D00 D 11 12 User data output byte 0 11 6401h s 1 02h 3 27 1 Technical data Order no 031 1PA00 Type SM 031 Module ID 0882 2880 Current consumption power loss Current consumption from backplane bus 60 mA Power loss 0 9 W Rated load voltage Status information alarms diagnostics Status display yes Interrupts yes parameterizable Process alarm no Diagnostic interrupt no Diagnostic functions yes paramet...

Page 306: ... power Reactive power Apparent power Cos phi Harmonic voltage RMS Harmonic current RMS Adjustable limits Voltage RMS min max Current RMS min max Cos phi min Temperature max Frequency min max Datasizes Input bytes 16 Output bytes 16 Parameter bytes 28 Diagnostic bytes 20 Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 12 9 mm x 109 mm x 76 5 mm Weight 60 g...

Page 307: ...itched off possibly remove fuses The electronic module may only be replaced on power off Only properly qualified electrical staff is allowed to install connect and or modify electrical equipment Please adhere to the national rules and regulations of the location and or country where the units are installed installation safety pre cautions EMC CAUTION Provide overvoltage protection The module is de...

Page 308: ...module will be destroyed by directly connecting one phase to a low resistance current connector CAUTION Use current transformer with max 1A You may only use current transformer with max current of 1A Please consider the data sheet of your current transformer CAUTION Note characteristics of current transformers Please consider the data sheet of your current transformer Some current transformer must...

Page 309: ...ter values The measured values of all the measurands are stored in the module with one record set ID DS ID The following must be observed n All measured values with the same DS ID come from the same measurement and are consistent n By specifying the DS ID you can address the individual measured values of the same measurement n The DS ID covers the values 1 15 The start value can freely be selected...

Page 310: ...wing the data types are listed which are used in the module The length is to be considered particularly by the definition of Frames Data type Length in byte Description UINT_8 1 Integer 8bit UINT_16 2 Integer 16bit UINT_32 4 Integer 32bit INT_8 1 Signed integer 8bit INT_16 2 Signed integer 16bit INT_32 4 Signed integer 32bit FLOAT 4 32bit floating point IEEE 754 3 27 3 2 Principle of measurement n...

Page 311: ...se note that the overall accuracy of the assembly of measuring module and current transformers depends on the accuracy class of the transformers The transformer factor is retentive stored and taken into account while counting A change of the transformer factor is taken immediately recognized Current counter values are not changed new values are added When the transformer factor was changed current...

Page 312: ...e The total cos j is calculated by dividing total active power P and total apparent power S Harmonics are oscillations of the voltages and currents whose frequency is an integer multiple of the basic frequency The 1 harmonic is the basic frequency or mains fre quency nominally 50Hz or 60Hz The level of harmonics is a measure for the network quality Harmonics or harmonic oscillations are caused by ...

Page 313: ...upply grid Please note that the phases to be measured must be from the same supply grid Reset energy counters after installation As soon as the module is supplied by the DC 24V power section supply the measurement is started and the counting of the energy counters is continued with the retentive stored counter values The measurement is not interrupted by STOP or RESET of the CPU respectively the b...

Page 314: ... UINT_16 Voltage upper limit V Range of values 0 500 260 83h 310Ah 310Bh 08h VRMS_MIN UINT_16 Voltage lower limit V Range of values 0 500 200 310Ch 310Dh 09h PF_MIN UINT_8 CosPhi lower limit 0 01 Range of values 0 100 30 84h 310Eh 0Ah T_MAX UINT_16 Temperature upper limit 0 01 C Range of values 0 20000 7000 85h 310Fh 3110h 0Bh F_MAX UINT_16 Frequency upper limit 0 01 Hz Range of values 0 20000 510...

Page 315: ...tion via Web server 0 Write Protect de activated 1 Write Protect activated Please see the following note 1 2 reserved 0 3 Phase 1 Measurement phase L1 0 Measurement is activated 1 Measurement is de activated 0 4 Phase 2 Measurement phase L2 0 Measurement is activated 1 Measurement is de activated 0 5 Phase 3 Measurement phase L3 0 Measurement is activated 1 Measurement is de activated 0 6 Data typ...

Page 316: ...e energy consumer INT_32 1Wh 0 4 294 967 295 2 Counter Active energy producer INT_32 1Wh 0 4 294 967 295 3 Counter Active energy L1 consumer INT_32 1Wh 0 4 294 967 295 4 Counter Active energy L1 producer INT_32 1Wh 0 4 294 967 295 5 Counter Active energy L2 consumer INT_32 1Wh 0 4 294 967 295 6 Counter Active energy L2 producer INT_32 1Wh 0 4 294 967 295 7 Counter Active energy L3 consumer INT_32 ...

Page 317: ...0 35 Current L3 INT_16 1mA 0 5 000 000 36 Cos phi L3 INT_8 0 01 100 100 37 Harmonic voltage L3 UINT_32 1mV 0 300 000 38 Harmonic current L3 UINT_16 1mA 0 5 000 000 39 Overflow energy meter Is incremented by 1 in case of overflow of the energy meter ID 1 UINT_32 40 Overflow energy meter Is incremented by 1 in case of overflow of the energy meter ID 2 UINT_32 41 Ä Status measurement on page 318 UINT...

Page 318: ...it 6 Frequency below limit value F_MIN n Bit 7 Temperature above limit value T_MAX 1 0 de activated 1 activated n Bit 0 0 deleted via CMD Frame 0x04 1 if there was a RESET of the module This happens after PowerON n Bit 1 Current at phase L1 above limit value L1 IRMS_MAX n Bit 2 Current at phase L2 above limit value L2 IRMS_MAX n Bit 3 Current at phase L3 above limit value L3 IRMS_MAX n Bit 4 Effic...

Page 319: ... measured value of a measurand hap pens by means of the corresponding ID B2 B2 Header byte 2 n Bit 3 0 Data set ID DS ID of the measured value 1 15 n Bit 7 4 Length of the user data 1 12 B3 B3 Header byte 3 Common status n Bit 0 Frequency F_MAX exceeded n Bit 1 Frequency F_MIN undershot n Bit 2 Temperature T_MAX exceeded n Bit 3 Voltage VRMS_MAX exceeded n Bit 4 Voltage VRMS_MIN undershot n Bit 5 ...

Page 320: ...asurand Ä 321 0x02 Read Frame Read a previously defined data package Frame Ä 325 0x03 Set Frame Define the data areas of a data package Frame Ä 323 0x04 CMD Frame Send a command Ä 327 The measured values of one measurement are accessible in the module via one DS ID Ä DS ID on page 309 Length of user data are specified from D00 D11 On error no user data are transferred i e the length of the user da...

Page 321: ...elegram type Read Frame applied at Frame 0 After the start up of the module there are automatic Zero Frame requests as long as the process data communication comes from the head module Ä Chapter 3 27 7 2 4 Read Frame on page 325 3 27 7 2 2 Read Value With Read Value all the measured values can be requested Request Byte Value Description B0 0x10 n Bit 3 0 Error code not relevant n Bit 6 4 001 Teleg...

Page 322: ...equest Byte Value Description B0 0x10 Telegram type Read Value B1 0x0E Ä ID on page 309 of the measurand B2 0x01 Ä DS ID on page 309 of the measured value to be read DS ID 1 B3 0x00 Common status not relevant D00 User data not relevant D11 Response Byte Value Description B0 0x10 Telegram type Read value from the request B1 0x0E ID of the measurand from the request B2 0x21 Length of the user data h...

Page 323: ...n 1 byte each measurand regarding that the measured values do not exceed the total length of 12 byte Here the format of the measured values is taken into account Ä Chapter 3 27 6 Measurands on page 316 Ä Data type on page 310 D11 Response Byte Value Description B0 0x30 n Bit 3 0 Ä Status communication on page 319 n Bit 6 4 011 Telegram type Set Frame n Bit 7 0 fix reserved B1 n FR ID of the Frame ...

Page 324: ...D00 0x03 User data with the ID of the measurands D01 0x0D D02 0x0C D03 Remaining user data are not relevant D11 Response Byte Value Description B0 0x30 Telegram type Set Frame from the request B1 0x01 FR ID of the Frame from the request B2 0x03 Length of the user data from the request B3 0x00 Ä Common status on page 320 OK D00 0x03 User data from the request D01 0x0D D02 0x0C D03 Remaining user da...

Page 325: ...to be read B3 0x00 n Common status not relevant D00 n Common status not relevant D11 Response Byte Value Description B0 0x20 n Bit 3 0 Ä Status communication on page 319 n Bit 6 4 010 Telegram type Read Frame n Bit 7 0 fix reserved B1 n FR ID of the Frame from the request B2 n Length of the user data with measured values in byte n DS ID of the measured value from the request which was read B3 n Ä ...

Page 326: ...0 Common status not relevant D00 User data not relevant D11 Response Byte Value Description B0 0x20 Telegram type Read value from the request B1 0x01 FR ID of the Frame from the request B2 0x71 Length of the Frame with measured values 7 DS ID of the measured value from the request B3 0x00 Ä Common status on page 320 OK D00 0x00 Counter Active energy L1 consumer 500kWh D01 0x07 D02 0xA1 D03 0x20 D0...

Page 327: ... not relevant D00 n User data depending on CMD ID 0x01 Reset of all energy counters user data not relevant 0x03 Reset the status bits User data 4byte with the corresponding set bits 0x04 Request the firmware version user data not relevant D11 Response Byte Value Description B0 0x40 n Bit 3 0 Ä Status communication on page 319 n Bit 6 4 100 Telegram type CMD Frame n Bit 7 0 fix reserved B1 n CMD ID...

Page 328: ... B1 0x03 CMD ID Reset the status bits B2 0x40 Reset the status bits length user data 4byte B3 0x00 Common status not relevant D00 0xFF User data Reset the status bits D01 0xFF D02 0xFF D03 0xFF Response Byte Value Description B0 0x40 Telegram type CMD Frame from the request B1 0x03 CMD ID from the request B2 0x40 Length of the user data from the request B3 0x00 Ä Common status on page 320 OK D00 0...

Page 329: ...00 Status bits have been reset 10 0x10 0x29 0x05 0x00 Query the status bits M 41 5 11 0x10 0x29 0x45 0x04 0x00 0x00 0x00 0x00 Status bits have been reset Temperature exceeded is reported 3 27 8 Error messages and diagnostics 3 27 8 1 Status and error messages Ä Common status on page 320 Ä Status communication on page 319 Ä Status measurement on page 318 3 27 8 2 Diagnostic data This module does no...

Page 330: ... NUMBIT 1 Number diagnostic bits per channel 08h 07h NUMCH 1 Number of channels of a module 01h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR CH7ERR 7 reserved 00h 0Bh 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at channel error n Bit 4 set at extern...

Page 331: ... at error in channel 0 Byte Bit 7 0 0 Channel specific error channel 0 n Bit 0 set at configuration parametrization error n Bit 7 1 reserved Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again ERR_D Diagnostic ...

Page 332: ...25 and the UDT 325 from the library into the directory blocks of your project ð Now you have access to the blocks via your user application 3 To use the UDT with your data block create a new data block in your project and enter at Type in the declaration view UDT 325 ð The data block is created and the structure of the UDT is used 3 27 9 2 FB 325 EM_COM_1 Communication with 031 1PA00 This module e...

Page 333: ...ng measured values Polltime INPUT TIME n Interval for the periodic reading Control_Global INPUT BYTE 0 de activated 1 activated n Bit 0 Periodic execution according to the Polltime default n Bit 1 Immediate execution bit is to be reset after the exe cution n Bit 6 2 reserved n Bit 7 Re initialization of the block by the configuration is sent again Status_Global OUTPUT BYTE Block status n 0x00 Not ...

Page 334: ...error information Reserved ARRAY of BYTE 1 28 reserved After the header data in the UDT there are the measurands sequentially listed with the following structure Name Declaration Data type Description Name IN_OUT STRUCT n Name of the measurand Read_Mode INPUT BYTE n Bit 0 Accessing the measured value 0 Measured value is not read 1 Measured value is read Value OUTPUT DWORD n Current measured value ...

Page 335: ...ed values available 0x80A7 Error DS ID 0x80A8 Error CMD Frame Command could not be executed 0x80AF Internal error Please contact the hotline On an internal error 0x0F all the measurements are stopped and a reset to the default parame ters of the module is triggered Here all counter values and Frame definitions are deleted VIPA System SLIO Analog Input 031 1PA00 AI1x 3Ph 230 400V 1A Use handling bl...

Page 336: ... indices IX respectively subindices SX for CANopen respec tively EtherCAT are listed The modules have diagnostics capability The following errors may release a diagnostic n Error in parameterization n Short circuit recognition n Wire break recognition Alternated blinking of the channel error LEDs The alternate blinking of the channel error LEDs of channel 0 and 1 indi cates a watchdog error due to...

Page 337: ...rmulas allow you to trans form a value digital value to an analog value and vice versa Voltage Output range funct no Voltage U Decimal D Hex Range Formulas 0 10V Siemens S7 format 10h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h Not possible is limited to 0V underrange 0 10V Siemens S5 format 20h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V 8...

Page 338: ...0h 10V 16384 C000h 12 5V 20480 B000h underrange Current Output range funct no Current I Decimal D Hex Range Formulas 0 20mA Siemens S7 format 31h 23 52mA 32511 7EFFh overrange 20mA 27648 6C00h nominal range 10mA 13824 3600h 0mA 0 0000h Not possible is limited to 0mA underrange 0 20mA Siemens S5 format 41h 25 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 10mA 8192 2000h 0mA 0 0000h Not ...

Page 339: ...A 27648 6C00h nominal range 12mA 13824 3600h 4mA 0 0000h 0mA 6912 E500h underrange 4 20mA Siemens S5 format 40h 24 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 12mA 8192 2000h 4mA 0 0000h 0mA 4096 F000h underrange 4 20mA VIPA System SLIO Analog Output Output ranges and function numbers HB300 SM AIO en 17 05 339 ...

Page 340: ...4V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Fehler Busversorgungsspannung X B X Error at bus power supply Ä Chapter 2 8 Trouble...

Page 341: ...he output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1 ...

Page 342: ...utput voltage ranges 0 V 10 V Operational limit of voltage ranges 0 3 Basic error limit voltage ranges 0 2 Destruction limit against external applied voltage max 24V Current outputs Max in load resistance current range Max inductive load current range Typ open circuit voltage current output Output current ranges Operational limit of current ranges Basic error limit current ranges Destruction limit...

Page 343: ...Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 4 Parameter bytes 8 Diagnostic bytes 20 Housing Mater...

Page 344: ...h 80h 3102h 03h CH1FN 1 Function number channel 1 10h 81h 3103h 04h Byte Bit 7 0 0 n Bit 0 Short circuit recognition channel 0 1 on n Bit 1 Short circuit recognition channel 1 1 on n Bit 7 2 reserved In the following there are the measuring ranges with corresponding function number listed which were supported by the analog module With FFh the corresponding channel is deactivated The formulas liste...

Page 345: ...ing parameterization n Short circuit overload if parameterized DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by DS 00h IX Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h More can be found in ...

Page 346: ... module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer overflow n Bit 4 set at internal communication error n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input output 76h Counter n Bit 7 reserved Byte Bit 7 0 0 Num...

Page 347: ... set at short circuit to ground n Bit 7 4 reserved Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMCH Channels CHERR Channel error CH0ERR CH1ERR Channel specific CH2ERR CH7ERR reserved DIAG_US µs ticker ...

Page 348: ...ication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 ...

Page 349: ...e output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1 0...

Page 350: ...tional limit of voltage ranges Basic error limit voltage ranges Destruction limit against external applied voltage Current outputs ü Max in load resistance current range 350 Ω Max inductive load current range 10 mH Typ open circuit voltage current output 12 V Output current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 4 0 5 Basic error limit current ranges 0 2 0 3 Destruction...

Page 351: ...difference between circuits Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 4 Parameter bytes 8 Diagn...

Page 352: ...number channel 0 31h 80h 3102h 03h CH1FN 1 Function number channel 1 31h 81h 3103h 04h Byte Bit 7 0 0 n Bit 0 Wire break recognition channel 0 1 on n Bit 1 Wire break recognition channel 1 1 on n Bit 7 2 reserved In the following there are the measuring ranges with corresponding function number listed which were supported by the analog module With FFh the corresponding channel is deactivated The f...

Page 353: ...inal range 12mA 13824 3600h 4mA 0 0000h 0mA 6912 E500h underrange 4 20mA Siemens S5 format 40h 24 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 12mA 8192 2000h 4mA 0 0000h 0mA 4096 F000h underrange 4 5 3 Diagnostic data So this module does not support diagnostic interrupt functions the diagnostics data serve for information about this module On error the corresponding channel LED of th...

Page 354: ...diagnostic bits per channel 08h 07h NUMCH 1 Number of channels of a module 02h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR CH7ERR 6 reserved 00h 0Ch 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at ch...

Page 355: ...mber of channels of a module here 02h Byte Bit 7 0 0 n Bit 0 set at error in channel group 0 n Bit 1 set at error in channel group 1 n Bit 7 2 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 3 1 reserved n Bit 4 set at wire break n Bit 7 5 reserved Byte Bit 7 0 0 reserved ERR_D Diagnostic CHTYP Channel type NUMBIT Diagnostic bits...

Page 356: ...tic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again DIAG_US µs ticker VIPA System SLIO Analog Output 032 1BB40 AO 2x12Bit 0 4 20mA Diagnostic data HB300 SM AIO en 17 05 356 ...

Page 357: ...5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble ...

Page 358: ... the output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Adr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1...

Page 359: ... 10 mA Output voltage ranges 10 V 10 V 0 V 10 V Operational limit of voltage ranges 0 3 Basic error limit voltage ranges 0 2 Destruction limit against external applied voltage max 24V Current outputs Max in load resistance current range Max inductive load current range Typ open circuit voltage current output Output current ranges Operational limit of current ranges Basic error limit current ranges...

Page 360: ...l difference between circuits Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 4 Parameter bytes 8 Dia...

Page 361: ...umber channel 0 12h 80h 3102h 03h CH1FN 1 Function number channel 1 12h 81h 3103h 04h Byte Bit 7 0 0 n Bit 0 Short circuit recognition channel 0 1 on n Bit 1 Short circuit recognition channel 1 1 on n Bit 7 2 reserved In the following there are the measuring ranges with corresponding function number listed which were supported by the analog module With FFh the corresponding channel is deactivated ...

Page 362: ...iemens S7 format 10h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h Not possible is limited to 0V underrange 0 10V Siemens S5 format 20h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V 8192 2000h 0V 0 0000h Not possible is limited to 0V underrange 4 6 3 Diagnostic data So this module does not support diagnostic interrupt functions the diagnostics ...

Page 363: ...4h ERR_D 1 Diagnostic 00h 05h CHTYP 1 Channel type 73h 06h NUMBIT 1 Number diagnostic bits per channel 08h 07h NUMCH 1 Number of channels of a module 02h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR CH7ERR 6 reserved 00h 0Ch 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n ...

Page 364: ... of channels of a module here 02h Byte Bit 7 0 0 n Bit 0 set at error in channel group 0 n Bit 1 set at error in channel group 1 n Bit 7 2 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 2 1 reserved n Bit 3 set at short circuit to ground n Bit 7 4 reserved Byte Bit 7 0 0 reserved ERR_D Diagnostic CHTYP Channel type NUMBIT Diagno...

Page 365: ...ostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again DIAG_US µs ticker VIPA System SLIO Analog Output 032 1BB70 AO 2x12Bit 10V Diagnostic data HB300 SM AIO en 17 05 365 ...

Page 366: ...DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble sh...

Page 367: ...corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1 02h 4 AO 2 2 Analog value channel ...

Page 368: ...utput voltage ranges 0 V 10 V Operational limit of voltage ranges 0 3 Basic error limit voltage ranges 0 2 Destruction limit against external applied voltage max 24V Current outputs Max in load resistance current range Max inductive load current range Typ open circuit voltage current output Output current ranges Operational limit of current ranges Basic error limit current ranges Destruction limit...

Page 369: ...Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 8 Parameter bytes 10 Diagnostic bytes 20 Housing Mate...

Page 370: ... 10h 82h 3104h 05h CH3FN 1 Function number channel 3 10h 83h 3105h 06h Byte Bit 7 0 0 n Bit 0 Short circuit recognition channel 0 1 on n Bit 1 Short circuit recognition channel 1 1 on n Bit 2 Short circuit recognition channel 2 1 on n Bit 3 Short circuit recognition channel 3 1 on n Bit 7 4 reserved In the following there are the measuring ranges with corresponding function number listed which wer...

Page 371: ...ing parameterization n Short circuit overload if parameterized DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by DS 00h IX Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h More can be found in ...

Page 372: ...Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer overflow n Bit 4 set at internal communication error n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input outp...

Page 373: ...ignment error n Bit 2 1 reserved n Bit 3 set at short circuit to ground n Bit 7 4 reserved Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMCH Channels CHERR Channel error CH0ERR CH3ERR Channel specific C...

Page 374: ...ication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 ...

Page 375: ...orresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1 02h 4 AO 2 2 Analog value channel 2...

Page 376: ...tional limit of voltage ranges Basic error limit voltage ranges Destruction limit against external applied voltage Current outputs ü Max in load resistance current range 350 Ω Max inductive load current range 10 mH Typ open circuit voltage current output 12 V Output current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 4 0 5 Basic error limit current ranges 0 2 0 3 Destruction...

Page 377: ...ifference between circuits Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 8 Parameter bytes 10 Diagn...

Page 378: ...ction number channel 2 31h 82h 3104h 05h CH3FN 1 Function number channel 3 31h 83h 3105h 06h Byte Bit 7 0 0 n Bit 0 Wire break recognition channel 0 1 on n Bit 1 Wire break recognition channel 1 1 on n Bit 2 Wire break recognition channel 2 1 on n Bit 3 Wire break recognition channel 3 1 on n Bit 7 4 reserved In the following there are the measuring ranges with corresponding function number listed...

Page 379: ... nominal range 12mA 13824 3600h 4mA 0 0000h 0mA 6912 E500h underrange 4 20mA Siemens S5 format 40h 24 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 12mA 8192 2000h 4mA 0 0000h 0mA 4096 F000h underrange 4 8 3 Diagnostic data So this module does not support interrupt functions the diagnostics data serve for infor mation about this module On error the corresponding channel LED of the modu...

Page 380: ... of channels of a module 04h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR 1 Channel specific error channel 2 00h 0Ch CH3ERR 1 Channel specific error channel 3 00h 0Dh CH4ERR CH7ERR 4 reserved 00h 0Eh 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal err...

Page 381: ... Bit 2 set at error in channel group 2 n Bit 3 set at error in channel group 3 n Bit 7 4 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 3 1 reserved n Bit 4 set at wire break n Bit 7 5 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With Pow...

Page 382: ...5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble ...

Page 383: ... corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1 02h 4 AO 2 2 Analog value channel...

Page 384: ... 10 mA Output voltage ranges 10 V 10 V 0 V 10 V Operational limit of voltage ranges 0 3 Basic error limit voltage ranges 0 2 Destruction limit against external applied voltage max 24V Current outputs Max in load resistance current range Max inductive load current range Typ open circuit voltage current output Output current ranges Operational limit of current ranges Basic error limit current ranges...

Page 385: ...l difference between circuits Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 60 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 8 Parameter bytes 10 Di...

Page 386: ...hannel 2 12h 82h 3104h 05h CH3FN 1 Function number channel 3 12h 83h 3105h 06h Byte Bit 7 0 0 n Bit 0 Short circuit recognition channel 0 1 on n Bit 1 Short circuit recognition channel 1 1 on n Bit 2 Short circuit recognition channel 2 1 on n Bit 3 Short circuit recognition channel 3 1 on n Bit 7 4 reserved In the following there are the measuring ranges with corresponding function number listed w...

Page 387: ...iemens S7 format 10h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h Not possible is limited to 0V underrange 0 10V Siemens S5 format 20h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V 8192 2000h 0V 0 0000h Not possible is limited to 0V underrange 4 9 3 Diagnostic data So this module does not support diagnostic interrupt functions the diagnostics ...

Page 388: ...h ERR_C 1 reserved 00h 04h ERR_D 1 Diagnostic 00h 05h CHTYP 1 Channel type 73h 06h NUMBIT 1 Number diagnostic bits per channel 08h 07h NUMCH 1 Number of channels of a module 04h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR 1 Channel specific error channel 2 00h 0Ch CH3ERR 1 Channel specific error channe...

Page 389: ...here 08h Byte Bit 7 0 0 Number of channels of a module here 04h Byte Bit 7 0 0 n Bit 0 set at error in channel group 0 n Bit 1 set at error in channel group 1 n Bit 2 set at error in channel group 2 n Bit 3 set at error in channel group 3 n Bit 7 4 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 2 1 reserved n Bit 3 set at short ...

Page 390: ...nostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again CH4ERR CH7ERR reserved DIAG_US µs ticker VIPA System SLIO Analog Output 032 1BD70 AO 4x12Bit 10V Diagnostic data HB300 SM AIO en 17 05 390 ...

Page 391: ...DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble sh...

Page 392: ...he output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1 ...

Page 393: ...utput voltage ranges 0 V 10 V Operational limit of voltage ranges 0 2 Basic error limit voltage ranges 0 1 Destruction limit against external applied voltage max 24V Current outputs Max in load resistance current range Max inductive load current range Typ open circuit voltage current output Output current ranges Operational limit of current ranges Basic error limit current ranges Destruction limit...

Page 394: ...Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 4 Parameter bytes 8 Diagnostic bytes 20 Housing Mater...

Page 395: ...0h 80h 3102h 03h CH1FN 1 Function number channel 1 10h 81h 3103h 04h Byte Bit 7 0 0 n Bit 0 Short circuit recognition channel 0 1 on n Bit 1 Short circuit recognition channel 1 1 on n Bit 7 2 reserved In the following there are the measuring ranges with corresponding function number listed which were supported by the analog module With FFh the corresponding channel is deactivated The formulas list...

Page 396: ...ing parameterization n Short circuit overload if parameterized DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by DS 00h IX Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h More can be found in ...

Page 397: ... module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer overflow n Bit 4 set at internal communication error n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input output 76h Counter n Bit 7 reserved Byte Bit 7 0 0 Num...

Page 398: ... set at short circuit to ground n Bit 7 4 reserved Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMCH Channels CHERR Channel error CH0ERR CH1ERR Channel specific CH2ERR CH7ERR reserved DIAG_US µs ticker ...

Page 399: ...ication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 ...

Page 400: ...e output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1 0...

Page 401: ...erational limit of voltage ranges Basic error limit voltage ranges Destruction limit against external applied voltage Current outputs ü Max in load resistance current range 350 Ω Max inductive load current range 10 mH Typ open circuit voltage current output 12 V Output current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 2 Basic error limit current ranges 0 1 Destruction limi...

Page 402: ...difference between circuits Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 4 Parameter bytes 8 Diagn...

Page 403: ...04h Byte Bit 7 0 0 n Bit 0 Wire break recognition channel 0 1 on n Bit 1 Wire break recognition channel 1 1 on n Bit 7 2 reserved Please consider with enabled wire break recognition with the output range 0 20mA when the current goes below of 40µA 100 Digits this can may lead to sporadic wire break messages In the following there are the measuring ranges with corresponding function number listed wh...

Page 404: ...nal range 12mA 13824 3600h 4mA 0 0000h 0mA 6912 E500h underrange 4 20mA Siemens S5 format 40h 24 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 12mA 8192 2000h 4mA 0 0000h 0mA 4096 F000h underrange 4 11 3 Diagnostic data So this module does not support diagnostic interrupt functions the diagnostics data serve for information about this module On error the corresponding channel LED of th...

Page 405: ...diagnostic bits per channel 08h 07h NUMCH 1 Number of channels of a module 02h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR CH7ERR 6 reserved 00h 0Ch 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal error n Bit 2 set at external error n Bit 3 set at ch...

Page 406: ...mber of channels of a module here 02h Byte Bit 7 0 0 n Bit 0 set at error in channel group 0 n Bit 1 set at error in channel group 1 n Bit 7 2 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 3 1 reserved n Bit 4 set at wire break n Bit 7 5 reserved Byte Bit 7 0 0 reserved ERR_D Diagnostic CHTYP Channel type NUMBIT Diagnostic bits...

Page 407: ...tic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again DIAG_US µs ticker VIPA System SLIO Analog Output 032 1CB40 AO 2x16Bit 0 4 20mA Diagnostic data HB300 SM AIO en 17 05 407 ...

Page 408: ...5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble ...

Page 409: ...the output area is embedded to the corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1...

Page 410: ... 10 mA Output voltage ranges 10 V 10 V 0 V 10 V Operational limit of voltage ranges 0 2 Basic error limit voltage ranges 0 1 Destruction limit against external applied voltage max 24V Current outputs Max in load resistance current range Max inductive load current range Typ open circuit voltage current output Output current ranges Operational limit of current ranges Basic error limit current ranges...

Page 411: ...l difference between circuits Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 4 Parameter bytes 8 Dia...

Page 412: ...number channel 0 12h 80h 3102h 03h CH1FN 1 Function number channel 1 12h 81h 3103h 04h Byte Bit 7 0 0 n Bit 0 Short circuit recognition channel 0 1 on n Bit 1 Short circuit recognition channel 1 1 on n Bit 7 2 reserved In the following there are the measuring ranges with corresponding function number listed which were supported by the analog module With FFh the corresponding channel is deactivated...

Page 413: ...emens S7 format 10h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h Not possible is limited to 0V underrange 0 10V Siemens S5 format 20h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V 8192 2000h 0V 0 0000h Not possible is limited to 0V underrange 4 12 3 Diagnostic data So this module does not support diagnostic interrupt functions the diagnostics ...

Page 414: ...4h ERR_D 1 Diagnostic 00h 05h CHTYP 1 Channel type 73h 06h NUMBIT 1 Number diagnostic bits per channel 08h 07h NUMCH 1 Number of channels of a module 02h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR CH7ERR 6 reserved 00h 0Ch 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n ...

Page 415: ... of channels of a module here 02h Byte Bit 7 0 0 n Bit 0 set at error in channel group 0 n Bit 1 set at error in channel group 1 n Bit 7 2 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 2 1 reserved n Bit 3 set at short circuit to ground n Bit 7 4 reserved Byte Bit 7 0 0 reserved ERR_D Diagnostic CHTYP Channel type NUMBIT Diagno...

Page 416: ...ostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again DIAG_US µs ticker VIPA System SLIO Analog Output 032 1CB70 AO 2x16Bit 10V Diagnostic data HB300 SM AIO en 17 05 416 ...

Page 417: ...DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble sh...

Page 418: ...corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1 02h 4 AO 2 2 Analog value channel ...

Page 419: ...utput voltage ranges 0 V 10 V Operational limit of voltage ranges 0 2 Basic error limit voltage ranges 0 1 Destruction limit against external applied voltage max 24V Current outputs Max in load resistance current range Max inductive load current range Typ open circuit voltage current output Output current ranges Operational limit of current ranges Basic error limit current ranges Destruction limit...

Page 420: ...Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 8 Parameter bytes 10 Diagnostic bytes 20 Housing Mate...

Page 421: ...2 10h 82h 3104h 05h CH3FN 1 Function number channel 3 10h 83h 3105h 06h Byte Bit 7 0 0 n Bit 0 Short circuit recognition channel 0 1 on n Bit 1 Short circuit recognition channel 1 1 on n Bit 2 Short circuit recognition channel 2 1 on n Bit 3 Short circuit recognition channel 3 1 on n Bit 7 4 reserved In the following there are the measuring ranges with corresponding function number listed which we...

Page 422: ...ing parameterization n Short circuit overload if parameterized DS Record set for access via CPU PROFIBUS and PROFINET The access happens by DS 01h Additionally the first 4 bytes may be accessed by DS 00h IX Index for access via CANopen The access happens by IX 2F01h Additionally the first 4 bytes may be accessed by IX 2F00h SX Subindex for access via EtherCAT with Index 5005h More can be found in ...

Page 423: ...Byte Bit 7 0 0 n Bit 3 0 module class 0101b analog module n Bit 4 set at channel information present n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 2 0 reserved n Bit 3 set at internal diagnostics buffer overflow n Bit 4 set at internal communication error n Bit 7 5 reserved Byte Bit 7 0 0 n Bit 6 0 Channel type 70h Digital input 71h Analog input 72h Digital output 73h Analog output 74h Analog input outp...

Page 424: ...ignment error n Bit 2 1 reserved n Bit 3 set at short circuit to ground n Bit 7 4 reserved Byte Bit 7 0 0 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again NUMCH Channels CHERR Channel error CH0ERR CH3ERR Channel specific C...

Page 425: ...ication 5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 ...

Page 426: ...orresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1 02h 4 AO 2 2 Analog value channel 2...

Page 427: ...erational limit of voltage ranges Basic error limit voltage ranges Destruction limit against external applied voltage Current outputs ü Max in load resistance current range 350 Ω Max inductive load current range 10 mH Typ open circuit voltage current output 12 V Output current ranges 0 mA 20 mA 4 mA 20 mA Operational limit of current ranges 0 2 Basic error limit current ranges 0 1 Destruction limi...

Page 428: ...ifference between circuits Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 8 Parameter bytes 10 Diagn...

Page 429: ...3105h 06h Byte Bit 7 0 0 n Bit 0 Wire break recognition channel 0 1 on n Bit 1 Wire break recognition channel 1 1 on n Bit 2 Wire break recognition channel 2 1 on n Bit 3 Wire break recognition channel 3 1 on n Bit 7 4 reserved Please consider with enabled wire break recognition with the output range 0 20mA when the current goes below of 40µA 100 Digits this can may lead to sporadic wire break mes...

Page 430: ... nominal range 12mA 13824 3600h 4mA 0 0000h 0mA 6912 E500h underrange 4 20mA Siemens S5 format 40h 24 00mA 20480 5000h overrange 20mA 16384 4000h nominal range 12mA 8192 2000h 4mA 0 0000h 0mA 4096 F000h underrange 4 14 3 Diagnostic data So this module does not support interrupt functions the diagnostics data serve for infor mation about this module On error the corresponding channel LED of the mod...

Page 431: ... of channels of a module 04h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR 1 Channel specific error channel 2 00h 0Ch CH3ERR 1 Channel specific error channel 3 00h 0Dh CH4ERR CH7ERR 4 reserved 00h 0Eh 11h DIAG_US 4 µs ticker 00h 13h Byte Bit 7 0 0 n Bit 0 set at module failure n Bit 1 set at internal err...

Page 432: ... Bit 2 set at error in channel group 2 n Bit 3 set at error in channel group 3 n Bit 7 4 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 3 1 reserved n Bit 4 set at wire break n Bit 7 5 reserved Byte Bit 7 0 0 3 Value of the µs ticker at the moment of the diagnostic µs ticker In the SLIO module there is a timer µs ticker With Pow...

Page 433: ...5 DC 24V power section supply 6 Electronic module 7 Terminal module 8 Locking lever electronic module 9 Terminal RUN MF AO x Description green red red X Bus communication is OK Module status is OK X Bus communication is OK Module status reports an error X Bus communication is not possible Module status reports an error X Error at bus power supply X B X Error in configuration Ä Chapter 2 8 Trouble ...

Page 434: ... corresponding address area IX Index for access via CANopen with s Subindex depends on number and type of analog modules SX Subindex for access via EtherCAT with Index 7000h EtherCAT Slot More can be found in the according manual of your bus coupler Addr Name Bytes Function IX SX 0 AO 0 2 Analog value channel 0 6411h s 01h 2 AO 1 2 Analog value channel 1 6411h s 1 02h 4 AO 2 2 Analog value channel...

Page 435: ... 10 mA Output voltage ranges 10 V 10 V 0 V 10 V Operational limit of voltage ranges 0 2 Basic error limit voltage ranges 0 1 Destruction limit against external applied voltage max 24V Current outputs Max in load resistance current range Max inductive load current range Typ open circuit voltage current output Output current ranges Operational limit of current ranges Basic error limit current ranges...

Page 436: ...l difference between circuits Max potential difference between inputs Ucm Max potential difference between Mana and Mintern Uiso DC 75 V AC 50 V Max potential difference between inputs and Mana Ucm Max potential difference between inputs and Mintern Uiso Max potential difference between Mintern and outputs Insulation tested with DC 500 V Datasizes Input bytes 0 Output bytes 8 Parameter bytes 10 Di...

Page 437: ...on number channel 2 12h 82h 3104h 05h CH3FN 1 Function number channel 3 12h 83h 3105h 06h Byte Bit 7 0 0 n Bit 0 Short circuit recognition channel 0 1 on n Bit 1 Short circuit recognition channel 1 1 on n Bit 2 Short circuit recognition channel 2 1 on n Bit 3 Short circuit recognition channel 3 1 on n Bit 7 4 reserved In the following there are the measuring ranges with corresponding function numb...

Page 438: ...emens S7 format 10h 11 76V 32511 7EFFh overrange 10V 27648 6C00h nominal range 5V 13824 3600h 0V 0 0000h Not possible is limited to 0V underrange 0 10V Siemens S5 format 20h 12 5V 20480 5000h overrange 10V 16384 4000h nominal range 5V 8192 2000h 0V 0 0000h Not possible is limited to 0V underrange 4 15 3 Diagnostic data So this module does not support diagnostic interrupt functions the diagnostics ...

Page 439: ...h ERR_C 1 reserved 00h 04h ERR_D 1 Diagnostic 00h 05h CHTYP 1 Channel type 73h 06h NUMBIT 1 Number diagnostic bits per channel 08h 07h NUMCH 1 Number of channels of a module 04h 08h CHERR 1 Channel error 00h 09h CH0ERR 1 Channel specific error channel 0 00h 0Ah CH1ERR 1 Channel specific error channel 1 00h 0Bh CH2ERR 1 Channel specific error channel 2 00h 0Ch CH3ERR 1 Channel specific error channe...

Page 440: ...here 08h Byte Bit 7 0 0 Number of channels of a module here 04h Byte Bit 7 0 0 n Bit 0 set at error in channel group 0 n Bit 1 set at error in channel group 1 n Bit 2 set at error in channel group 2 n Bit 3 set at error in channel group 3 n Bit 7 4 reserved Byte Bit 7 0 0 Channel specific error channel x n Bit 0 set at configuring parameter assignment error n Bit 2 1 reserved n Bit 3 set at short ...

Page 441: ...nostic µs ticker In the SLIO module there is a timer µs ticker With PowerON the timer starts counting with 0 After 232 1µs the timer starts with 0 again CH4ERR CH7ERR reserved DIAG_US µs ticker VIPA System SLIO Analog Output 032 1CD70 AO 4x16Bit 10V Diagnostic data HB300 SM AIO en 17 05 441 ...