GPD315/V7 Modbus RTU Technical Manual TM 4325
Page
28
Table 5-4 Drive Parameters (continued)
Parameter
ADDR
Name
Set
Description
Default
n090
015Ah
DC Injection
Time @ Stop
0.0 - 25.5 Seconds
(0.0 = Disabled)
0.5
n091
015Bh
DC Injection
Time @ Start
0.0 - 25.5 Seconds
(0.0 = Disabled)
0.0
0
Enabled
n092
015Ch
Stall Prevention
During Decel
1
Disabled
0
n093
015Dh
Stall Prevention
During Accel
30 - 200%
(200% = Disabled
170
n094
015Eh
Stall Prevention
During Run
30 - 200%
(200% = Disabled)
160
n095
015Fh
Frequency
Detection Level
0.00 - 9.99hz or 100.0 - 400.0hz
0.00
0
Detection Disabled.
1
Detects Only @ Speed Agree; Operation Continues
2
Detects Only @ Speed Agree; Coast To Stop
3
Detects During Run; Operation Continues
n096
0160h
Overtorque
Detection 1
4
Detects During Run; Coast To Stop
0
0
Detected By Output Torque
n097
0161h
Overtorque
Detection 2
1
Detected By Output Current
0
n098
0162h
Overtorque
Detection Level
30 - 200%
160
n099
0163h
Overtorque
Detection Time
0.1 - 10.0 Seconds
0.1
0
Output Frequency is Not stored when using up/down function
n100
0164h
Up/Down
Memory Hold
1
Output Frequency is stored when using up/down function
0
n101
0165h
Reserved
3
n102
0166h
Reserved
3
n103
0167h
Torque
Compensation
Gain
0.0 - 2.5
1.0
n104
0168h
Torque
Compensation
Time Constant
0.0 - o 25.5 Seconds
(0 Disables Primary Delay Filter)
0.3
n105
0169h
Torque
Compensation
Iron Loss
0.0 – 999.9W or 1000 – 6550W
6
n106
016Ah
Motor Rated
Slip
0.0 - 20.0hz
6
n107
016Bh
Motor Line-To-
Line
Resistance
0.000 – 9.999
ω
or 10.00 – 65.50
ω
6
n108
016Ch
Motor Leakage
Inductance
0.00 – 99.99mh or 100.0 - 655.0mh
6
n109
016Dh
Torque Limiter
0 - 250%
(Vector Control Mode)
150
n110
016Eh
Motor No-Load
Current
0 - 99%
6
n111
016Fh
Slip
Compensation
Gain
0.0 - 2.5
0.0
n112
0170h
Slip
Compensation
Time Constant
0.0 - 25.5 Seconds
(0.0 Disables Primary Delay Filter)
2.0
0
Disabled
n113
0171h
Slip
Compensation
During Regen
1
Enabled
0
n114
0172h
Reserved
3
0
Disabled
(Level Based On N094)
n115
4
0173h
Stall Prevention
During Run
1
Enabled
(Level At FMAX Is N094 X 0.4)
0