PI Feedbac
N
Input Met
K
ods
Input one feedback signal for normal PI control or input two feedback signals for controlling a differential process value.
Normal PI Feedbac
N
Input the PI feedback signal from one of the sources listed below:
7
able 1
PI Feedbac
N
Sources
PI Feedbac
N
Source
Settin
J
s
Analog Input A1
Set H3-02 = B
Analog Input A2
Set H3-10 = B
Note:
A duplicate allocation of the PI feedback input will cause an oPE alarm.
Di
II
erential Feedbac
N
The second PI feedback signal for differential feedback can come from the sources listed below. The differential feedback
function is automatically enabled when a differential feedback input is assigned.
7
able 1
1
PI Di
II
erential Feedbac
N
Sources
PI Di
II
erential Feedbac
N
Source
Settin
J
s
Analog Input A1
Set H3-02 = 16
Analog Input A2
Set H3-10 = 16
Note:
A duplicate allocation of the PI differential feedback input will cause an oPE alarm.