A
C
7
unin
J
C parameters are used to adjust the acceleration and deceleration times, S-curves, torque compensation, and carrier frequency
selections.
C1
Acceleration and Deceleration
7
imes
No
(Addr
+
e
[
)
Name
LCD Display
Description
9
alues
Pa
J
e
C1-01
(200)
Acceleration Time 1
Accel Time 1
Sets the time to accelerate from 0 to maximum frequency.
Default: 30.0 s
Min.: 0.1
Max.: 6000.0
52
C1-02
(201)
Deceleration Time 1
Decel Time 1
Sets the time to decelerate from maximum frequency to 0.
52
C1-03
(202)
Acceleration Time 2
Accel Time 2
Sets the time to accelerate from 0 to maximum frequency.
Default: 30.0 s
Min.: 0.1
Max.: 6000.0
52
C1-04
(203)
Deceleration Time 2
Decel Time 2
Sets the time to decelerate from maximum frequency to 0.
52
C1-09
(208)
Fast Stop Time
Fast Stop Time
Sets the time for the Fast Stop function.
Default: 10.0 s
Min.: 0.1
Max.: 6000.0
53
C1-11
(20A)
Accel/Decel Time
Switching Frequency
Acc/Dec SW Freq
Sets the frequency to switch between accel/decel time settings.
Setting units are determined by parameter A1-02, Control
Method Selection.
Default: 0.0 Hz
Min.: 0.0
Max.: 240.0
53
C2
S
Cur
Y
e C
K
aracteristics
No
(Addr
+
e
[
)
Name
LCD Display
Description
9
alues
Pa
J
e
C2-01
(20B)
S-Curve Characteristic
at Accel Start
SCrv Acc @ Start
The S-curve can be controlled at the four points shown below.
Run Command
Time
Output Frequency
C2-01
0.20 s <1>
C2-02
0.20 s <1>
ON
OFF
Default:
<2>
Min.: 0.00 s
Max.: 10.00 s
53
C2-02
(20C)
S-Curve Characteristic
at Accel End
SCrv Acc @ End
Default: 0.20 s
Min.: 0.00
Max.: 10.00
53
<1> S-curve characteristics at decel start/end are fixed to 0.20 s.
<2> Default setting is determined by parameter A1-02, Control Method Selection.
C
7
or
T
ue Compensation
No
(Addr
+
e
[
)
Name
LCD Display
Description
9
alues
Pa
J
e
C4-01
(215)
Torque Compensation
Gain
Torq Comp Gain
Sets the gain for the automatic torque (voltage) boost function
and helps to produce better starting torque. Used for motor 1.
Default:
<1>
Min.: 0.00
Max.: 2.50
54
C4-02
(216)
Torque Compensation
Primary Delay Time 1
Torq Comp Time
Sets the torque compensation filter time.
Default:
<2>
Min.: 0 ms
Max.: 60000 ms
54
<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
A
C
7
unin
J
222
<$6.$:$(/(&75,&
6,(3&(<$6.$:$$&'ULYH±=3URJUDPPLQJ0DQXDO
Summary of Contents for CIMR-ZU A Series
Page 10: ...7able oI Contents 7Kis PaJe Intentionally BlanN 1 6 75 6 3 6 ULYH 3URJUDPPLQJ 0DQXDO...
Page 210: ...2 DriYe CoolinJ Fans 7Kis PaJe Intentionally BlanN 21 6 75 6 3 6 ULYH 3URJUDPPLQJ 0DQXDO...
Page 320: ...C 8 7roublesKootinJ 7Kis PaJe Intentionally BlanN 2 6 75 6 3 6 ULYH 3URJUDPPLQJ 0DQXDO...
Page 377: ......