1 Multi
Function Di
J
ital Input Selections
+
1
Settin
J
Function
LCD Display
Description
Pa
J
e
B1
Customer Safeties
CustomerSafeties
The functionality is identical to Drive Enable 2 (H1-
= 70), except for the
following characteristics:
• The stopping method is forced to Coast to Stop when the input is open
• The drive will display a “SAFE” alarm if the input is open when a Run command
is present. It will not display “dnE”.
Open: Customer Safeties are open. Drive will not run. Stopping method is Coast
to Stop.
Closed: Customer Safeties are in place.
84
B2
BAS Interlock
BAS Interlock
Open: Damper interlock is not closed. Drive output is shut off (baseblocked). The
drive displays an "inTLK" message if a Run command is present. It will not display
"dnE".
Closed: Damper interlock is closed. Drive operates normally.
Note:
The state of the BAS Interlock multi-function input has no effect on
the Emergency Override multi-function inputs (H1-
= AF, B0).
The Emergency Override command is accepted when the BAS
Interlock digital input is open or closed.
84
+
2
Multi
Function Di
J
ital Outputs
No
(Addr
+
e
[
)
Name
LCD Display
Description
9
alues
Pa
J
e
H2-01
(40B)
Terminal M1-M2
function selection
(relay)
M1-M2 Func Sel
Refer to H2 Multi-Function Digital Output Settings on pages
237
to
239
for descriptions of setting values.
Default: 0
Range: 0 to 1B2
84
H2-02
(40C)
Terminal M3-M4
function selection
(relay)
M3/M4 Func Sel
Default: 1
Range: 0 to 1B2
84
H2-03
(40D)
Terminal M5-M6
function selection
(relay)
M5/M6 Func Sel
Default: 2
Range: 0 to 1B2
84
+
2 Multi
Function Di
J
ital Output Settin
J
s
+
2
Settin
J
Function
LCD Display
Description
Pa
J
e
0
During run
During RUN 1
Closed: A Run command is active or voltage is output.
85
1
Zero speed
Zero Speed
Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
85
2
Speed agree 1
Fref/Fout Agree1
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
set to L4-02).
86
3
User-set speed agree 1
Fref/Set Agree 1
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
hysteresis set to L4-02).
86
4
Frequency detection 1
Freq Detect 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
86
5
Frequency detection 2
Freq Detect 2
Closed: Output frequency is greater than or equal to the value in L4-01 with
hysteresis determined by L4-02.
87
6
Drive ready
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
87
7
DC bus undervoltage
DC Bus Undervolt
Closed: DC bus voltage is below the Uv trip level set in L2-05.
88
8
During baseblock (N.O.) BaseBlk 1
Closed: Drive has entered the baseblock state (no output voltage).
88
9
Frequency reference
source
Ref Source
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or
b1-15).
Closed: HOA keypad supplies the frequency reference.
88
A
Run command source
Run Cmd Source
Open: External Reference 1 or 2 supplies the Run command (set in b1-02).
Closed: HOA keypad supplies the Run command.
88
B
Torque detection 1
(N.O.)
Trq Det 1 N.O.
Closed: An overtorque or undertorque situation has been detected.
88
C
Frequency reference loss Loss of Ref
Closed: Analog frequency reference has been lost.
88
E
Fault
Fault
Closed: Fault occurred.
88
F
Through mode
Not Used
Set this value when using the terminal in the pass-through mode.
88
A
+
Parameters
Multi
Function
7
erminals
<$6.$:$(/(&75,&
6,(3&(<$6.$:$$&'ULYH±=3URJUDPPLQJ0DQXDO
2
7
A
Parameter List