3 Electrical Installation
EN 14
YASKAWA Europe
TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide
Control Circuit
Use wires within the specification listed below. For safe wiring use solid wires or flexible
wires with ferrules. The stripping length or ferrule length should be 6 mm.
EMC Filter Installation
This drive has been tested in accordance with European standards EN61800-3:2004. In order
to comply to the EMC standards, wire the main circuit as described below.
1. Install an appropriate EMC noise filter to the input side.See the list above or refer to the
instruction manual for details.
2. Place the drive and EMC noise filter in the same enclosure.
3. Use braided shield cable for the drive and motor wiring.
4. Remove any paint or dirt from ground connections for minimal ground impedance.
5. Install an AC reactor at drives smaller than 1 kW for compliance with the
EN61000-3-2. Refer to the instruction manual or contact your supplier for details.
EMC Standards Compliant Wiring of Single- and Three Phase Units
Terminal
Screw Size Tightening
Torque N·m
Bare Wire Terminal
Ferrule-Type Terminal
Applicable wire
size mm
2
Recomm.
mm
2
Applicable wire
size mm
2
Recomm.
mm
2
MA, MB, MC
M3
0.5 to 0.6
0.25 to 1.5
0.75
0.25 to 1.0
0.5
S1-S5, SC, +V, A1,
AC, AM
M2
0.22 to 0.25
0.25 to 1.0
0.75
0.25 to 0.5
0.5
N
L1E
N
L1 PE
Wiring distance as
short as possible
Cable shield
grounding clamp
Drive
Cable clamp
Braid shielded motor
cable
EMC
Filter
Grounding Surface
(remove any paint)
Metal plate
Panel or mounting wall
M
Grounding
Surface
(remove any
paint)
Ground shield at
motor side
L3L2 L1
E
L1 PE
Wiring distance as
short as possible
Cable shield
grounding clamp
Drive
Cable clamp
Braid shielded motor
cable
EMC
Filter
Grounding Surface
(remove any paint)
Metal plate
Panel or mounting wall
M
Grounding
Surface
(remove any
paint)
Ground shield at
motor side
L3
L2