Power On
Before turning on the power supply,
• Make sure all wires are connected properly.
• Make sure no screws, loose wire ends or tools are left in the drive.
• After turning the power on, the drive mode display should appear and no fault or alarm
should be displayed.
Normal / Heavy Duty Selection (C6-01)
The drive supports two ratings, Normal Duty and Heavy Duty. Both have different output cur-
rent ratings (refer to the catalog or instruction manual). Set the Duty mode in accordance with
the application.
Reference and Run Source
The drive has a LOCAL and a REMOTE mode. The LED in the LO/RE key indicates the
drive status.
If the drive is operated in the REMOTE mode, make sure that the correct sources for the fre-
quency reference and Run command are set in parameters b1-01/02 and that the drive is in
the REMOTE mode.
Mode
Heavy Duty Ratings (HD)
Normal Duty Rating (ND)
C6-01
0
1
Application
Applications with a constant torque like
extruders, conveyors and cranes. High
overload capability might be needed.
Applications where the torque increases with
the speed like fans or pumps. High overload
tolerance is normally not needed.
Overload capability (OL2)
150% of drive rated current for 60 s
120% of drive rated current for 60 s
L3-02 Stall Prevention dur-
ing Acceleration
150%
120%
L3-06 Stall Prevention dur-
ing Run
150%
120%
Default carrier frequency
10 kHz, 8 kHz
<1> Single-Phase AC200 V CIMR-JCBA0001 ~ BA0006 : 10kHz
Single-Phase AC200 V CIMR-JCBA0010 : 8kHz
Three-Phase AC200 V CIMR-JC2A0001 ~ 2A0006 : 10kHz
Three-Phase AC200 V CIMR-JC2A0008 ~ 2A0020 : 8kHz
Three-Phase AC400 V CIMR-JC4A0001 ~ 4A0011 : 8kHz
Swing PMW
Status
Description
LO/RE LED
LOCAL
The Run/ Stop command and the frequency reference are entered at the operator keypad.
ON
REMOTE
The Run command source entered in parameter b1-02 and the frequency reference
source entered in parameter b1-01 are used.
OFF