4 OPERATION
43
Fig. 22
Braking Unit Power Supply Voltage Selection
(Models CDBR-2045B, -2110B, -4090B, -5037B, -5110B, -5300B,
Indicating Cover Removed)
* Allowable voltage fluctuation is
±
10%
200 V
208 V
220 V
230 V
400 V
380 V
440 V
415 V
460 V
500 V
575 V
575 V
class
200 V
class
400 V
class
Table 3 Power Supply Voltage Selection Connector and Braking Start Voltage
200 V
Class*
Power
Supply
Voltage
Braking Start
Voltage
(PN Bus-bar
Voltage)
400 V
Class*
Power
Supply
Voltage
Braking Start
Voltage
(PN Bus-bar
Voltage)
575 V
Class*
Power
Supply
Voltage
Braking Start
Voltage
(PN Bus-bar
Voltage)
230 V
380 V (TYP)
460 V
760 V (TYP)
575 V
950 V (TYP)
220 V
365 V (TYP)
440 V
730 V (TYP)
–
–
208 V
345 V (TYP)
415 V
690 V (TYP)
–
–
200 V
330 V(TYP)
400 V
660 V (TYP)
500 V
825 V (TYP)
–
–
380 V
630 V(TYP)
–
–