![Yamatake 900 Series User Manual Download Page 125](http://html.mh-extra.com/html/yamatake/900-series/900-series_user-manual_905236125.webp)
Yamatake Corporation
ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter
5-49
Procedure for setting URV (input differential pressure at 100% output)
Step
Description
SFC screen
1
Press the
key.
The current set value for URV
will be displayed.
2
Press the
key.
The SFC asks whether or not to
set the URV based on the current
pressure.
3
Press the
key.
The data will be loaded to the
memory of the transmitter and the
SFC and the new LRV value will
be displayed.
URV F
100%
URV FIT-1234
50 mmH
2
O
G
SET
URV FIT-1234
SET URV?
ENTER
( Yes )
NON-VOL
URV FIT-1234
WORKING...
URV FIT-1234
50 mmH
2
O