ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter
Measured value displaying operation
The following case is explained here:
• Low limit of setting range
: 0KPA
High limit
: 50 kPa
• Input pressure to the transmitter
: 25 kPa
In this case, the output is 50%.
• If the output value does not correctly reflect the input value, check again
the range and calibrate the transmitter. If inappropriate output value per-
sists for the input value, apply troubleshooting procedures ("Chapter 7 :
Maintenance and Troubleshooting").
• If the displayed data value is unstable, adjust the damping time constant
("6-7-10 : Display or Change Damping Time Constant").
Step
Description
SFC screen
4
Press the
and
keys in
that order.
5
Press the
key.
6
After completing measurement, remove the clip of the communication
cable and then switch the process to normal operation.
CAUTION
Securely close the case cover of the transmitter. Take pre-
cautions against moisture ingress into the transmitter body.
Water entering the transmitter will damage the internal ter-
minals and the electronics module.