System 182-XT-4
Relay outputs
6 - 21
ba76027e02
12/2014
6.4.8
Cleaning
Function
The Cleaning function enables the time controlled automatic start of the
sensor cleaning function with the aid of a relay of the DIQ/S 182-XT-4-
PR. The relay controls the DIQ/CHV valve module and switches the
compressed air for the CH sensor cleaning head on or off.
In order to set up the Cleaning function for a relay output, the relay
output must be linked with a sensor (see section 6.2.1).
The assigned relay always works as a closer.
The cleaning cycle consists of Cleaning duration and Adjustment time.
During the cleaning cycle the Clean display flashes. The outputs linked
with this sensor are frozen. The maintenance condition is active.
After the Cleaning duration, the relay is opened. During the following
Adjustment time the outputs remain blocked.
The outputs linked with this sensor are only released when the cleaning
cycle is complete. The Clean display disappears. The maintenance
condition is finished.
Testing the
operativeness
The operativeness of the cleaning system can be tested as follows:
manually open or close the relay with the Manual control function (see
section 6.4.9) and, while doing so, check the behavior of the cleaning
system.
Alternatively, the operativeness of the cleaning system can be tested
by checking the performance of the function at the programmed start
time (reference time ± interval). To perform a test immediately, the
reference time can be set so that the next cleaning cycle will start in a
few minutes (settings: see following table).
Summary of Contents for YSI DIQ/S 182-XT-4-PR
Page 6: ...Contents System 182 XT 4 0 4 ba76027e02 12 2014...
Page 10: ...Overview System 182 XT 4 1 4 ba76027e02 12 2014...
Page 14: ...Safety System 182 XT 4 2 4 ba76027e02 12 2014...
Page 64: ...Installation System 182 XT 4 3 50 ba76027e02 12 2014...
Page 82: ...Operation System 182 XT 4 4 18 ba76027e02 12 2014...
Page 88: ...The SETTINGS menu System 182 XT 4 5 6 ba76027e02 12 2014...
Page 114: ...Relay outputs System 182 XT 4 6 26 ba76027e02 12 2014...
Page 116: ...Maintenance and cleaning System 182 XT 4 7 2 ba76027e02 12 2014...
Page 122: ...What to do if System 182 XT 4 8 6 ba76027e02 12 2014...
Page 134: ...Technical data System 182 XT 4 9 12 ba76027e02 12 2014...
Page 135: ...System 182 XT 4 1 ba76027e02 12 2014...
Page 138: ...Accessories and options System 182 XT 4 11 2 ba76027e02 12 2014...
Page 142: ...Appendix store separately if required System 182 XT 4 13 2 ba76027e02 12 2014...
Page 143: ......