Genyo plus, Additional Installation, Operation and Maintenance Instructions
6.4
Parameters for lack of water
N° Description
Parameters
Unit of
measurement
Default
Additional notes
8
The ART function
•
Ar0, disabled
•
Ar1, enabled
-
Ar0
ART automatic restart function in case of
triggering of the A01 lack of water or
A11 minimum pressure alarm: see The
ART function on page 26
9
A01 lack of water alarm
•
nf0, disabled
•
nf1, enabled and
pump unit STOP
-
nf1
If nf1 is set, activation of the ART
function: see The ART function on page
26
9.1 Delay time till triggering of
alarm A01
•
r01 = 1 s
•
..
•
r5.0 = 5 min
s / min
r05
Can be activated with parameter 9 set
to nf1
Example: r2.5 = 2 min and 50 s
10 A11 minimum pressure
threshold
•
P0.0 = disabled
•
..
•
P8.0 = 8 bar (psi)
bar / psi
0.0
•
Alarm A11 is triggered if the
pressure does not reach the set
value
•
If not set at 0.0, activation of the
ART function: see The ART function
on page 26
10.1 Delay time till triggering of
alarm A11
•
t01 = 1 s
•
..
•
t5.0 = 5 min
s / min
t05
Example: t1.5 = 1 min and 50 s
6.5
Other parameters
N° Description
Parameters
Unit of
measurement
Default
Notes
11 A02 overcurrent alarm
•
c10 = 10%
•
..
•
c30 = 30%
%
c20
Percentage of overload of the current
absorbed by the motor for triggering
the overcurrent alarm
12 Loading the default parameters
•
rS0 = NO
•
rS1 = OK
-
rS0
-
6.6
The ART function
If the alarms A01 and/or A11 are triggered, an attempt is automatically made to restart the
pump unit:
•
After 5 minutes
•
If the alarms persist, every 30 minutes over the next 24 hours.
If the alarms continue to persist, the pump unit remains off with the LED (11) on.
Note: the alarms can be reset at any time by pressing the MENU/ENTER button (6).