en - Original instructions
18
e-SV series - Installation, Operation and Maintenance Manual
If the space available is any less, refer to the technical catalogue.
4.2.2
Permitted positions
Figure 9: Unit position
4.2.3
Installation on concrete foundation
Requirements
The concrete must have a compression resistance of C12/15 and meet the requirements of
exposure class XC1 according to EN 206-1
Sizes must be appropriate for the sizes of the unit support plate. See the section: Fastening
of the unit
The foundation weight must be ≥ 1.5 times the unit weight (≥ 5 times the weight of the unit
if a quieter operation is required)
The surface should be as flat and level as possible.
4.2.4
Fastening of the unit
Figure 10: Fastening of the unit