Parameter number Parameter name
Unit of measurement
Description
P27
Min RPM set
[Min*-ACT set]
G
rpmx10
Minimum pump speed setup.
P28
Ramp 1 [1–250]
G
s
This parameter adjusts the fast acceleration time.
It affects the control of the pump for HCS, MSE and MSY
control modes (also see Par. 6.6.2).
Default: 3 s.
P29
Ramp 2 [1–250]
G
s
This parameter adjusts the fast deceleration time
It affects the control of the pump for HCS, MSE and MSY
control modes (also see Par. 6.6.2).
Default: 3 s.
P30
Ramp 3 [1–999]
G
s
This parameter adjusts the slow acceleration.
It determines:
• The Hydrovar
®
adjustment speed, in case of small
flow rate variations
• The constant outgoing pressure.
The ramp depends on the system being controlled, and
affects the control of the pump in HCS, MSE and MSY
modes (also see Par. 6.6.2).
Default: 35 s.
P31
Ramp 4 [1–999]
G
s
Adjustment of the slow deceleration time (also see Par.
6.6.2).
Other characteristics: as for Ramp 3.
P32
Ramp Speed Min Acceleration
[2.0-25.0]
G
s
This parameter sets the fast acceleration time.
It represents the acceleration ramp used by the
Hydrovar
®
controller until the minimum speed of the
pump is reached (P27).
It affects the control of the pump for HCS, MSE and MSY
control modes (also see Par. 6.6.2).
Default: 2.0 s.
P33
Ramp Speed Min Deceleration
[2.0-25.0]
G
s
This parameter sets the fast deceleration time.
It represents the deceleration ramp used by the
Hydrovar
®
controller for stopping the pump once the
minimum speed of the pump is reached (P27).
It affects the control of the pump for HCS, MSE and MSY
control modes (also see Par. 6.6.2).
Default: 2.0 s.
P34
Speed Min Configuration [STP,
SMI]
G
This parameter defines the operation of the Hydrovar
®
controller once the minimum speed of the pump is
reached (P27):
• STP (STP): once the required pressure is reached
and no further request is made, the pump speed
decreases to the selected P27 value: Hydrovar
®
then keeps running for the selected time interval
(P35), and then stops automatically.
• SNI (SMI): once the required pressure is reached
and no further request is made, the pump speed
decreases to the selected P27 value: Hydrovar
®
continues running at the same speed. This
parameter affects the control of the pump for HCS,
MSE and MSY control modes.
Default: STP
6 System Setup and Operation
Smart Pump Range INSTRUCTION MANUAL
35