Menu number
Description
2.12.5.2
Very high (0 — 30s)
2.12.5.3
High (0 — 30s)
2.13
Leakage stator housing
2.13.1
Sensor
2.13.1.1
FLS/FLS10/FLS20/None
2.13.2
Alarm limits
2.13.2.1
Short circuit (I > 55 mA)
2.13.2.2
Leakage (I > 22 mA)
2.13.2.6
Broken circuit (I < 3 mA)
2.13.3
Alarm action priority
2.13.3.1
Short circuit (Warning/Pump stop/Off)
2.13.3.2
Leakage (Warning/Pump stop/Off)
2.13.3.6
Broken circuit (Warning/Pump stop/Off)
2.13.4
Alarm reset option
2.13.4.1
Short circuit (Manual/Automatic)
2.13.4.2
Leakage (Manual/Automatic)
2.13.4.6
Broken circuit (Manual/Automatic)
2.13.5
Alarm delay
2.13.5.1
Short circuit (0 — 30s)
2.13.5.2
Leakage (0 — 30s)
2.13.5.6
Broken circuit (0 — 30s)
2.14
Leakage junction box
Same structure as for Leakage stator housing (2.13) above
2.15
Leakage inspection chamber/Leakage oil housing (Water in oil)
2.15.1
Input source (sensor)
2.15.1.1
CLS (Water in oil)/FLS10 (Insp. chamber)
• If CLS is selected, the channel name is set to Leak water in oil
• If FLS10 is selected, the channel name is set to Leak. insp. chamber
2.15.2
Same structure as for Leakage stator housing (2.13) above
2.15.5.6
Same structure as for Leakage stator housing (2.13) above
2.16
Vibration
The vibration monitoring channel can be configured for an optional sensor with 4-20 mA output.
2.16.1
Input source
2.16.1.1
4–20 mA/None
2.16.2
Alarm limits
2.16.2.1
Short circuit (I > 22 mA)
2.16.2.2
Very high (Vib > x mm/s)
2.16.2.3
High (Vib > y mm/s)
2.16.2.4
Low (Vib < z mm/s)
2.16.2.5
Very low (Vib < p mm/s)
2.16.2.6
Broken circuit (I < 2 mA)
2.16.3
Action priority
2.16.3.1
Short circuit (Warning/Pump stop/Off)
2.16.3.2
Very high (Warning/Pump stop/Off)
10 Technical Reference
64
MAS 711 Installation, Operation, and Maintenance Manual
Summary of Contents for FLYGT MAS 711