Gnd
+
+
Gnd
+
WS009538A
Sensor
Wire number
Base unit terminal
FLS - Leakage in stator housing
1
13
2
14
Pt100 - Temperature measurement, main bearing
3
8
4
4
Thermal switches - Temperature guard stator windings
5
1
6
2
FLS - Leakage in junction box
7
15
(2)
(14)
Pt100 - Temperature measurement, stator winding phase 1
8
3
(4)
(4)
2. Connect the pump memory.
Function
Wire number
Base unit terminal
RS-485 B
9
38
RS-485 A
10
37
Supply, ground (earth)
11
36
Supply, +12 V
12
35
3. When applicable, attach the cable screen to the ground (earth) terminals in the pump
and in the electrical cabinet.