4. If a portable operator panel is used for a temporary connection, then turn off the
operator panel communication alarm for the base unit.
5. Select the type of Power analyzer from the drop-down menu.
6. Set the Baudrate and Modbus Address to allow communication between the power
analyzer and the base unit.
The default Baudrate is 9600 and default Address is 255. If no changes are made to
the default settings in the power analyzer, then these default settings must be used.
7. Set the Communication alarm status for the power analyzer.
8. Set up communication with a Higher level controller.
For more information, contact the sales and service representative.
9. Click Update.
10.Click Restart to execute the settings.
6.8.6 Set up a monitoring channel
1. Click Setup.
2. Click a channel to set up.
This example shows the Temp stator ph 1 channel:
WS009565A
Right-click and select Refresh to update the current page. To restart the entire web
tool, press F5 or click the Refresh button.
3. Select a sensor in the Sensor drop-down menu.
4. Enter the alarm trip temperature for the warning level, High, and for the pump stop
level, Very high.
5. Select Action priority for each alarm level in the drop-down menus.
6. Select the Reset option. A-alarms must be manually reset, but B-alarms can be allowed
to reset automatically.
7. Enter the alarm Delay.
Use a short delay for Broken circuit and Short circuit to show the errors.
8. Set the Y-axis max value in Graph settings to adjust the presentation of the
measurement results with graphs.
9. When the distance between the pump and the electrical cabinet is more than 30 m
(98.4 ft) long, then enter a value under Compensation for long leads.
For more information, ee
Correct the measurement error due to long leads
10.Click Update.
6 System Setup
MAS 711 Installation, Operation, and Maintenance Manual
27