background image

10

SYSTEM START-UP

1. Make sure all strainer blow down valves are closed 

and capped to prevent accidental burns.

2. Open 1/4 NPT feedback control line shut-off valve.

3. Close inlet valve to main valve.  Open outlet gate 

valve and all equipment drain valves.  Allow system 
to drain completely.

4. Make sure bypass globe valve is tightly closed.

5. Release any actuating force on pilot(s).

Spring

Close pilot valve by equally unscrewing
adjusting nuts to release compression 
on the adjusting spring.

Air

Adjust Air PRV Regulator to 0 psig 
(0.00 bar)

Temperature Set temperature adjusting knob to the 

lowest setting.

NOTE: On 

STPA-300 and STPA-400 pilots,

loosen 

the calibration set screw and move the pointer out 
the way.  Gently turn the adjustment knob clockwise 
until the seat is completely closed.  

This requires that 

the pilot be recalibrated, see "Adjusting Temperature 
Pilots", page 11.

Solenoid

Make sure normally open solenoid is 
open or normally closed solenoid is 
closed.

6. Slightly open steam supply inlet valve. Open only 

enough to allow steam into the system.

7. Apply a small amount of force to the pilots.

Spring

Gradually compress adjusting spring 
by tightening adjusting nuts equally 
until the pilot valve opens.

Air

Adjust Air PRV to allow pressure to 
build slightly until the air pilot valve 
opens.

Temperature

Increase temperature setting a couple 
of degrees at a time.

Pneumatic

Dial in temperature and adjust air 

Temperature

supply pressure to 9 psi (0.62 bar).

8. Allow system to stabilize. 

9. Open steam supply inlet valve slightly more.  A little 

pressure will build on the inlet to the regulator, which 
allows it to open and steam to flow.

10. Close all equipment drain valves.

11. Open supply inlet valve more.

12. Allow system to stabilize.

13.

Check for any leaks.

Allow time for the piping to heat 

up and the drip trap to drain condensate. 

14. Slowly allow pressure to build until the inlet gate 

valve is about half open.  If there are no problems 
open inlet gate valve completely. 

15. Refer to "Adjusting Pilot(s)", page 11, for final pilot 

adjustments.

Never open a reducing valve without positive indication
that the high pressure side is clear of condensate.  Be
sure no one is in area of any open end of pipes when
steam is turned on.  Failure to follow this caution may
result in serious burns.

!

CAUTION

Hearing protection is required if drain valves are open to
atmosphere.  Failure to do so may result in hearing loss.

!

CAUTION

Summary of Contents for Bell & Gossett Hoffman Specialty 2000 Series

Page 1: ...INSTRUCTION MANUAL HS 601I 510549...

Page 2: ...lots only The steam system relief valve opening set point pressure is based on the supply steam inlet pressure to the regulator and must be set as follows 12 Locate temperature regulators close to the...

Page 3: ...ee siphon loop tube petcock and pressure gauge 12 On NPT sized regulator valves install a pipe union M to allow regulator removal for service or replacement 13 Use compressed air or steam to clean pip...

Page 4: ...d directly into the heat exchanger shell 22 Install pressure relief valve V in the downstream piping as required by codes 23 Install a tee fitting W for pressure feedback line 24 Install a siphon loop...

Page 5: ...254 5 7 145 Combination 2 1 2 65 10 6 269 12 8 325 10 0 254 5 9 150 Pilots 3 80 11 2 284 13 1 333 10 0 254 6 4 162 4 100 13 0 330 13 9 353 10 0 254 7 9 200 6 150 16 6 422 14 9 378 10 0 254 9 5 241 1...

Page 6: ...n 6 Install the L fitting from the hardware kit in the tapping at the center of the main valve diaphragm cover Note For steps 7 and 8 trim the length of the copper tubing as required see Tubing Length...

Page 7: ...t 1 When only a temperature pilot is used the outlet tapping port must be reduced Use the 1 8 x 1 4 NPT bushing from the hardware kit in the 1 4 NPT outlet 2 Insert the sensing bulb so the full length...

Page 8: ...from the tank or piping without draining the system When using a dry well coat the bulb with high temperature grease or heat transfer compound to aid heat transfer Make sure that bulb and dry well ar...

Page 9: ...ediate pressures can be interpolated from the chart PNT Air Signal Maximum Steam Pressure from Main Valve Outlet Pressure AP 1A Pressure Pilot AP 4A Pressure Pilot psig Bar psig Bar psig Bar 9 0 62 0...

Page 10: ...radually compress adjusting spring by tightening adjusting nuts equally until the pilot valve opens Air Adjust Air PRV to allow pressure to build slightly until the air pilot valve opens Temperature I...

Page 11: ...making the adjustment 4 Observe the temperature while the system is running 5 Adjust the sleeve until the desired temperature is reached 6 Tighten the dial set screw without turning the adjusting sle...

Page 12: ...e Cause Low inlet pressure Solution Correct supply pressure from the boiler Fully open supply valve Check for upstream blockage Cause The regulator is not properly adjusted Solution Readjust the pilot...

Page 13: ...e air line slowly increase the air pressure on the main valve diaphragms from 0 psig to 30 psig 0 to 2 1 bar Slowly decrease the pressure back to 0 psig 0 bar Repeat this step several times 4 Check fo...

Page 14: ...Valve Seat Lapping Procedures below 9 To continue disassembly Replace plug and stem nut onto stem to prevent damage to diaphragm when air pressure is released Do not fully tighten nut Relieve air pres...

Page 15: ...necessary or replace components to stop any leaks 15 Return the main valve to service Main Valve Diaphragm Replacement A leak in the diaphragm will not allow full steam pressure to build up under the...

Page 16: ...t 7 Connect a 30 psig air supply to the 1 4 NPT pilot INLET port 8 Test for seat and disc leakage Open shut off valve from SIGNAL LINE port Apply air pressure at the INLET port Check for leakage from...

Page 17: ...ding the stem Spring Pilot Seat Lapping Operations Lap sparingly using 500 grit lapping compound and light pressure Heavy grinding may cause galling wide sealing surfaces and a grooved disc all of whi...

Page 18: ...urns 3 Back off air loading pressure 4 If used in conjunction with a temperature pilot set temperature setting higher than the bulb temperature 5 Slightly open the shut off valve in the steam supply t...

Page 19: ...If air is leaking replace the diaphragms AP 4A With a 30 psig air supply to the FEEDBACK tapping the SIGNAL line and IN tapings plugged check for air leakage from the vent hole of the pilot If air is...

Page 20: ...ble well is provided Failure to follow this procedure may result in serious burns CAUTION Temperature pilot bulb will be inserted in the heated fluid Before immersing check compatibility of copper bul...

Page 21: ...ecessary 4 Apply non hardening sealant to bottom plug 4 threads Reassemble pilot 5 Retest pilot y y y yy y yy yy yy yyy y y y yy y y y y y y yy yy yy yy yy 150 F 70 C 60 C 50 C 125 F BELLOWS HOUSING B...

Page 22: ...achieve the desired system temperature 3 Allow system temperature to stabilize at the desired set point temperature and normal load conditions Securely tighten the adjustment knob set screw 4 Rotate...

Page 23: ...lect alteration accident or physical damage c used in a manner contrary to Seller s instructions for installation operation and maintenance d damaged from ordinary wear and tear corrosion or chemical...

Page 24: ...ration and maintenance d damaged from ordinary wear and tear corrosion or chemical attack e damaged due to abnormal conditions vibration failure to properly prime or operation without flow f damaged d...

Reviews: