background image

ADJUSTING PILOTS

Spring/Air Pilots

Adjust spring/air pilot to control the system at desired
pressure.  The system pressure can be set for full steam
or partial steam flow.

Full Steam Flow

– If the spring pilot is adjusted to the

required reduced pressure while the system is running at
full steam flow, then the reduced pressure will rise
approximately 10% when the system is running at low
steam flow.

Partial Steam Flow

– If the spring pilot is adjusted to the

required reduced pressure while the system is running at
5 – 10% of full steam flow, the reduced pressure will fall
(droop) approximately 10% when the system is running at
full steam flow. 

Spring Pilot

1. To increase downstream pressure, increase compres-

sion on the adjusting spring by tightening the adjusting
nuts an equal amount.

2. To decrease downstream pressure, release compres-

sion on the adjusting spring by loosening the adjusting
nuts an equal amount.

Air Pilot

1. To increase downstream pressure, increase the outlet 

pressure from the air regulator.  The pilot should open 
at approximately 9 psig (0.62 bar).

2. To decrease downstream pressure, decrease the out-

let pressure from the air regulator.

Temperature Pilot

1. To increase temperature, loosen Allen lock screw and 

turn adjusting knob counterclockwise.  Then securely 
tighten lock screw.

2. To decrease temperature, loosen Allen lock screw and 

turn adjusting knob clockwise.  Then securely tighten 
lock screw.

3. Once system is running, temperature can be set 

immediately.

• Insert a thermometer in heated fluid.

• When thermometer (in heated fluid) indicates 

temperature is 5˚F (3˚C) below the required 
temperature, turn adjusting knob to lower tempera-
ture setting until steam flow stops.

• The calibrated temperature dial provides an approx-

imate setting.  If the temperature dial reading is 
slightly off from the thermometer reading, the dial 
should be recalibrated, as follows:  

– Loosen the set screw and turn the indicator and 

the mounting collar.  

– Retighten the set screw after making the adjustment.

4. Observe the temperature while the system is running.

5. Adjust the sleeve until the desired temperature is 

reached.

6. Tighten the dial set screw without turning the adjusting

sleeve.

7. When the temperature setting is complete, use the 

Allen head set screw to lock the knob.

Temperature and Spring Pilot Combination

1. With the temperature pilot set to the highest tempera-

ture setting, adjust the spring pilot as noted above.

2. Adjust the temperature pilot according to instructions 

above.

Pneumatic Temperature and Pneumatic Air Pilot
Combination

With this combination, steam pressure is limited rather
than controlled.  The air regulator upstream of the air pilot
and pneumatic temperature pilots controls the air pilot
pressure setting.  Through this combination, the air pilot
limits the steam pressure delivered by the main valve.
Therefore, only the temperature is adjusted.  

1. The air supply to the PNT pilot should be set between 

18 and 36 psig (1.24 – 2.5 bar).

2. Turn the adjusting knob on the pneumatic temperature 

pilot to the approximate desired operating temperature.

3. Insert a thermometer in heated fluid.

4. When the thermometer reaches the desired tempera-

ture, turn the PNT adjusting knob to indicate 9 psig 
(0.62 bar) on the PNT pressure gauge.

5. After conditions have stabilized, make adjustments as 

necessary.

For steam pressure limits, refer to "Maximum Steam
Pressure from Main Valve" chart, page 9.

MAINTENANCE

Schedule

1. Initially every 2-3 days after start-up until system is 

clean.

2. Every 6 months thereafter.

Procedure:

1. Inspect joints for leaks. Tighten bolts to stop leaks.
2. Open blow down valves on strainers.
3. Allow full pressure steam to pass for two minutes.
4. Close the blow down valves.
5. Observe system pressure and readjust if required.

Control of Pressure and/or Temperature

1. Check to see that operating condition initial adjust-

ments are still set.

2. Consider slightly altering the adjustment to see if the 

system responds appropriately.

Solenoid Pilot Actuation

•  Make sure solenoid is functioning properly.

Strainers

•  If screens in Y- strainers or pilot strainers are excessively

dirty, system blowdown should be done once a week.

11

Summary of Contents for Bell & Gossett Hoffman Specialty 2000 Series

Page 1: ...INSTRUCTION MANUAL HS 601I 510549...

Page 2: ...lots only The steam system relief valve opening set point pressure is based on the supply steam inlet pressure to the regulator and must be set as follows 12 Locate temperature regulators close to the...

Page 3: ...ee siphon loop tube petcock and pressure gauge 12 On NPT sized regulator valves install a pipe union M to allow regulator removal for service or replacement 13 Use compressed air or steam to clean pip...

Page 4: ...d directly into the heat exchanger shell 22 Install pressure relief valve V in the downstream piping as required by codes 23 Install a tee fitting W for pressure feedback line 24 Install a siphon loop...

Page 5: ...254 5 7 145 Combination 2 1 2 65 10 6 269 12 8 325 10 0 254 5 9 150 Pilots 3 80 11 2 284 13 1 333 10 0 254 6 4 162 4 100 13 0 330 13 9 353 10 0 254 7 9 200 6 150 16 6 422 14 9 378 10 0 254 9 5 241 1...

Page 6: ...n 6 Install the L fitting from the hardware kit in the tapping at the center of the main valve diaphragm cover Note For steps 7 and 8 trim the length of the copper tubing as required see Tubing Length...

Page 7: ...t 1 When only a temperature pilot is used the outlet tapping port must be reduced Use the 1 8 x 1 4 NPT bushing from the hardware kit in the 1 4 NPT outlet 2 Insert the sensing bulb so the full length...

Page 8: ...from the tank or piping without draining the system When using a dry well coat the bulb with high temperature grease or heat transfer compound to aid heat transfer Make sure that bulb and dry well ar...

Page 9: ...ediate pressures can be interpolated from the chart PNT Air Signal Maximum Steam Pressure from Main Valve Outlet Pressure AP 1A Pressure Pilot AP 4A Pressure Pilot psig Bar psig Bar psig Bar 9 0 62 0...

Page 10: ...radually compress adjusting spring by tightening adjusting nuts equally until the pilot valve opens Air Adjust Air PRV to allow pressure to build slightly until the air pilot valve opens Temperature I...

Page 11: ...making the adjustment 4 Observe the temperature while the system is running 5 Adjust the sleeve until the desired temperature is reached 6 Tighten the dial set screw without turning the adjusting sle...

Page 12: ...e Cause Low inlet pressure Solution Correct supply pressure from the boiler Fully open supply valve Check for upstream blockage Cause The regulator is not properly adjusted Solution Readjust the pilot...

Page 13: ...e air line slowly increase the air pressure on the main valve diaphragms from 0 psig to 30 psig 0 to 2 1 bar Slowly decrease the pressure back to 0 psig 0 bar Repeat this step several times 4 Check fo...

Page 14: ...Valve Seat Lapping Procedures below 9 To continue disassembly Replace plug and stem nut onto stem to prevent damage to diaphragm when air pressure is released Do not fully tighten nut Relieve air pres...

Page 15: ...necessary or replace components to stop any leaks 15 Return the main valve to service Main Valve Diaphragm Replacement A leak in the diaphragm will not allow full steam pressure to build up under the...

Page 16: ...t 7 Connect a 30 psig air supply to the 1 4 NPT pilot INLET port 8 Test for seat and disc leakage Open shut off valve from SIGNAL LINE port Apply air pressure at the INLET port Check for leakage from...

Page 17: ...ding the stem Spring Pilot Seat Lapping Operations Lap sparingly using 500 grit lapping compound and light pressure Heavy grinding may cause galling wide sealing surfaces and a grooved disc all of whi...

Page 18: ...urns 3 Back off air loading pressure 4 If used in conjunction with a temperature pilot set temperature setting higher than the bulb temperature 5 Slightly open the shut off valve in the steam supply t...

Page 19: ...If air is leaking replace the diaphragms AP 4A With a 30 psig air supply to the FEEDBACK tapping the SIGNAL line and IN tapings plugged check for air leakage from the vent hole of the pilot If air is...

Page 20: ...ble well is provided Failure to follow this procedure may result in serious burns CAUTION Temperature pilot bulb will be inserted in the heated fluid Before immersing check compatibility of copper bul...

Page 21: ...ecessary 4 Apply non hardening sealant to bottom plug 4 threads Reassemble pilot 5 Retest pilot y y y yy y yy yy yy yyy y y y yy y y y y y y yy yy yy yy yy 150 F 70 C 60 C 50 C 125 F BELLOWS HOUSING B...

Page 22: ...achieve the desired system temperature 3 Allow system temperature to stabilize at the desired set point temperature and normal load conditions Securely tighten the adjustment knob set screw 4 Rotate...

Page 23: ...lect alteration accident or physical damage c used in a manner contrary to Seller s instructions for installation operation and maintenance d damaged from ordinary wear and tear corrosion or chemical...

Page 24: ...ration and maintenance d damaged from ordinary wear and tear corrosion or chemical attack e damaged due to abnormal conditions vibration failure to properly prime or operation without flow f damaged d...

Reviews: