9  Troubleshooting

9.1  Start up and operation troubleshooting

Table 30: Troubleshooting

Symptom

Possible cause

Test

Solution

Display dark/No function

Missing or open fuses or circuit

breaker tripped

See Pre-startup inspections table

in this manual.

Check the input power source

No power to the LCP

Check the LCP cable for proper

connection or damage

Replace the faulty LCP or

connection cable

Shortcut on control voltage

(terminal 12 or 50) or at control

terminals

Check the 24 V control voltage

supply for terminals 12/13 to 20-

39 or 10 V supply for terminals 50

to 55

Wire the terminals properly

Wrong LCP

Use only LCP #9K651.

Wrong contrast setting

Press [status] + [

]/[

] to adjust

the contrast

Display (LCP) is defective

Test using a different LCP

Replace the faulty LCP or

connection cable

Internal voltage supply fault or

SMPS is defective

Contact supplier

Intermittent display

Overloaded power supply (SMPS)

due to improper control wiring or

fault within the frequency

converter

To rule out a problem in the

control wiring, disconnect all

control wiring by removing the

terminal blocks.

If the display stays lit, then the

problem is in the control wiring.

Check the wiring for shorts or

incorrect connections. If the

display continues to cut out, follow

the procedure for display dark.

Motor not running

Service switch open or missing

motor connection

Check if the motor is connected

and the connection is not

interrupted (by a service switch or

other device)

Connect the motor and check the

service switch

No mains power with 24 V DC

option card

If the display is functioning but no

output, check that mains power is

applied to the frequency converter

Apply mains power to run the unit

LCP Stop

Check if [Off] has been pressed

Press [Auto On] or [Hand On]

(depending on operation mode) to

run the motor

Missing start signal (Standby)

Check 

5–10 Terminal 18 Digital

Input

 for correct setting for

terminal 18 (use default setting)

Apply a valid start signal to start

the motor

Motor coast signal active

(Coasting)

Check 

5–12 Coast inv.

 for correct

setting for terminal 27 (use

default setting)

Apply 24 V on terminal 27 or

program this terminal to No

operation

Wrong reference signal source

Check reference signals: Local,

remote or bus reference? Preset

reference active? Terminal

connection correct? Scaling of

terminals correct? Reference

signal available?

Program correct settings. Check 

3–

13 Reference Site

. Set preset

reference active in parameter

group 

3–1* References

. Check for

correct wiring. Check scaling or

terminals. Check reference signal.

9  Troubleshooting

118

Aquavar

®

 Intelligent Pump Controller INSTRUCTION MANUAL

Troubleshooting

Start up and operation troubleshooting

Summary of Contents for Aquavar IPC

Page 1: ...Aquavar IPC WARNINGS AND ALARMS DOCUMENT INSTRUCTION MANUAL IM299...

Page 2: ...ears for a fault in the input rectifier on the frequency converter Options are programmed at 14 12 Function at Input Imbalance not applicable for single phase drives Check the supply voltage and suppl...

Page 3: ...tor Current is correct 11 Motor thermistor over temp The thermistor might be disconnected Select whether the frequency converter gives a warning or an alarm in 1 90 Motor Thermal Protection Check for...

Page 4: ...0 FC Type 15 41 Power Section 15 42 Voltage 15 43 Software Version 15 45 Actual Typecode String 15 49 SW ID Control Card 15 50 SW ID Power Cord 15 60 Option Mounted 15 61 Option SW Version 16 Short ci...

Page 5: ...ing is issued The frequency converter is still operational but since the brake transistor has short circuited substantial power is transmitted to the brake resistor even if it is inactive Remove power...

Page 6: ...rd The problem could be on the power card on the gate drive card or the ribbon cable between the power card and gate drive card 40 Overload of digital output terminal 27 Check the load connected to te...

Page 7: ...r Speed High Limit RPM the frequency converter will show a warning When the speed is below the specified limit in 1 86 Trip Speed Low RPM except when starting or stopping the frequency converter will...

Page 8: ...ower card temperature The temperature sensor on the power card is either too hot or too cold Check that the ambient operating temperature is within limits Check for clogged filters Check fan operation...

Page 9: ...ller had entered fire mode Cycle power to the unit to remove the warning See the fire mode data in the alarm log on the controller 202 Fire mode limits exceeded While operating in fire mode one or mor...

Page 10: ...shorts or incorrect connections If the display continues to cut out follow the procedure for display dark Motor not running Service switch open or missing motor connection Check if the motor is connec...

Page 11: ...ck brake parameters Check ramp time settings Check parameter group 2 0 DC Brake and 3 0 Reference Limits Open power fuses or circuit breaker trip Phase to phase short Motor or panel has a short phase...

Page 12: ...e makes noise or vibrations at certain frequencies Resonances for example in the motor pump system Bypass critical frequencies by using parameters in parameter group 4 6 Speed Bypass Check if noise an...

Reviews: